Model 8311HP or 8311LP

Back Pressure/Relief 

Regulator

System

Recommended Piping Schematic 

for  Models 8311HP/LP

INSTALLATION, OPERATION & MAINTENANCE MANUAL

IOM-8311HP/LP-BASIC

             12-13

1.  An inlet block valve should always be installed.

2.  If service application is continuous such that shut down 

is not readily accomplished, it is rec om mend ed that 
an inlet block valve, outlet block valve, and a manual 
bypass valve be installed.

3.  Pipe unions are recommended for NPT screwed in stal -

la tions to allow removal from piping.

4.  An inlet pressure gauge should be located ap prox i mate ly 

ten pipe diameters upstream, and within sight.

5.  All installations should include a upstream re lief device 

if the inlet pressure could exceed the pressure rating of 
any upstream equipment or the maximum inlet pres sure 
rating of the unit.

6.  Clean the piping of all foreign material including chips, 

welding scale, oil, grease and dirt before in stall ing the 
regulator.  Strainers are recommended.

l.  DESCRIPTION AND SCOPE

The Model 8311 is a high capacity back pressure / relief regulator with double seat design used to control upstream (inlet or P

1

pressure.  Sizes are 1-1/2" (DN40), 2" (DN50), 2-1/2" (DN65), 3" (DN80) and 4" (DN100).  With proper trim utilization, the unit 
is suitable for liquid, gas eous, or steam service.  Refer to Tech ni cal Bulletin 8311-TB for design conditions and selection recom-
mendations.

This is not a safety device and must not be sub sti tut ed for a code 
approved pressure safety relief valve or rupture disc.

SECTION II

II. INSTALLATION

7.  In placing thread sealant on pipe ends prior to en-

 gage ment, ensure that excess material is re moved and 
not allowed to enter the regulator upon start-up.

8.  Flow Direction:  Install so the 

fl

 ow direction match es the 

arrow on the body.  Install an external sensing line (1/2" 
O.D. tubing min i mum) from the 3/8" NPT con nec tion  
to a point up stream, pref er a bly at gauge location.  If 
regulator pipe line is ex pand ing to a larger pipe line, 
always connect sensing line to the larger pipe line.

9.   For best performance, install in well drained hor i zon tal 

pipe, properly trapped, if a steam service ap pli ca tion.

MODELS  8311HP AND 8311LP

BACK PRESSURE / RELIEF REG U LA TORS

SECTION l

          

CAUTION

Installation of adequate overpressure pro tec tion is recom-
mended to pro tect the reg u la tor from overpressure and 
all down stream equip ment from damage in the event of 
regulator failure.

WARNING

The maximum inlet pressure is equal to 1.3 times the 
larger number of the stated range spring on the nameplate, 
and is the recommended “upper op er a tive limit” for the 
sensing diaphragm. Higher pres sures could damage the 
diaphragm. (Field hy dro stat ic tests frequently destroy 
diaphragms. DO NOT HYDROSTATIC TEST THRU AN 
IN STALLED UNIT; ISOLATE FROM TEST.)

CAUTION

Содержание 8311LP

Страница 1: ...uid gaseous or steam service Refer to Technical Bulletin 8311 TB for design conditions and selection recom mendations This is not a safety device and must not be substituted for a code approved pressu...

Страница 2: ...til fully open 7 Observing the inlet upstream pressure gauge rotate the adjusting screw clockwise CW slowly until the inlet pressure begins to rise Rotate CW until the desired setpoint is reached 8 Co...

Страница 3: ...de optimum free vertical movement 8 Pryloosepressureplate 22 fromdiaphragm s 20 andremoveboth Inspecttoensurenodeformation due to over pressurization If deformed replace NOTE 1 Not removing the pusher...

Страница 4: ...ttern that allows bottom flange 3 to be brought up evenly Refer to Step 11 for recommended torques Regulator Size Torque Bolt Size 1 1 2 2 50 ft lbs 68 N M 1 2 3 4 50 ft lbs 68 N M 5 8 NOTE Never repl...

Страница 5: ...ange Contact factory adjusting screw does not allow bringing pressure to a stable and proper level C Too much build C1 Review build expected C2 Contact factory D Restricted diaphragm movement D Ensure...

Страница 6: ...tminimum parts required for inspection and rebuild Soft Goods Kit Those in column B include minimum trim replacement parts needed plus those Soft Goods parts from column A If the BOM is not available...

Страница 7: ...aphragm 21 Diaphragm Gasket 22 Pressure Plate 24 Pressure Plate Nut 25 Diaphragm Ring 27 Spring Button 28 Range Spring 29 Flange Bolt 30 Flange Nut 31 Nameplate 32 Adjusting Screw or Handwheel Assembl...

Страница 8: ...hco com Printed in U S A IOM 8311HP LP Cashco GmbH Handwerkerstrasse 15 15366 Hoppegarten Germany PH 49 3342 4243135 Fax No 49 3342 4243136 www cashco com Email germany cashco com Cashco do Brasil Ltd...

Отзывы: