24
1000
200 | 250
42
56
54
57
62
55
32
19
65
49
2000
200 | 250
58
65
55
51
53
44
22
14
66
49
3000
200 | 250
58
67
48
51
51
43
23
14
66
48
4500
200 | 250
64
66
54
59
61
51
30
22
69
51
6000
200 | 250
68
64
50
55
56
45
24
18
69
51
8000
200 | 250
57
52
56
64
68
59
37
29
71
51
10000
200 | 250
74
70
56
61
61
50
29
21
76
56
13000
200 | 250
71
67
53
58
59
48
27
21
73
54
17000
200 | 250
58
53
57
65
69
60
38
32
71
51
21500
200 | 250
60
66
61
63
69
57
40
34
73
52
1020
1020
1020
1020
1020
1020
1020
1020
1020
1020
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
010
020
030
045
060
080
100
130
170
240
010
020
030
045
060
080
100
130
170
240
010
020
030
045
060
080
100
130
170
240
EN
11. SOUND DATA
The noise level of units is basically due to the fan rotation speed.
Obviously, with the same air flow rate, the fan speed will be lower if the required static pressure is low, while it will be higher (and
therefore noisier) if the required static pressure is higher.
11.1 Noise levels
The table below shows the sound levels of the units at the nominal working conditions:
Octave band (Hz)
Lw
Lp
MOD.
Nominal
air flow
E.S.P.
Ret. | Supp.
63
125
250
500
1K
2K
4K
8K
dB(A)
dB(A)
m
3
/h
Pa
dB
dB
dB
dB
dB
dB
dB
dB
Lw: sound power level calculated in accordance with EN 3744
Lp: sound pressure level measured in free field at 1 m from the unit, directionality factor Q=2, according to EN 3744 with ducted unit.
11.2 Sound attenuators reduction
The sound attenuators are of sound-absorbing baffles type. They are suitable for reducing the noise that propagates through the
ventilation systems in the aeraulic ducts.
To check the sound absorpion data to the various octave band frequencies, please refer to the our selection
software.
The sound attenuators are supplied in a dedicated section external to the base unit, thus increasing the total length of the unit
(depth and height of the section remain the same as the base unit).
Below are the additional section lengths according to size and profile, to be taken into account when calculating the final
length of the unit.
Additional dimensions sound attenuator section
(60 mm profile)
MOD.
Length
[mm]
Additional dimensions sound attenuator section
(50 mm profile)
MOD.
Length
[mm]
Содержание QUANTICA EEC
Страница 55: ...55 EN NOTES...