15
PURON
®
(R-410A) REFRIGERANT
This unit is designed for use with Puron (R-410A) refrigerant.
Do not use any other refrigerant in this system.
Puron (R-410A) refrigerant is provided in pink (rose) colored
cylinders. These cylinders are available with and without dip
tubes; cylinders with dip tubes will have a label indicating this
feature. For a cylinder with a dip tube, place the cylinder in the
upright position (access valve at the top) when removing liquid
refrigerant for charging. For a cylinder without a dip tube, in-
vert the cylinder (access valve on the bottom) when removing
liquid refrigerant.
Because Puron (R-410A) refrigerant is a blend, it is strongly
recommended that refrigerant always be removed from the cyl-
inder as a liquid. Admit liquid refrigerant into the system in the
discharge line. If adding refrigerant into the suction line, use a
commercial metering/expansion device at the gage manifold;
remove liquid from the cylinder, pass it through the metering
device at the gage set and then pass it into the suction line as a
vapor. Do not remove Puron (R-410A) refrigerant from the
cylinder as a vapor.
Refrigerant Charge
Amount of refrigerant charge is listed on the unit’s nameplate.
Refer to
Carrier GTAC2-5 Charging, Recovery, Recycling and
Reclamation
training manual and the following procedures.
Unit panels must be in place when unit is operating during the
charging procedure.
NO CHARGE
Use standard evacuating techniques. After evacuating system,
weigh in the specified amount of refrigerant.
LOW-CHARGE COOLING
Using Cooling Charging Charts, Fig. 24-32, vary refrigerant
until the conditions of the appropriate chart are met. Note the
charging charts are different from type normally used. Charts
are based on charging the units to the correct sub-cooling for
the various operating conditions. Accurate pressure gage and
temperature sensing device are required. Connect the pressure
gage to the service port on the liquid line. Mount the tempera-
ture sensing device on the liquid line and insulate it so that out-
door ambient temperature does not affect the reading. Indoor-
air cfm must be within the normal operating range of the unit.
EXAMPLE:
Model 50HC*A04
Outdoor Temperature. . . . . . . . . . . . . . . . 85°F (29°C)
Suction Pressure. . . . . . . . . . . . . . . . . . . . 140 psig (965 kPa)
Suction Temperature should be . . . . . . . . 60°F (16°C)
USING COOLING CHARGING CHARTS
Take the outdoor ambient temperature and read the liquid pres-
sure gage. Refer to chart to determine what liquid temperature
should be. If liquid temperature is low, add refrigerant. If liquid
temperature is high, carefully recover some of the charge. Re-
check the liquid pressure as charge is adjusted.
COOLING CHARGING CHARTS
Fig. 24 — Cooling Charging Chart - 3 Ton
Fig. 25 — Cooling Charging Chart - 4 Ton
50HC SIZE DESIGNATION
NOMINAL TONS REFERENCE
04
3
05
4
06
5
07
6
08
7.5
09
8.5
12
10
14
12.5
CHARGING CHART – R-410A REFRIGERANT
COOLING MODE – OUTDOOR FAN MUST BE RUNNING
160
140
120
100
80
60
40
20
150
200
250
300
350
400
450
500
550
600
Compressor Discharge Pressure (psig)
Outdoor Coil Leaving Refrigerant
T
e
mperature (Degrees F)
Add charge if above the curve
Remove charge if below the curve
48TM502520
REV C
Outdoor Coil Leaving Refrigerant
T
e
mperature (Degrees F)
CHARGING CHART – R-410A REFRIGERANT
COOLING MODE – OUTDOOR FAN MUST BE RUNNING
Remove charge if below the curve
Add charge if above the curve
160
140
120
100
80
60
40
20
150
200
250
300
350
400
450
500
550
600
Compressor Discharge Pressure (psig)
48TM502521
REV C
Содержание WeatherMaster 50HC04
Страница 32: ...32 Fig 63 RTU Open Overlay for Economizer Wiring ...
Страница 33: ...33 Fig 64 VFD Overlay for W2770 Controller Wiring ...
Страница 85: ...85 Fig B 50HC A04 A06 PAC Control Diagram 208 1 60 208 230 3 60 460 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Страница 86: ...86 Fig C 50HC A07 PAC Control Diagram 208 230 3 60 460 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Страница 89: ...89 Fig F 50HC D08 D09 PAC Control Diagram 208 230 3 60 460 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Страница 90: ...90 Fig G 50HC D11 PAC Control Diagram 208 230 3 60 460 3 60 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Страница 91: ...91 Fig H 50HC D12 PAC Control Diagram 208 230 3 60 460 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Страница 92: ...92 Fig I 50HC D14 PAC Control Diagram 208 230 3 60 460 3 60 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Страница 93: ...93 Fig J 50HC A04 A06 PAC Power Diagram 208 230 1 60 APPENDIX D WIRING DIAGRAMS ...
Страница 94: ...94 Fig K 50HC A04 A06 PAC Power Diagram 208 230 3 60 460 3 60 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Страница 95: ...95 Fig L 50HC A07 PAC Power Diagram 208 230 3 60 460 3 60 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Страница 98: ...98 Fig O 50HC D07 PAC Power Diagram 575 3 60 6 Ton 2 Stage with Dehumidification APPENDIX D WIRING DIAGRAMS ...
Страница 99: ...99 Fig P 50HC D08 D09 PAC Power Diagram 208 230 3 60 460 3 60 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Страница 100: ...100 Fig Q 50HC D11 PAC Power Diagram 208 230 3 60 APPENDIX D WIRING DIAGRAMS ...
Страница 101: ...101 Fig R 50HC D11 PAC Power Diagram 460 3 60 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Страница 102: ...102 Fig S 50HC D12 PAC Power Diagram 208 230 3 60 460 3 60 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Страница 103: ...103 Fig T 50HC D14 PAC Power Diagram 208 230 3 60 APPENDIX D WIRING DIAGRAMS ...
Страница 104: ...104 Fig U 50HC D14 PAC Power Diagram 460 3 60 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Страница 109: ...109 Fig Z 50HC D12 PAC Control Diagram 230 460 575 3 60 with Humidi MiZer System APPENDIX D WIRING DIAGRAMS ...
Страница 110: ...110 Fig AA 50HC D14 PAC Control Diagram 230 460 575 3 60 with Humidi MiZer System APPENDIX D WIRING DIAGRAMS ...
Страница 111: ...111 Fig AB 50HC A04 A06 PAC Power Diagram 208 230 1 60 with Humidi MiZer System APPENDIX D WIRING DIAGRAMS ...
Страница 112: ...112 Fig AC 50HC A04 A06 PAC Power Diagram 208 230 460 3 60 with Humidi MiZer System APPENDIX D WIRING DIAGRAMS ...
Страница 113: ...113 Fig AD 50HC A04 A06 PAC Power Diagram 575 3 60 with Humidi MiZer System APPENDIX D WIRING DIAGRAMS ...
Страница 114: ...114 Fig AE 50HC A07 PAC Power Diagram 208 230 460 3 60 with Humidi MiZer System APPENDIX D WIRING DIAGRAMS ...
Страница 115: ...115 Fig AF 50HC A07 PAC Power Diagram 575 3 60 with Humidi MiZer System APPENDIX D WIRING DIAGRAMS ...
Страница 116: ...116 Fig AG 50HC D08 D09 PAC Power Diagram 208 230 460 3 60 with Humidi MiZer System APPENDIX D WIRING DIAGRAMS ...
Страница 117: ...117 Fig AH 50HC D08 D09 PAC Power Diagram 575 3 60 with Humidi MiZer System APPENDIX D WIRING DIAGRAMS ...
Страница 118: ...118 Fig AI 50HC D11 PAC Power Diagram 208 230 3 60 with Humidi MiZer System APPENDIX D WIRING DIAGRAMS ...
Страница 119: ...119 Fig AJ 50HC D11 PAC Power Diagram 460 3 60 575 3 60 with Humidi MiZer System APPENDIX D WIRING DIAGRAMS ...
Страница 121: ...121 Fig AL 50HC D14 PAC Power Diagram 208 230 3 60 with Humidi MiZer System APPENDIX D WIRING DIAGRAMS ...
Страница 122: ...122 Fig AM 50HC D14 PAC Power Diagram 460 3 60 with Humidi MiZer System APPENDIX D WIRING DIAGRAMS ...
Страница 123: ...123 Fig AN 50HC D14 PAC Power Diagram 575 3 60 with Humidi MiZer System APPENDIX D WIRING DIAGRAMS ...
Страница 124: ...124 Fig AO PremierLink System A04 A06 Wiring Diagram APPENDIX D WIRING DIAGRAMS ...
Страница 125: ...125 Fig AP RTU Open System Control A04 A06 Wiring Diagram APPENDIX D WIRING DIAGRAMS ...
Страница 126: ...126 Fig AQ PremierLink System A07 D14 Wiring Diagram APPENDIX D WIRING DIAGRAMS ...
Страница 127: ...127 Fig AR RTU Open A07 D14 Wiring Diagram APPENDIX D WIRING DIAGRAMS ...