23. Outdoor Air/Return Air Temperature Sensor
(adjustable) (EconoMi$er2):
Optional sensor uses the PremierLink control
to control outdoor air damper and compressor
operation.
24. Indoor Air Quality (CO
2
) Sensor
(EconoMi$er2):
a. Shall have the ability to provide demand ven-
tilation indoor air quality (IAQ) control
through the EconoMi$er2 with an IAQ
sensor.
b. The IAQ sensor shall be available in duct
mount, wall mount, and wall mount with
LED display. The set point shall have adjust-
ment capability.
c. Requires EconoMi$er2, PremierLink or
Apollo control options.
25. Indoor Air Quality (CO
2
) Room Sensor
(EconoMi$er IV):
Sensor shall have the ability to provide demand
ventilation control through the EconoMi$er IV.
The IAQ sensor shall be wall mounted with an
LED display in parts per million. The set point
shall have adjustment capability.
26. Return Air CO
2
Sensor (EconoMi$er IV):
Sensor shall have the ability to provide demand
ventilation control through the EconoMi$er IV.
The IAQ sensor shall be duct mounted. The set
point shall have adjustment capability.
27. Ultra-Violet Germicidal Lamps:
Ultra-violet germicidal lamps are designed to
eliminate odor-causing mold and fungus that
may develop in the wet area of the indoor
section of the unit. The high output, low tem-
perature germicidal lamps are field installed in
the indoor section of the unit, aimed at the
indoor coil and condensate pan. The short
wave-length ultra-violet light inhibits and kills
mold, fungus and microbial growth. The lamps
have an output rating at 45 F in 400 fpm air-
flow of 120 microwatts/cm
2
at 1 meter.
28. Hinged Panel Option:
Hinged panel option provide hinged access
panels for the filter, compressor, evaporator
fan, and control box areas. Filter hinged panels
permit tool-less entry for changing filters. Each
hinged panel is permanently attached to the
rooftop unit.
29. Emergency Heat Control Package:
When mechanical heating is locked out, auxil-
iary heat shall be activated when necessary.
→
→
905
50
HJ
Q
Содержание WEATHERMASTER 50HJQ016
Страница 19: ...19 Base unit dimensions 50TFQ004 007 50TFQ ...
Страница 20: ...20 Base unit dimensions 50TFQ008 012 50TFQ ...
Страница 84: ...84 Base unit dimensions 50HJQ004 007 50HJQ ...
Страница 85: ...85 Base unit dimensions 50HJQ008 012 50HJQ ...
Страница 91: ...91 2 1 5 8 2 2 1 16 1 6 5 16 NON FUSED DISCONNECT 50HJQ014 016 POWER EXHAUST 50HJQ014 016 50HJQ ...
Страница 141: ...141 Typical wiring schematics 50HJQ 50HJQ016 460 v shown 50HJQ ...