30
REVEX
1PH 280A
User’s manual
9.4.3 Advanced Setup Menu
This section describes each item on the advanced setup menu. Use this menu to configure the power
switching, closed loop control of power and adjustable settings for data logging and heater bakeout.
The
password to access this menu is 10.
Parameter Name
Description
Default
Modbus
Address
Par.
Type
Firing Type
Choose the firing mode
3
18
Read
Write
Option
Value
Zero Cross
1
Single Cyc
2
Burst fire
3
Ph Angle
4
Burst StrtR
19
PA SoftS
20
Delay Trig
35
Half Cycle
10
DEFAULT:
Burst Fire
3
Parameter Name
Description
Default
Range
Unit
Modbus
Address
Par.
Type
Min Cycles
Set the minimum number of On
cycles and off cycles for burst firing
8
0 to 999.9
n°
20
Read
Write
Soft Start
Set the duration of the soft start in
increment of 100mSec. The power
controller ramps set to point changes
over the time set here. For more
information see “Firing type” page:
Soft Start with Burst Firing and Soft
Start with Phase Angle
100
(10 sec)
0 to 255
(0 to 25,5
sec)
23
Read
Write
Start Ramp
Set the number of half cycles over
which the power ramps each time
the output turns on
0
0 to 1024
n°
25
Read
Write
Delay
Set the firing delay degrees. Applies
to burst firing with delay trigger
1
1 to 255
°
22
Read
Write
Cycle time
Set the duration of one on-off cycle
in increments of 50mSec.
Applies to zero crossing
60
(3 sec)
0 to 255
0 to 12,75
sec)
24
Read
Write
Содержание REVEX 1Ph 280A
Страница 2: ......