CD Automation srl
MULTIDRIVE-1PH 850A
User’s Manual
27
Parameter
Display
Parameter
Name
Contents
UM
Default
Value
UM
Min
Value
DEC
Max
Value
DEC
Min
Value
UM
Max
Value
UM
Par.
Type
L_SP
Setpoint Digital
Value
%
0
0
4095
0
100,0
R/W
Remote Set-point value:
This parameter read only contains the analog setpoint value
present at the terminals 17-18 of the command terminals.
Parameter
Display
Parameter
Name
Contents
UM
Default
Value
UM
Min
Value
DEC
Max
Value
DEC
Min
Value
UM
Max
Value
UM
Par.
Type
r_SP
Remote
Setpoint value
%
0
0
4095
0
100,0
R
Voltage Supply:
This parameter read only contains the voltage value of the power supply.
Parameter
Display
Parameter
Name
Contents
UM
Default
Value
UM
Min
Value
DEC
Max
Value
DEC
Min
Value
UM
Max
Value
UM
Par.
Type
V_Ln
Voltage Supply
V
−
0
4095
0
1000
R
Maximum Output:
This parameter set in % the maximum output voltage.
Parameter
Display
Parameter
Name
Contents
UM
Default
Value
UM
Min
Value
DEC
Max
Value
DEC
Min
Value
UM
Max
Value
UM
Par.
Type
OutN
Maximum Output
%
100,0
2048
4095
50,0
100,0
R/W
Setpoint Ramp Up:
This parameter set the Setpoint Ramp Up.
Parameter
Display
Parameter
Name
Contents
UM
Default
Value
UM
Min
Value
DEC
Max
Value
DEC
Min
Value
UM
Max
Value
UM
Par.
Type
Rp_u
Set Ramp Up
sec
2
0
1000
0
1000
R/W
Setpoint Ramp Down:
This parameter set the Setpoint Ramp Down.
Parameter
Display
Parameter
Name
Contents
UM
Default
Value
UM
Min
Value
DEC
Max
Value
DEC
Min
Value
UM
Max
Value
UM
Par.
Type
Rp_d
Set Ramp Down
sec
2
0
1000
0
1000
R/W
Sample Values and Note
With input 4÷20mA:
Input 4mA P008
= 0
Input 12mA P008
= 50
Input 20mA P008
= 100
Содержание MULTIDRIVE-1PH
Страница 2: ......
Страница 13: ...CD Automation srl MULTIDRIVE 1PH 850A User s Manual 13 5 2 Order Code ...
Страница 25: ...CD Automation srl MULTIDRIVE 1PH 850A User s Manual 25 10 1 Scroll the parameters ...
Страница 60: ...CD Automation srl MULTIDRIVE 1PH 850A User s Manual 60 ENG MULTIDRIVE 1PH_850A ...