background image

RRS-3 WL 
Installation and Operation

 

5

 

 

2

 

Operation 

A

TTENTION

Please ensure that all cables are clear of moving parts. Failure to do so may result in damage 
to cables and/or actuator. 

A

TTENTION

Please ensure that the batteries to the RSO-IV are fully charged or that the unit is plugged into 

AC power.  

For detailed instructions on the operation of the RSO-IV please see the RSO-IV Manual. 

1.

 

Ensure that the RRS-3 is properly installed. See the In-
stallation section of this manual for detailed instruc-

tions. 

2.

 

Connect the cable from the RSO-IV to the motor control 

box on the RRS-3 

3.

 

Turn the power switch on the RSO-IV to the ON position. 

4.

 

Program the settings for the RRS-3 into the RSO-IV.  

These settings can be found on the placard on the RRS-

3.  For more information on programming the RSO-IV 

please refer to the RSO-IV Technical Manual. 

5.

 

Exit the arc flash boundary. 

6.

 

Once the current limits have been properly set, press 

and release the REMOVE button on the RSO-IV control 

panel or remote pendant to rack the breaker out. 

7.

 

Press and release  the INSTALL button on the RSO-IV 

control panel or remote pendant to rack the breaker in. 

Содержание RRS-3 WL

Страница 1: ...d in the United States of America Reproduction adaptation or translation without prior written permission is prohibited except as is allowed by law RRS 3 WL Installation and Operation 2616 Sirius Road...

Страница 2: ...y install and remove a particular type of circuit breaker safely while stationed safely outside of the arc flash boundary during the potentially dangerous operation The lightweight and compact design...

Страница 3: ...the user will want to pay particular attention to DANGER Ensure that personnel using this equipment are adequately trained in the operation of the switchgear they are planning to work with that they a...

Страница 4: ...s may interfere with the installation of the remote operating equipment These items may need to be removed or repositioned for proper installation 1 Ensure that the breaker is free from any obstructio...

Страница 5: ...RRS 3 to the breaker by turning the handles of the twist magnets 180 degrees clockwise 6 Extract the racking handle from the WL breaker and pull it out fully until it clicks and locks into place Ensur...

Страница 6: ...Ensure that the breaker s racking handle fits properly into the racking operator on the RRS 3 as shown If it does not align slowly rotate the adapter on the RRS 3 until it aligns properly with the han...

Страница 7: ...this manual for detailed instruc tions 2 Connect the cable from the RSO IV to the motor control box on the RRS 3 3 Turn the power switch on the RSO IV to the ON position 4 Program the settings for the...

Страница 8: ...c situation Note A inch drive torque wrench will be required to perform this adjust ment 1 First remove the racking tool adapter from the RRS 3 by pushing in the locking pin at the base of the adapter...

Страница 9: ...blems which could lead to an arc flash If the RRS does not seem to have enough torque first double check that the breaker is operat ing properly before racking out by hand 5 Take the the higher of the...

Страница 10: ...n the frame The RRS 3 comes pre adjusted from the factory for it s breaker so these adjustments should not normally need to be made To adjust the vertical positioning of the slide assembly 1 Loosen th...

Страница 11: ...on 9 To adjust horizontal positioning of the slide assembly 1 Loosen the two bolts on the angle brackets above the slide assembly as shown 2 Next move the assembly left or right as required 3 Re tight...

Страница 12: ......

Страница 13: ...RRS 3 WL Installation and Operation 11 Notes...

Страница 14: ...RRS 3 WL Installation and Operation 12...

Страница 15: ......

Страница 16: ...that they are correctly stationed outside the arc flash boundary and that they comply with all applicable Federal State Local and In house safety regulations and procedures Attention should be given t...

Отзывы: