INSTALLATION MANUAL
V1.3EN
BLEU
TITANE
RT
I
-EZ
CCEI
p
6
POWER
1~ current
3~ current
1~ cable
3~ cable
3 kW
14 A
5 A
4mm²
2.5mm²
6 kW
27 A
9 A
6mm²
2.5mm²
9 kW
40 A
13 A
6mm²
4mm²
For cable length of 50 m max
All versions of our electric heaters can be powered in single or three-phase. Both
types of electrical power are presented below. In single phase, bridges must be done
on the terminals with wire jumpers provided.
A circuit diagram is presented in the appendix of this manual.
Single
phase
3
phase
A B
T C N 1 2 3 A B T C N 1 2 3
Terminals A and B are used to control the heater from a control panel. If the remote
control is not used, A and B must be bridged.
PRINCIPLE OF OPERATIONS
Regulation
The thermostat controls the heating temperature. The setting value may vary
between 20 and 40 ° C.
Time clock setting
The time clock is useful to limit the heating period in a given time slot of the day .
(i.e. between 14h and 18h).
Indeed, the heat loss of the pool decreases when the water temperature drops. It is
interesting to let the water temperature drop during the non-use (eg at night) and to
anticipate a time of warming-up before the use phase.
The clock allows such a division of heating time and thus save power
consumption. The use of the clock depends on the needs of everyone; it must be
programmed according to individual needs.
Neutral
Phase
Earth
Earth
Neutral
Phases 1,
2 & 3
Filtration
remote
control
* Fils de jonction
Filtration
remote
control
POWER SUPPLY
CABLE
POWER SUPPLY
CABLE