Messenger W
User Manual
12
9M02-7000-A001-EN
Version A
Channel
Number
Channel Name Type
Description
5
User DIN3
Digital
If SWX4-3 closed:
0 = input open
1 = input voltage < 1 VDC
If SWX4-3 open:
1 = input open
0 = input voltage > 3 VDC
6
User DIN4
Digital
If SWX4-4 closed:
0 = input open
1 = input voltage < 1 VDC
If SWX4-4 open:
1 = input open
0 = input voltage > 3 VDC
30
User DOUT1
Digital
State of digital output 1
0 = not energized
1 = energized
Start Analog Channels (data values are floating point, precision is user configurable)
62
User Analog
Analog
Onboard analog input, 10-bit ADC can be configured
for 0-1 VDC, 0-5 VDC, 0-10 VDC, or 0-20 mA
154
Daily Flow
Volume
Derived
Accumulated flow volume for the day
(flow rate from ADC input)
155
Running
Flow Volume
Derived
Accumulated flow volume since last volume reset
(flow rate from ADC input)
4.2 Channel Data
All values read from physical IO or from a Modbus slave device are continually updated and tested as defined by
the configuration parameters. For each channel, based on its type (analog or digital), there is a basic set of data
collected. For purposes of discussion, the term “not normal” is used to indicate an analog value that has violated a
limit threshold or a digital value that does not match its configured ‘normal’ state.
Basic Data Set –
For the analog channel:
•
Current value
•
Max/min values (daily and trip)