Table 40 — Run Status Cool Display
SumZ Operation — The SumZ algorithm is an adaptive PID
style of control. The PID is programmed within the control and
the relative speed of staging can only be influenced by the user
through the adjustment of the
Z.GN
configuration, described in
the reference section. The capacity control algorithm uses a
modified PID algorithm, with a self adjusting gain which
compensates for varying conditions, including changing flow
rates across the evaporator coil.
Previous implementations of SumZ made static assump-
tions about the actual size of the next capacity jump up or
down. This control uses a “rise per percent capacity” technique
in the calculation of SumZ, instead of the previous “rise per
stage” method. For each jump, up or down in capacity, the
control will know beforehand the exact capacity change
brought on. Better overall staging control can be realized with
this technique.
SUM Calculation
— The PID calculation of the “SUM” is
evaluated once every 80 seconds.
SUM = Error + “SUM last time through” + (3 * Error Rate)
Where:
SUM = the PID calculation
Error = EDT – Cooling Control Point
Error Rate = Error – “Error last time through”
NOTE: “Error” is clamped between –10 and +50 and “Error
rate” is clamped between –5 and +5.
This “SUM” will be compared against the “Z” calculations
in determining whether cooling stages should be added or
subtracted.
Z Calculation
— For the “Z” calculation, the control attempts
to determine the entering and the leaving-air temperature of the
evaporator coil and based upon the difference between the two
during mechanical cooling, determines whether to add or
subtract a stage of cooling. This is the adaptive element.
The entering-air temperature is referred to as
MAT
(mixed-air temperature) and the leaving-air temperature of the
evaporator coil is referred to as
EDT
(evaporator discharge
temperature). They are found at the local display under the
Temperatures
→
CTRL
sub-menu.
The main elements to be calculated and used in the calcula-
tion of SumZ are:
1) the rise per percent capacity (
R.PCT
)
2) the amount of expected rise for the next cooling stage
addition
3) the amount of expected rise for the next cooling stage
subtraction
The calculation of “Z” requires two variables,
Z.PLU
used
when adding a stage and
Z.MIN
used when subtracting a stage.
They are calculated with the following formulas:
Z.PLU
=
Z.GN
* (10 + (4*(–
ADD.R
))) * 0.6
Z.MIN
=
Z.GN
* (–10 + (4*(–
SUB.R
))) * 0.6
Where:
Z.GN
= configuration used to modify the threshold levels used
for staging (
Configuration
→
COOL
→
Z.GN
)
ADD.R
=
R.PCT
*
(
C.CAP
– capacity after adding a cooling
stage)
SUB.R
=
R.PCT
* (
C.CAP
– capacity after subtracting a cool-
ing stage)
Both of these terms,
Z.PLU
and
Z.MIN
,
represent a thresh-
old both positive and negative upon which the “SUM” calcula-
tion must build up to in order to cause the compressor to stage
up or down.
Comparing SUM and Z
— The “SUM” calculation is com-
pared against
Z.PLU
and
Z.MIN
.
• If “SUM” rises above
Z.PLU
, a cooling stage is added.
• If “SUM” falls below
Z.MIN
, a cooling stage is subtracted.
There is a variable called
SMZ
which is described in the
reference section and which can simplify the task of watching
the demand build up or down over time. It is calculated as
follows:
If SUM is positive:
SMZ
= 100*(SUM/
Z.PLU
)
If SUM is negative:
SMZ
= –100*(SUM/
Z.MIN
)
Mixed Air Temperature Calculation (MAT)
— The mixed-
air temperature is calculated and is a function of the economiz-
er position. Additionally there are some calculations in the con-
trol which can zero in over time on the relationship of return
and outside air as a function of economizer position. There are
two configurations which relate to the calculation of “MAT”.
These configurations can be located at the local display under
Configuration
→
UNIT
.
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
WRITE STATUS
COOL
COOLING INFORMATION
C.CAP
Current Running Capacity
%
CAPTOTAL
CUR.S
Current Cool Stage
COOL_STG
REQ.S
Requested Cool Stage
CL_STAGE
MAX.S
Maximum Cool Stages
CLMAXSTG
DEM.L
Active Demand Limit
%
DEM_LIM
forcible
SUMZ
COOL CAP. STAGE CONTROL
SMZ
Capacity Load Factor
-100 – +100
SMZ
ADD.R
Next Stage EDT Decrease
^F
ADDRISE
SUB.R
Next Stage EDT Increase
^F
SUBRISE
R.PCT
Rise Per Percent Capacity
RISE_PCT
Y.MIN
Cap Deadband Subtracting
Y_MINUS
Y.PLU
Cap Deadband Adding
Y_PLUS
Z.MIN
Cap Threshold Subtracting
Z_MINUS
Z.PLU
Cap Threshold Adding
Z_PLUS
H.TMP
High Temp Cap Override
HI_TEMP
L.TMP
Low Temp Cap Override
LOW_TEMP
PULL
Pull Down Cap Override
PULLDOWN
SLOW
Slow Change Cap Override
SLO_CHNG
ITEM
EXPANSION
RANGE
CCN
POINT
DEFAULTS
UNIT
UNIT CONFIGURATION
MAT.S
MAT Calc Config
0 - 2
MAT_SEL
1
MAT.R
Reset MAT Table
Entries?
Yes/No
MATRESET No
Содержание WEATHERMASTER 48Z030
Страница 103: ...103 Fig 15 Typical Power Schematic Sizes 030 050 Shown a48 8408 ...
Страница 104: ...104 Fig 16 Main Base Board Input Output Connections a48 8409 ...
Страница 105: ...105 Fig 17 RCB ECB CEM SCB Input Output Connections a48 8410 ...
Страница 106: ...106 Fig 18 Typical Gas Heat Unit Control Wiring 48Z055 105 Units Shown a48 8411 ...
Страница 107: ...107 Fig 19 Typical Electric Heat Unit Control Wiring 50Z055 105 Units Shown a50 8248 ...
Страница 108: ...108 Fig 20 Typical Power Wiring 115 V 48Z Units a48 8412 ...
Страница 109: ...109 Fig 21 Typical Power Wiring 115 V 50Z Units a50 8249 ...
Страница 110: ...110 Fig 22 Typical Gas Heat Section Size 055 105 Units Shown a48 8413 ...
Страница 111: ...111 Fig 23 Component Arrangement Size 030 050 Units ...
Страница 112: ...112 Fig 24 Component Arrangement Size 055 070 Units ...
Страница 113: ...113 Fig 25 Component Arrangement Size 075 105 Units ...