background image

Page | 2 

RSA-161A Manual – Schneider Class 9421 Type L Mechanism - 3" Handle

 

 

1.0 Installation 

 

DANGER! 

Ensure that the equipment to be remotely operated matches the equipment shown and 

described on the cover page.  If the equipment does not match, please contact CBS 

ArcSafe® for more information regarding remote operating applications for the equipment 

in question. 

 

 

Step 1

: First, ensure that the panel surrounding the handle operator is free from any 

obstruction that may interfere with the proper installation of the RSA-161A.  The device will be 

mounted on top of the handle operator and will require several inches of clearance around the 
handle as shown in all directions. 

 

 

 

Step 2:

 Next, ensure that the handle operator on the RSA-161A matches the location of the 

handle to be remotely operated.  If it does not, jog the handle to the correct position either 

manually or the RSO control device. 

 

Step 3: 

The RSA-161A will be mounted over the top of the handle operator and will locate on 

the right edge of the cabinet door/panel.  Place the RSA-161A over the handle and install onto 

the surface of the door/panel.  Check to ensure that all mounting surfaces are sit flush to the 

surface of the door/panel and do not interfere with any protruding labels, placards, or 

hardware.  Ensure that the locator is properly located on the right edge of the door/panel as 

shown in the image on the following page. 