background image

31

ADVANCED 

SETUP

(cont)

STG3 DLY

2.0h

0 min, 5 min, 

15 min, then 

15 min intervals. 

Up to 4 hrs or OFF

COOLING STAGE 3 DELAY

Delay after stage 2 cool has been active. Turns on second  stage of 

cooling when economizer is first  stage and mechanical cooling is 

second  stage. Allows three stages of cooling, 1 economizer and 2 

mechanical.

OFF = no Stage 3 cooling

SD DMPR POS

CLO

CLO or OPN

Indicates shutdown signal from space thermostat or unitary 

controller. When controller receives 24 Vac input on the SD 

terminal in conventional mode, the OA damper will open if 

programmed for OPN and OA damper will close if programmed for 

CLO. All other controls, e.g., fans, etc. will shut off.

DA LO ALM

45°F (7°C)

35°F to 65°F

(2°C to 18°C); 

Incremented by 

5°F.

Used for alarm for when the DA air temperature is too low. Set 

lower range of alarm, below this temperature the alarm will show on 

the display.

DA HI ALM

80°F (27°C)

70°F to 180°F

(21°C to 82°C); 

Incremented by 

5°F

Used for alarm for when the DA air temperature is too high. Set 

upper range of alarm, above this temperature the alarm will show 

on the display.

DCVCAL ENA

MAN

MAN (manual) 

AUTO

Turns on the DCV automatic control of the dampers. Resets 

ventilation based on the RA, OA, and MA sensor conditions. 

Requires all 3 RA, OA, and MA sensors.

MAT T CAL

0.0°F

±2.5°F

SUPPLY AIR TEMPERATURE CALIBRATION

Allows for the operator to adjust for an out of calibration 

temperature sensor.

OAS T CAL

0.0°F

±2.5°F

OUTSIDE AIR TEMPERATURE CALIBRATION

Allows for the operator to adjust for an out of calibration 

temperature sensor.

OA H CAL

0% RH

±10% RH

OUTSIDE AIR HUMIDITY CALIBRATION

Allows for operator to adjust for an out of calibration humidity 

sensor.

RA T CAL

0.0°F

±2.5°F

RETURN AIR TEMPERATURE CALIBRATION

Allows for the operator to adjust for an out of calibration 

temperature sensor.

RA H CAL

0% RH

±10% RH

RETURN AIR HUMIDITY CALIBRATION

Allows for operator to adjust for an out of calibration humidity 

sensor.

DA T CAL

0.0°F

±2.5°F

DISCHARGE AIR TEMPERATURE CALIBRATION

Allows for the operator to adjust for an out of calibration 

temperature sensor.

2SP FAN DELAY

5 Minutes

0 to 20 minutes in 

1 minute 

increments

TIME DELAY ON SECOND STAGE ECONOMIZING

When in economizing mode this is the delay for the high speed fan 

to try to satisfy the call for second stage cooling before the first 

stage mechanical cooling is enabled.

CHECKOUT

DAMPER MINIMUM 

POSITION

N/A

N/A

The checkout for the damper minimum position is based on the 

system.

DAMPER OPEN

N/A

N/A

Position damper to the full open position.

Exhaust fan contacts enable during the DAMPER OPEN test. Make 

sure you pause in the mode to allow exhaust contacts to energize 

due to the delay in the system.

DAMPER CLOSE

N/A

N/A

Positions damper to the fully closed position

CONNECT Y1–O

N/A

N/A

Closes the Y1-O relay (Y1-O)

CONNECT Y2–O

N/A

N/A

Closes the Y2-O relay (Y2-O)

CONNECT AUX1-O

N/A

N/A

Energizes the AUX output. If Aux setting is:

• NONE — not action taken

• ERV — 24 Vac out. Turns on or signals an ERV that the 

conditions are not good for economizing but are for ERV 

operation.

††

• SYS — 24 Vac out. Issues a system alarm

CONNECT EXH1

N/A

N/A

Closes the power exhaust fan 2 relay (EXH1)

ALARMS

Alarms display only when they are active. The menu title “ALARMS(#)” includes the number of active alarms in parenthesis ( ). 

When using SYLK bus sensors, “SYLK” will appear on the screen, and when using 20k OA temperature sensors, “SENS T” will 

appear on the screen

MA T SENS ERR

N/A

N/A

SUPPLY AIR TEMPERATURE SENSOR ERROR

Mixed air sensor has failed or become disconnected - check wiring 

then replace sensor if the alarm continues.

CO2 SENS ERR

N/A

N/A

CO

2

 SENSOR ERROR

CO

2

 sensor has failed, gone out of range or become disconnected - 

check wiring then replace sensor if the alarm continues.

OA SYLK T ERR

N/A

N/A

OUTSIDE AIR S-BUS SENSOR ERROR

Outdoor air enthalpy sensor has failed or become disconnected - 

check wiring then replace sensor if the alarm continues.

OA SYLK H ERR

N/A

N/A

RA SYLK T ERR

N/A

N/A

RETURN AIR S-BUS SENSOR ERROR

Return air enthalpy sensor has failed or become disconnected - 

check wiring then replace sensor if the alarm continues.

RA SYLK H ERR

N/A

N/A

Table 7 — W7220 Menu Structure* (cont)

 MENU

PARAMETER

PARAMETER 

DEFAULT 

VALUE

PARAMETER 

RANGE AND 

INCREMENT

NOTES

Содержание WeatherMaster 50GC 04-06 Series

Страница 1: ...FAN OPERATION 2SP H C AND 3 SPEED FAN OPERATION CHECKOUT TROUBLESHOOTING RTU Open Controller Factory Option 35 SystemVu Controller Factory Option 35 Controller Options 35 LOW AMBIENT Smoke Detectors 3...

Страница 2: ...uld cause personal injury death and or equipment damage R 410A refrigerant systems operate at higher pressures than standard R 22 systems Do not use R 22 service equipment or components on R 410A refr...

Страница 3: ...installed W7212 EconoMi er IV Non Fault Detection and Diagnostic 2 RTU Open Multi Protocol Controller 3 SystemVu Controller 6 Electro mechanical can be used with W7220 EconoMi er X with Fault Detecti...

Страница 4: ...4 Fig 2 50GC 04 06 Unit Dimensional Drawing...

Страница 5: ...5 Fig 2 50GC 04 06 Unit Dimensional Drawing cont...

Страница 6: ...6 Fig 2 50GC 04 06 Unit Dimensional Drawing cont...

Страница 7: ...ions 9 Install other accessories PAD MOUNTED INSTALLATION 1 Prepare pad and unit supports 2 Check and tighten the bottom condensate drain connection plug 3 Rig and place unit 4 Convert unit to side du...

Страница 8: ...ENGINEERING MANUFACTURING ENGINEERING REQUIREMENTS SIZE DRAWING NUMBER REV T 005 Y 002 DRAFTER CHECKER D 48TC400427 B WEIGHT MMC 06 17 11 SHEET 5 OF 5 SURFACE FINISH MFG PURCH MODEL INTERNAL USE ONLY...

Страница 9: ...using unit frame as a refer ence See Table 2 on page 7 and Fig 5 for additional information Lifting holes are provided in base rails as shown in Fig 5 Refer to rigging instructions on unit Rigging mat...

Страница 10: ...weatherproof all external ductwork joints and roof or build ing openings with counter flashing and mastic in accordance with applicable codes Do not cover or obscure visibility to the unit s informati...

Страница 11: ...Save the aluminum filter for use in the power exhaust hood assembly 1 The indoor coil access panel will be used as the top of the hood Remove the screws along the sides and bottom of the indoor coil a...

Страница 12: ...owered convenience outlet the power source leads to the convenience outlet s transformer primary are not factory connected Installer must connect these leads accord ing to required operation of the co...

Страница 13: ...ndle Fig 18 Power Wiring Connections Field Install the NFD Shaft and Handle 1 Remove the Control Box access panel The NFD enclosure is located below the Control Box see Fig 19 2 Remove 3 cap head scre...

Страница 14: ...sition See Fig 22 6 Tighten the locking screw to secure the shaft to the HACR 7 Turn the handle to the OFF position with red arrow pointing at OFF 8 Install the handle on to the painted cover horizont...

Страница 15: ...over Aweatherproof while in use cover for the factory installed conve nience outlets is now required by UL standards This cover cannot be factory mounted due its depth it must be installed at unit ins...

Страница 16: ...zation is con firmed Observe National Electrical CodeArticle 210 Branch Cir cuits for use of convenience outlets Fuse On Power Type The factory fuse is a Bussman1 Fusetron T 15 non renewable screw in...

Страница 17: ...rminals during operation must be within voltage range indicated on unit nameplate On 3 phase units volt ages between phases must be balanced within 2 and the current within 10 Use the formula shown in...

Страница 18: ...terminal strip on the upper left corner of the Unit Control Board See Fig 32 NOTE If thru the bottom connections accessory is used refer to the accessory installation instructions for information on r...

Страница 19: ...e heater module VIO and BRN two of each if a two circuit heater module is installed identify for circuit 1 to the 4 pole terminal board TB4 located on the heater bulkhead to the left of the Heater mod...

Страница 20: ...ee Fig 40 Fig 40 Humidistat Connections to UCB Connecting the Thermidistat device 33CS2PPRH 01 1 Route the Thermidistat multi conductor thermostat cable field supplied through the hole provided in the...

Страница 21: ...it with Humidi MiZer Adaptive Dehumidification System and Edge Pro Thermidistat Device Rc Rh W1 G Y2 C O W2 B Y1 OAT RRS SRTN HUM D1 D2 V Vg C HUM G W2 W1 Y2 Y1 R PROGRAMMABLE THERMOSTAT UNIT CONTROL...

Страница 22: ...22 Fig 42 Typical 50GC 04 06 Control Wiring Diagram 208 230V W7220 Control Unit Shown...

Страница 23: ...23 Fig 43 Typical 50GC 04 06 Power Wiring Diagram 208 230V Unit Shown...

Страница 24: ...ce Provides status for normal operation setup parameters checkout tests and alarm and error conditions with a 2 line 16 character LCD display and four button keypad Electrical Rated Voltage 20 to 30 V...

Страница 25: ...Sensor Input e g CO2 sensor IAQ COM COM Air Quality Sensor Common IAQ 24V 24 vac Air Quality Sensor 24 vac Source ACT 2 10 2 10 vdc Damper Actuator Output 2 10 vdc ACT COM COM Damper Actuator Output C...

Страница 26: ...t a menu s item and return to the list of menus Fig 48 W7220 Controller Navigation Buttons To use the keypad when working with Setpoints System and Ad vanced Settings Checkout tests and Alarms 1 Navig...

Страница 27: ...the and arrow buttons to move forward and back ward through the menus and press the button to select and confirm setup item changes TIME OUT AND SCREENSAVER When no buttons have been pressed for 10 m...

Страница 28: ...re Displays _ _ _F if sensor sends invalid value if not connected short or out of range OA TEMP _ _ _ F 40 F to 140 F 40 C to 60 C OUTSIDE AIR TEMP Displays measured value of outdoor air temperature D...

Страница 29: ...TILATION MINIMUM POSITION AT LOW SPEED Only displays if unit is set for 2 or 3 speed and CO2 is not used If using 2 speed with 1 heat and 1 cool then set for HEATING ventilation If using 3 speed with...

Страница 30: ...If using 2 speed fan mode you must program CONV mode for W Shutdown is not available in 2 speed fan mode See Menu Note 4 In HP O B mode HP O energize heat pump on Cool default HP B energize heat pump...

Страница 31: ...o adjust for an out of calibration temperature sensor 2SP FAN DELAY 5 Minutes 0 to 20 minutes in 1 minute increments TIME DELAY ON SECOND STAGE ECONOMIZING When in economizing mode this is the delay f...

Страница 32: ...A OUTSIDE AIR TEMPERATURE SENSOR ERROR Outdoor air temperature sensor has failed or become disconnected check wiring then replace if the alarm continues ACT ERROR N A N A ACTUATOR ERROR Actuator has f...

Страница 33: ...dary the conditions are not good to economize and the mode is set to NO Figure 49 shows the 5 current boundaries There is also a high lim it boundary for differential enthalpy The high limit boundary...

Страница 34: ...delay time specified N A Not applicable Table 9 Fan Speed STATE FAN SPEED OCC Low Y1 Low Y2 High W High Table 10 Economizer Operation FAN TYPE 2SPEED INPUTS OUTPUTS DEMAND CONTROLLED VENTILATION DCV O...

Страница 35: ...Once the alarm has been identified and the cause has been removed e g replaced faulty sensor the alarm can be cleared from the display To clear an alarm perform the following 1 Navigate to the desired...

Страница 36: ...e sure that the elbow fitting is pointing down See Fig 51 Step 2 3 Screw the sensor and detector plate into its operating position using screws from Step 1 See Fig 51 Step 3 4 Connect the flexible tub...

Страница 37: ...oc cupied sequence at terminals marked OCCUPANCY Detach the jumper covering the Occupancy terminals on the UCB and then attach the required connections Step 13 Install Accessories Available accessorie...

Страница 38: ...for the base unit Then add Vdc for any accessories installed per the Field Accessories section of the label NOTE The fan speed set up labels are located on the High Volt age cover in the Control Box...

Страница 39: ...he following determin ing the values per the RPM Calculator label see Fig 55 Use the UP and DOWN arrow keys and the BACK key to set the values Press ENTER after setting each value to continue to the n...

Страница 40: ...75 66 80 107 0 4 1477 1544 1615 1688 1764 1842 1921 2003 2068 66 0 6 1639 1699 1763 1828 1897 1967 2040 2115 2191 0 8 1788 1843 1902 1962 2025 2090 2157 2227 2298 66 1 0 1925 1976 2031 2087 2146 2208...

Страница 41: ......

Страница 42: ...iscontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53500269 01 Printed in U S A Form 50GC 4 6 03SI Pg 42 12 19A 12 19 Replaces 50...

Страница 43: ...ns Y N _____ Verify that all electrical connections and terminals are tight Y N _____ Check that indoor air filters are clean and in place Y N _____ Check that outdoor air inlet screens are in place Y...

Страница 44: ...______________ F D Liquid line temperature at outlet or reheat coil _______________ F E Confirm correct rotation for compressor Y N _____ F Check for correct ramp up of outdoor fan motor as condenser...

Отзывы: