COOLING CAPACITIES (cont)
LEGEND
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:
t
lwb
= Wet-bulb temperature corresponding to enthalpy of air leav-
ing indoor coil (h
lwb
)
Where: h
ewb
= Enthalpy of air entering indoor coil
3. SHC is based on 80 F edb temperature of air entering indoor coil.
Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.
Interpolation is permissible.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).
INSTANTANEOUS AND INTEGRATED HEATING RATINGS
See Legend and Notes on page 97.
50HJQ016 (15 Tons)
Temp (F)
Outdoor
Entering Air
(Edb)
Indoor Entering Air — Cfm/BF
4500/0.06
5250/0.08
6000/0.10
6750/0.10
7500/0.12
Indoor Entering Air — Ewb (F)
72
67
62
72
67
62
72
67
62
72
67
62
72
67
62
75
TC
210.0
192.0
173.4
216.0
196.6
178.4
220.0
202.0
182.2
222.0
204.0
185.6
224.0
206.0
190.2
SHC
100.6
125.2
148.2
106.0
134.0
160.6
110.6
143.0
172.2
115.0
151.2
183.2
120.2
158.2
190.0
kW
13.58
13.12
12.66
13.76
13.28
12.84
13.88
13.44
12.98
13.96
13.52
13.10
14.02
13.60
13.26
85
TC
202.0
183.0
164.4
208.0
187.8
169.0
212.0
191.4
172.8
212.0
194.0
177.2
214.0
195.8
182.2
SHC
98.0
121.8
144.2
103.8
131.2
156.4
109.0
140.0
168.6
112.0
148.0
177.0
116.2
155.6
182.2
kW
14.86
14.32
13.78
15.08
14.52
13.98
15.22
14.66
14.14
15.26
14.78
14.30
15.34
14.86
14.50
95
TC
192.4
173.2
155.0
196.2
177.8
159.2
200.0
180.8
163.4
202.0
183.4
169.0
204.0
185.4
174.2
SHC
94.8
118.0
140.0
100.2
127.4
152.6
105.6
136.4
163.4
110.6
144.8
169.0
114.2
153.2
173.8
kW
16.16
15.52
14.88
16.32
15.72
15.10
16.48
15.88
15.30
16.62
16.00
15.54
16.64
16.12
15.76
105
TC
182.0
163.0
145.0
186.4
167.0
149.4
188.6
170.0
155.4
191.0
172.2
160.8
193.0
173.8
165.2
SHC
91.0
114.2
135.2
96.8
123.6
147.6
101.8
132.6
155.2
107.2
141.2
160.6
112.2
149.6
165.2
kW
17.36
16.64
15.92
17.58
16.86
16.16
17.70
17.04
16.48
17.84
17.18
16.74
17.94
17.28
16.96
115
TC
171.2
152.4
134.8
175.0
156.2
140.6
177.8
158.8
146.8
179.4
160.8
152.2
179.6
162.2
156.4
SHC
87.4
110.2
130.8
92.6
119.4
140.6
98.8
128.2
146.8
103.6
136.8
151.8
107.2
144.6
156.2
kW
18.54
17.72
16.90
18.76
17.94
17.24
18.94
18.12
17.60
19.02
18.28
17.90
19.04
18.38
18.16
125
TC
159.4
141.2
125.0
162.8
143.8
132.0
165.6
147.0
137.8
166.6
148.8
143.0
168.2
150.0
146.8
SHC
83.6
105.8
125.0
89.0
115.0
131.8
94.4
123.6
137.8
99.8
132.2
142.8
105.0
139.6
146.6
kW
19.64
18.74
17.88
19.86
19.00
18.34
20.00
19.12
18.72
20.20
19.28
19.00
20.20
19.40
19.28
BF
—
Bypass Factor
Edb —
Entering Dry-Bulb
Ewb —
Entering Wet-Bulb
kW
—
Compressor Motor Power Input
SHC —
Gross Sensible Heat Capacity (1000 Btuh)
TC
—
Gross Total Capacity (1000 Btuh)
t
ldb
= t
edb
–
sensible capacity (Btuh)
1.10 x cfm
h
lwb
= h
ewb
–
total capacity (Btuh)
4.5 x cfm
BYPASS
FACTOR
(BF)
ENTERING AIR DRY-BULB TEMP (F)
79
78
77
76
75
under 75
81
82
83
84
85
over 85
Correction Factor
.05
1.04
2.07
3.11
4.14
5.18
Use formula
shown below.
.10
.98
1.96
2.94
3.92
4.90
.20
.87
1.74
2.62
3.49
4.36
.30
.76
1.53
2.29
3.05
3.82
50HJQ004 (3 Tons)
Return
Air
(F db)
Cfm
(Standard
Air)
Temperature Air Entering Outdoor Coil (F db at 70% rh)
–20
–10
0
10
17
30
40
47
50
60
55
900
Cap.
10.3 9.47 13.7 12.6 16.8 15.4 20.1 18.5 23.5 21.3 27.6 24.2 31.9 31.9 35.1 35.1 36.3 36.3 40.3 40.3
kW
1.48
1.58
1.66
1.75
1.85
1.97
2.11
2.22
2.27
2.41
1200
Cap.
10.8 9.92 14.2 13.0 17.3 15.9 20.7 19.0 24.0 21.7 28.3 24.8 32.8 32.8 36.2 36.2 37.4 37.4 41.5 41.5
kW
1.45
1.52
1.59
1.66
1.73
1.82
1.94
2.03
2.06
2.18
1500
Cap.
11.1 10.2 14.6 13.4 17.6 16.2 21.2 19.4 24.4 22.1 28.9 25.3 33.5 33.5 36.5 36.5 37.7 37.7 41.2 41.2
kW
1.43
1.49
1.54
1.60
1.66
1.74
1.83
1.90
1.92
2.00
70
900
Cap.
8.67 7.97 11.9 10.9 15.1 13.9 18.6 17.1 22.2 20.2 26.4 23.1 30.5 30.5 33.6 33.6 34.7 34.7 39.0 39.0
kW
1.69
1.83
1.95
2.08
2.21
2.38
2.54
2.67
2.72
2.92
1200
Cap.
9.15 8.42 12.4 11.4 15.7 14.5 19.3 17.7 22.9 20.7 27.1 23.8 31.4 31.4 34.6 34.6 35.8 35.8 40.0 40.0
kW
1.67
1.78
1.88
1.99
2.09
2.22
2.35
2.45
2.49
2.64
1500
Cap.
9.55 8.78 12.8 11.8 16.2 14.9 19.8 18.2 23.3 21.1 27.7 24.3 32.0 32.0 35.2 35.2 36.4 36.4 40.2 40.2
kW
1.65
1.75
1.84
1.93
2.02
2.12
2.23
2.32
2.35
2.46
80
900
Cap.
7.32 6.73 10.6 9.79 14.1 12.9 17.7 16.2 21.4 19.4 25.6 22.4 29.5 29.5 32.5 32.5 33.7 33.7 38.1 38.1
kW
1.83
1.99
2.14
2.30
2.45
2.64
2.82
2.97
3.02
3.25
1200
Cap.
7.80 7.17 11.2 10.3 14.7 13.5 18.4 16.8 22.1 20.1 26.3 23.1 30.4 30.4 33.6 33.6 34.7 34.7 39.0 39.0
kW
1.81
1.95
2.08
2.20
2.33
2.48
2.62
2.73
2.78
2.94
1500
Cap.
8.22 7.56 11.7 10.7 15.2 14.0 18.8 17.3 22.6 20.5 26.9 23.5 31.1 31.1 34.3 34.3 35.5 35.5 39.6 39.6
kW
1.79
1.92
2.04
2.15
2.25
2.38
2.50
2.60
2.63
2.76
Performance data — 50HJQ (cont)
50H
JQ
Содержание WEATHERMASTER 50HJQ016
Страница 19: ...19 Base unit dimensions 50TFQ004 007 50TFQ ...
Страница 20: ...20 Base unit dimensions 50TFQ008 012 50TFQ ...
Страница 84: ...84 Base unit dimensions 50HJQ004 007 50HJQ ...
Страница 85: ...85 Base unit dimensions 50HJQ008 012 50HJQ ...
Страница 91: ...91 2 1 5 8 2 2 1 16 1 6 5 16 NON FUSED DISCONNECT 50HJQ014 016 POWER EXHAUST 50HJQ014 016 50HJQ ...
Страница 141: ...141 Typical wiring schematics 50HJQ 50HJQ016 460 v shown 50HJQ ...