E
E
P
P
by
30
En
TRMS voltage measurement
• Voltage types:
AC
,
DC
,
AC+DC
.
• Bandwidth: signal
45Hz
to
66Hz
+ harmonics up to
1Khz
.
General characteristics
Central unit
Controller
Operating temperature
-10 to +45°C
-10 to +45°C
Storage temperature
-25 to +70°C
-25 to +70°C
Maximum relative humidity
80%
80%
Dimensions
244.5 x 132.6 x 85.8
231.1 x 56.9 x 36
Weight of the device
(with batteries)
907.45 g
289.70 g
Pollution degree
2
2
Installation category
III 600V
III 600V with cap
II 600V without cap
IP, IK
IK 06 IP 40
IK 06 IP 40
Battery type
4 * Alkaline LR06
2 * Alkaline LR06
Fuse type
500V 500mA 6.3x32mm
Breaking current 50 kA
NA
Double insulated
Yes
Yes
Electrical safety
EN 61010-1
EN 61010-1
EMC
EN 61326-1 61326-2
EN 61326-1 61326-2
Wireless
EN 300220-1 et -2
EN 300220-1 et -2
Wireless device category
CAT 2
CAT 2
Wireless power
≤
10mW
≤
10mW
Wireless standard
EN 300220-1 et -2
Wireless frequency
Band ISM433 MHz (433.075 à 434.775)
Altitude
< 2000 m
< 2000 m
Voltage range
±1V to ±99.99 V AC or DC
±100V to ±999 V AC or DC
Resolution
0.01 V
0.1
V
Accuracy
2% ± 2 digits
2% ± 2 digits
MENU