CD Automation srl
MULTIDRIVE-1PH 850A
User’s Manual
14
6
Installation
Caution:
Don't install near the hot elements or near the units that could give
electromagnetic interferences.
The MULTIDRIVE Thyristor unit must be always mounted in vertical position to improve air cooling on
heat-sink. Maintain the minimum distances in vertical and in horizontal as represented.
When more unit has mounted inside the cabinet maintain the air circulation like represented in figure.
Sometimes is necessary installing a fan to have better air circulation.
6.1
Environmental installation conditions
Ambient temperature
0-45°C at nominal current. Over 45°C use the
derating curve (see par. 8.1)
Storage temperature
-25°C to 70°C
Installation place
Don’t install at direct sun light, where there are
conductive dust, corrosive gas, vibration or water
and also in salty environmental.
Altitude
Up to 1000 meter over sea level. For higher
altitude reduce the nominal current of 2% for each
100m over 1000m
Humidity
From 5 to 95% without condense and ice
Содержание MULTIDRIVE-1PH
Страница 2: ......
Страница 13: ...CD Automation srl MULTIDRIVE 1PH 850A User s Manual 13 5 2 Order Code ...
Страница 25: ...CD Automation srl MULTIDRIVE 1PH 850A User s Manual 25 10 1 Scroll the parameters ...
Страница 60: ...CD Automation srl MULTIDRIVE 1PH 850A User s Manual 60 ENG MULTIDRIVE 1PH_850A ...