background image

A

DJUSTING

 F

LOODLIGHT

 T

IME

 

See Figure 6 on page 10. The amount of time the floodlights remain on after the system is tripped 

may be adjusted from 15 seconds to 15 minutes. The normal floodlight time is 5-10 minutes.  

To set the floodlight time, remove the photocell wire from terminal No. 7. Push the TRIP-TEST 

button. Measure from the moment the floodlight relay clicks on to the moment it clicks off. Adjust 
potentiometer "B" (clockwise for time increase) and repeat until desired time is achieved. Reconnect 
the photocell wire to terminal No. 7. 

A

DJUSTING

 P

HOTOCELL

 S

ENSITIVITY

 

See Figure 6 on page 10. Photocell sensitivity determines the level of outdoor light at which the 

lights are allowed to come on. The factory sets the floodlights to come on at dusk.  

To set the photocell sensitivity, make all adjustments at the precise moment when the amount of 

daylight is visible at which time you want the floodlights to come on. Adjust potentiometer "D" 
counter clockwise in very small increments and push the TRIP-TEST button after each adjustment 
(see page 3). Stop adjusting at the point where the floodlight relay clicks on. The floodlights will be 
allowed to turn on at that same daylight level from then on.  

A

DJUSTING

 P

ROBE

 S

ENSITIVITY

 

See Figure 6 on page 10. Probe sensitivity is set at the factory and does not usually need to be 

adjusted. Factory setting allows a single standard probe to cover a 12 foot wide driveway when 
installed beside it (see "Installing CT-6 Probe and Cable" on page 5). Increasing the sensitivity 
above the factory setting is not recommended unless the probe is located in a low sensitivity area. 

When the probe is placed in the center of a driveway that is 18 feet wide or less, the sensitivity may 

be decreased considerably, allowing the probe to be installed close to highway traffic or power lines.  

To adjust probe sensitivity, turn the potentiometer "G" clockwise to increase, counter-clockwise to 

decrease. A typical setting should be such that the CF-2C reliably detects a small car going 5 MPH. 
You may increase sensitivity if necessary. Be aware, increasing sensitivity may cause false alarms. 

A

DJUSTING

 T

RANSIENT

 S

UPPRESSOR

 

See Figure 6 on page 10. The factory setting for the transient suppressor circuit potentiometer "H" 

is in the "on" position (fully clockwise). In this setting, short duration transient signals will be ignored. 
With the circuit activated, false alarms from lightning will be reduced. 

Note: if the probe sensitivity cannot be properly set as described in the "Adjusting Probe 

Sensitivity" section (above), turn off the transient suppressor by adjusting potentiometer "H" fully 
counter-clockwise.  

F

IELD

 T

ROUBLESHOOTING

 

Cartell does not provide schematic diagrams or service manuals for our products. However, we try 

our best to provide technical support through our 

(800) 878-7829 

number and fast repair service for 

our products. Before calling

,

 refer to the “

SPECIAL NOTE

” sections under the following headings: 

Initial power-up and exit delay, page 2

Purchasing ground rod, page 3

Sensor probe check of existing installations, page 4

Probe system supervision, page 6

Using Probe Fault Mode to test circuit board, page 6

11 

www.GateOpenerSafety.com  |  (800) 878-7829  |  [email protected]

Содержание DRIVEGUARD ULTRA

Страница 1: ...125 VAC Floodlight relay can be used to switch on up to 1800 watts of lights Floodlight relay can be used to operate coil of multi contact relay or contactor and thus operate many banks of lights Floodlight relay can be used to switch low voltage devices such as line carrier interface modules Photocell daytime lockout keeps lights from coming on during daylight hours Adjustable photocell sensitivi...

Страница 2: ... System Supervision 6 Using Probe Fault Mode for Testing 6 SD 6 Short Driveway Probe System 7 Connecting Other Sensing Devices to Control Unit 7 Installing Photocell Block 7 Installing Sounders Annunciators 7 Adjusting CT A1 Exit Delay 9 Adjusting Sounder Annunciator Time 10 Adjusting Re Trigger Hold Off 10 Adjusting Floodlight Entry Delay Time 10 Adjusting Floodlight Time 11 Adjusting Photocell S...

Страница 3: ...lectrical or R F noise Install control unit in a sealed box when used in a corrosive atmosphere such as an animal barn or chemical plant Install in a sealed weather proof box when installed outside The weatherproof box must have a thermostatically controlled light bulb or heater to maintain temperatures above freezing Drastic changes in temperature cause condensation on the board and will make the...

Страница 4: ...tery should be used DO NOT use a gelled electrolyte battery Recommended batteries are made by Yuasa Battery Inc Gates Energy Products Inc Eagle Picher Industries Inc Panasonic Industries Co or G S Battery Inc The positive RED lead connected to terminal No 4 and the negative BLACK lead connected to terminal No 5 are provided for connections to the battery When an outside DC power source is being us...

Страница 5: ... set of Form C relay contacts on terminals No 11 12 and 13 These contacts may be used to trip an alarm panel trip a dialer trip a line carrier interface trigger a transmitter or trip a door bell Potentiometer F controls the relay time of these contacts INTEGRATING WITH A SECURITY OR HOME AUTOMATION PANEL See Figure 2 on page 2 The CF 2C has a floating dry relay contact that can be used in conjunct...

Страница 6: ...ld decide to take the circuit board out of its case not advisable DO NOT bury the probe within 6 to 10 feet of a buried power or telephone line DO NOT bury the probe within 6 to 10 feet of a buried invisible dog fence DO NOT bury the probe within 10 feet of a natural gas line DO NOT bury the probe within 20 feet of a power pole with a transformer attached to it DO NOT bury the probe within 100 fee...

Страница 7: ...inch PVC pipe under the driveway as described above Then pour cement or asphalt the drive Insert the probe and cable after landscaping is complete to prevent possible damage to the cable The probe cable is direct burial and does not require conduit Depth of burial depends on lawn conditions In cultured grass bury the cable 2 3 inches deep The root system of the grass will capture the cable for lif...

Страница 8: ...2C went into PROBE FAULT mode that would indicate when the wire was damaged In high security areas this feature is extremely valuable If the RED and BLACK probe wires are shorted together the PROBE FAULT SYSTEM will not go into alarm mode and the CF 2C control will not respond to the probe or the TRIP TEST button If the circuit board has stopped working use the instructions in USING PROBE FAULT MO...

Страница 9: ...of the photocell should be at the top and the screw terminals situated so that the wires will be connected from the top Using a 2 wire shielded cable connect the two primary wires to the screw terminal on the photocell The shield drain wire does not connect to anything on the photocell Cut it off there At the CF 2C control unit connect the SHIELD drain wire to terminal No 16 and the two primary wi...

Страница 10: ... quick succession in less than one second The LED will begin blinking and continue blinking the duration of the mute cycle To restore sound hold PROG button down and push the DOWN button two times in quick succession as before The LED will stop blinking when sound is restored to its previous setting ADJUST TIMING OPTIONAL The default timing for the CT A1 is set at the control unit see Adjusting So...

Страница 11: ...UNDERS See Figure 2 on page 2 Connect the RED lead to the terminal marked SON or on the sounder Connect the BLACK lead to GND or on the sounder At the control unit test the resistance RED to BLACK as noted above If resistance proves correct at the control unit connect the RED lead to terminal No 14 Twist the BLACK lead to the SHIELD wire and connect to terminal No 15 ADJUSTING CT A1 EXIT DELAY See...

Страница 12: ...longer hold off period of time Repeat until the desired hold off time is achieved Re attach the RED probe wire ADJUSTING FLOODLIGHT ENTRY DELAY TIME See Figure 6 This function can be used to delay activation of the floodlight timer after the CF 2C is tripped Adjustment time is from 1 second up to 2 minutes For long driveways or if the exact location of the probe is to be concealed for security rea...

Страница 13: ...sensitivity above the factory setting is not recommended unless the probe is located in a low sensitivity area When the probe is placed in the center of a driveway that is 18 feet wide or less the sensitivity may be decreased considerably allowing the probe to be installed close to highway traffic or power lines To adjust probe sensitivity turn the potentiometer G clockwise to increase counter clo...

Страница 14: ...or it will not splice Improper cable splices will cause false alarms To insure a proper splice follow the instructions below Two items are necessary when splicing both available from Cartell First a two wire shielded direct burial cable unshielded cable and PVC jacketed cable will not give proper splices Second an underground splice kit made by 3M part 82 F1 Cartell s part number is CA 1 The follo...

Страница 15: ...NICAL SPECIFICATIONS CF 2C CONTROL UNIT TECHNICAL SPECIFICATIONS CT 6 PROBE 13 TEMPERATURE RANGE 40 F 250 F PROBE DIMENSIONS 16 1 2 in x 1 3 8 in diameter WEIGHT 3 5 lbs with 100 cable OTHER 500 to 800 ohms coil resistance depending on length of cable POWER REQUIRED 12 VAC or 12 15 VDC STANDBY CURRENT 35 mA ALARM CURRENT 180 mA max with 1 FC 9 or 1 CT 8 RELAY CONTACT RATING Double Pole Double Thro...

Отзывы: