CD Automation srl
MULTIDRIVE-1PH 850A
User’s Manual
51
12.5.2
Output 2: Voltage Output (Terminals 15 and 24 or 16 and 24 - see par. 7.4)
The Voltage output is already configured in line with customer requirements that are defined in the
Order Code. The Order Code is written on the identification label.
However, if you wish to change the Voltage output (ex. from 0÷10V to 4÷20mA) proceed as follows:
Caution:
this procedure must be performed only by qualified persons
Type
Output features
P097
JP15
0
÷
10V
20mA Max
0
A-B
0
÷
20mA
500
Ω
Max
0
B-C
4
÷
20mA
500
Ω
Max
1
B-C
Setting the Output 2 Value:
The parameter P106
allows to set the full scale value to have the maximum output,
for example if you use an indicator with full scale 400V set the parameter P106
= 400.
12.5.3
Output 3: RMS current (Terminals 15 and 25 or 16 and 25 - see par. 7.4)
The RMS current output is already configured in line with customer requirements that are defined in the
Order Code. The Order Code is written on the identification label.
However, if you wish to change the RMS current output (ex. from 0÷10V to 4÷20mA) proceed as
follows:
Caution:
this procedure must be performed only by qualified persons
Type
Output features
P097
JP16
0
÷
10V
20mA Max
0
A-B
0
÷
20mA
500
Ω
Max
0
B-C
4
÷
20mA
500
Ω
Max
1
B-C
Setting the Output 3 Value:
The parameter P108
allows to set the full scale value to have the maximum output,
for example if you use an indicator with full scale 50A set the parameter P108
= 50.
12.5.4
Output 4: Line Frequency Output (Terminals 15 and 26 or 16 and 26 - see par. 7.4)
The Line Frequency output is already configured in line with customer requirements that are defined in
the Order Code. The Order Code is written on the identification label.
However, if you wish to change the Feed_back output (ex. from 0÷10V to 4÷20mA) proceed as follows:
Caution:
this procedure must be performed only by qualified persons
Type
Output features
P097
JP17
0
÷
10V
20mA Max
0
A-B
0
÷
20mA
500
Ω
Max
0
B-C
4
÷
20mA
500
Ω
Max
1
B-C
Setting the Output 4 Value:
The parameter P110
allows to set the full scale value to have the maximum output,
for example if you use an indicator with full scale 100Hz set the parameter P110
= 100.