Appendix A: Network Points List for WSHP Open
WSHP Open v3
CARRIER CORPORATION ©2021
Integration Guide
All rights reserved
40
BACnet
Modbus
Point Name
Point
Access
Units
Default
Value
BACnet Point Name
BACnet
Object ID
Modbus
Register
Type
Modbus
Register #
System Mode
R
(1) Off
(2) Fan Only
(3) Economize
(4) Cooling
(5) Heating
(6) Cont Fan
(7) Test
(8) Start Delay
run_status
MSV:2002
Input
Register
(Signed)
1
Occ Relative Humidity
Setpoint
R/W
%rh
60
occ_dehum_stpt
AV:3011
Holding
Register
(Float)
83
Optimal Start
R/W
hr
1
optm_start
AV:9026
Holding
Register
(Float)
147
Smoke Detector
Contact
R
(0) Alarm / Open
(1) Normal /
Closed
smk_detect
BV:1004
Discrete
Input
1
Effective Cool
Setpoint
R
°F
eff_cl_stpt
AV:3005
Input
Register
(Float)
55
Setpoint
R/W
°F
unocc_cl_stpt
AV:3003
Holding
Register
(Float)
15
Heating Lockout
Temperature
R/W
°F
65
oat_ht_lockout
AV:9003
Holding
Register
(Float)
69
Power Fail Restart
Delay
R/W
seconds
180
start_delay
AV:9007
Holding
Register
(Float)
127
Setpoint
R/W
°F
occ_cl_stpt
AV:3001
Holding
Register
(Float)
9
Filter Service Alarm
Timer
R/W
hr
600
filter_service_hrs
AV:2019
Holding
Register
(Float)
67
Indoor Air Quality CO2
(ppm)
R
ppm
iaq
AV:1009
Input
Register
(Float)
73
Setpoint
R/W
°F
unocc_ht_stpt
AV:3004
Holding
Register
(Float)
17
System Outdoor Air
Temperature
R/W
°F
-999
system_oat
AV:1901
Holding
Register
(Float)
119
System Setpoint
Adjustment
R/W
°F
-999
system_stpt_adj
AV:1913
Holding
Register
(Float)
53
Reset Filter Alarm
R/W
(0) Off
(1) On
(0) Off
filter_rntm_clr
BV:7517
Coil
22
Effective Heat
Setpoint
R
°F
eff_ht_stpt
AV:3006
Input
Register
(Float)
57
Maximum Heating
SAT
R/W
°F
110
sat_ht_max
AV:83004
Input
Register
(Float)
41
Содержание WSHP Open v3
Страница 6: ...Introduction WSHP Open v3 CARRIER CORPORATION 2021 Integration Guide All rights reserved 2 ...
Страница 56: ......
Страница 57: ......
Страница 58: ...CARRIER CORPORATION 2021 Catalog No 11 808 539 01 6 15 2021 ...