COOLING CAPACITIES
50HJQ004 (3 Tons)
Temp (F)
Outdoor
Entering Air
(Edb)
Indoor Entering Air — Cfm/BF
900/0.12
1200/0.15
1500/0.18
Indoor Entering Air — Ewb (F)
72
67
62
72
67
62
72
67
62
75
TC
41.2
37.8
34.4
42.9
39.6
36.3
43.6
40.6
37.5
SHC
19.8
24.5
28.8
21.5
27.6
32.9
22.5
30.1
36.3
kW
2.11
2.08
2.05
2.12
2.10
2.07
2.12
2.10
2.08
85
TC
39.9
36.5
33.1
41.9
38.2
34.9
42.5
39.2
36.1
SHC
19.4
24.0
28.2
21.2
27.2
32.4
22.6
29.8
35.9
kW
2.36
2.34
2.31
2.38
2.35
2.33
2.38
2.36
2.35
95
TC
38.6
35.0
31.7
40.4
36.7
33.4
41.3
37.6
34.8
SHC
18.9
23.4
27.4
20.8
26.6
31.6
22.4
29.2
34.7
kW
2.65
2.62
2.58
2.66
2.63
2.61
2.67
2.64
2.63
105
TC
37.1
33.2
30.0
38.7
35.0
31.5
39.3
36.0
33.2
SHC
18.3
22.7
26.6
20.3
26.1
30.7
21.7
29.0
33.2
kW
2.96
2.92
2.88
2.98
2.95
2.90
2.97
2.96
2.93
115
TC
35.1
31.4
28.0
36.7
32.8
29.7
37.7
33.8
31.6
SHC
17.6
21.9
25.6
19.7
25.2
29.6
21.5
28.1
31.6
kW
3.29
3.25
3.20
3.31
3.27
3.23
3.32
3.29
3.26
125
TC
33.0
29.0
25.7
34.4
30.6
27.8
35.4
31.5
29.8
SHC
16.9
21.0
24.5
19.0
24.3
27.8
20.9
27.1
29.7
kW
3.65
3.59
3.53
3.68
3.62
3.57
3.69
3.64
3.61
50HJQ005 (4 Tons)
Temp (F)
Outdoor
Entering Air
(Edb)
Indoor Entering Air — Cfm/BF
1200/0.1
1600/0.12
2000/0.15
Indoor Entering Air — Ewb (F)
72
67
62
72
67
62
72
67
62
75
TC
51.0
48.9
43.9
52.3
50.2
46.0
53.7
51.5
48.1
SHC
24.1
33.1
40.3
26.0
37.0
44.2
27.8
40.9
48.0
kW
2.65
2.64
2.60
2.66
2.65
2.61
2.67
2.66
2.63
85
TC
48.9
47.1
41.9
50.7
48.4
44.2
52.6
49.8
46.6
SHC
22.9
32.2
40.2
25.4
36.4
43.4
27.9
40.6
46.6
kW
2.99
2.98
2.94
3.01
3.00
2.96
3.03
3.01
2.99
95
TC
47.1
45.1
39.2
49.0
46.3
42.1
50.8
47.6
44.9
SHC
22.3
31.5
39.2
24.9
35.6
42.1
27.4
39.8
44.9
kW
3.37
3.37
3.31
3.40
3.38
3.34
3.42
3.39
3.37
105
TC
44.9
42.9
37.5
46.8
44.1
40.3
48.7
45.4
43.2
SHC
21.3
30.7
37.5
24.1
34.8
40.3
26.9
39.0
43.1
kW
3.79
3.78
3.71
3.82
3.80
3.75
3.84
3.81
3.79
115
TC
42.9
40.8
35.2
44.6
41.9
38.3
46.3
43.0
41.3
SHC
20.4
30.1
35.2
23.3
34.0
38.3
26.1
37.9
41.3
kW
4.24
4.23
4.15
4.26
4.24
4.19
4.29
4.25
4.23
125
TC
40.9
38.2
32.9
42.2
39.3
36.1
43.5
40.5
39.3
SHC
19.8
29.1
32.9
22.4
33.0
36.1
25.1
36.9
39.3
kW
4.72
4.70
4.62
4.73
4.71
4.66
4.74
4.72
4.71
50HJQ006 (5 Tons)
Temp (F)
Outdoor
Entering Air
(Edb)
Indoor Entering Air — Cfm/BF
1500/0.17
1750/0.25
2000/0.31
2500/0.42
Indoor Entering Air — Ewb (F)
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
75
TC
70.2
65.3
59.9
56.6
71.7
66.8
61.9
59.7
72.8
67.8
63.4
62.4
74.1
69.9
65.8
65.8
SHC
31.6
40.6
49.2
54.1
33.3
43.5
53.8
57.0
34.8
46.0
57.8
59.6
37.5
51.8
62.9
62.9
kW
3.51
3.47
3.45
3.43
3.52
3.48
3.46
3.44
3.45
3.49
3.47
3.46
3.55
3.51
3.48
3.48
85
TC
68.7
63.3
57.4
54.2
70.3
65.1
59.3
57.8
71.8
66.3
60.9
60.5
73.2
68.5
64.5
64.4
SHC
31.3
40.0
48.3
51.8
33.1
43.2
52.8
55.2
34.9
46.2
56.8
57.7
38.0
52.5
61.6
61.5
kW
3.95
3.91
3.89
3.87
3.96
3.92
3.89
3.89
3.98
3.93
3.91
3.91
4.00
3.96
3.93
3.92
95
TC
66.7
60.6
52.0
50.1
68.4
62.4
55.5
54.7
69.1
63.8
58.2
58.2
71.2
65.6
62.2
62.2
SHC
30.7
39.1
46.2
47.8
32.7
42.5
51.3
52.3
34.2
45.8
55.5
55.5
38.0
51.6
59.4
59.4
kW
4.43
4.39
4.34
4.32
4.45
4.41
4.37
4.37
4.46
4.43
4.39
4.40
4.48
4.43
4.42
4.42
105
TC
63.7
55.4
45.8
45.8
65.6
58.6
50.2
50.1
66.9
60.5
53.3
53.6
68.2
62.4
59.5
59.5
SHC
29.8
37.4
43.5
43.7
31.9
41.3
47.9
47.9
33.9
44.8
50.9
51.2
37.3
51.1
56.8
56.8
kW
4.96
4.91
4.81
4.81
4.99
4.94
4.86
4.86
5.00
4.96
4.90
4.90
5.00
4.97
4.95
4.95
115
TC
60.2
47.9
41.2
41.2
62.0
50.9
45.2
45.2
63.3
52.8
48.2
48.2
65.1
56.2
54.2
54.1
SHC
28.8
34.8
39.3
39.3
30.9
38.8
43.1
43.2
32.9
42.4
46.1
46.0
36.8
49.2
51.8
51.7
kW
5.55
5.43
5.33
5.33
5.57
5.46
5.40
5.40
5.58
5.49
5.44
5.44
5.59
5.53
5.50
5.50
Performance data — 50HJQ
Standard Ratings
LEGEND
NOTES:
1. Direct interpolation is permissible. Do not
extrapolate.
2. The following formulas may be used:
Where: h
ewb
= Enthalpy of air entering evapo-
rator coil
3. The SHC is based on 80 F edb temperature of
air entering evaporator coil.
Below 80 F edb, subtract (corr factor x cfm)
from SHC.
Above 80 F edb, add (corr factor x cfm) to
SHC.
Correction Factor = 1.10 x (1 – BF) x
(edb – 80).
BF
—
Bypass Factor
Edb —
Entering Dry-Bulb
Ewb —
Entering Wet-Bulb
kW
—
Compressor Motor Power Input
SHC —
Sensible Heat Capacity (1000 Btuh) Gross
TC
—
Total Capacity (1000 Btuh) Gross
t
ldb
=
t
edb
–
sensible capacity
(Btuh)
1.10 x cfm
t
lwb
=
Wet-bulb temperature
corresponding to enthalpy of air
leaving evaporator coil (h
lwb
)
h
lwb
=
h
ewb
–
total capacity
(Btuh)
4.5 x cfm
50
HJ
Q
Содержание WEATHERMASTER 50HJQ016
Страница 19: ...19 Base unit dimensions 50TFQ004 007 50TFQ ...
Страница 20: ...20 Base unit dimensions 50TFQ008 012 50TFQ ...
Страница 84: ...84 Base unit dimensions 50HJQ004 007 50HJQ ...
Страница 85: ...85 Base unit dimensions 50HJQ008 012 50HJQ ...
Страница 91: ...91 2 1 5 8 2 2 1 16 1 6 5 16 NON FUSED DISCONNECT 50HJQ014 016 POWER EXHAUST 50HJQ014 016 50HJQ ...
Страница 141: ...141 Typical wiring schematics 50HJQ 50HJQ016 460 v shown 50HJQ ...