Appendix A: Network Points List for WSHP Open
WSHP Open v3
CARRIER CORPORATION ©2021
Integration Guide
All rights reserved
38
Network points list for BACnet and Modbus
BACnet
Modbus
Point Name
Point
Access
Units
Default
Value
BACnet Point Name
BACnet
Object ID
Modbus
Register
Type
Modbus
Register #
Aux Heat Control
Setpoint
R
°F
aux_heat_stpt
AV:3014
Input
Register
(Float)
161
Auxiliary Heat Output R
%
aux_heat_output
AV:2021
Input
Register
(Float)
163
Cooling Lockout
Temperature
R/W
°F
45
oat_cl_lockout
AV:9002
Holding
Register
(Float)
43
Damper Output
R
%
oa_dpr_pos
AV:2022
Input
Register
(Float)
169
Leaving Source Water
Temp
R
°F
cwl_temp
AV:1017
Input
Register
(Float)
167
Vent Dmpr Pos / DCV
Min Pos
R/W
%
20
econ_min
AV:4005
Holding
Register
(Float)
131
Outdoor Air
Temperature
R
°F
oa_temp
AV:1003
Input
Register
(Float)
87
Override Time
Remaining
R
min
ovrde_time
AV:2016
Input
Register
(Float)
93
Setpoint
R/W
°F
occ_ht_stpt
AV:3002
Holding
Register
(Float)
19
Setpoint Adjustment
R
°F
stpt_adj
AV:1006
Input
Register
(Float)
99
Space Temperature -
Prime Variable
R
°F
space_temp
AV:2007
Input
Register
(Float)
107
Supply Air
Temperature
R
°F
sa_temp
AV:1008
Input
Register
(Float)
109
System Space AQ
R/W
no units
-999
system_iaq
AV:1903
Holding
Register
(Float)
149
System Space RH
R/W
%
-999
system_rh
AV:1904
Holding
Register
(Float)
151
System Space
Temperature
R/W
°F
-999
system_spt
AV:1902
Holding
Register
(Float)
123
Unocc Relative
Humidity Setpoint
R/W
%rh
95
unocc_dehum_stpt
AV:3012
Holding
Register
(Float)
129
Water Economizer
Control Setpoint
R
°F
h2o_econ_ctrl_stpt
AV:3015
Input
Register
(Float)
171