8
NOTE: Unit not designed to have overhead obstruction. Contact Application Engineering for guidance on any application planning overhead obstruc-
tion or for vertical clearances.
Fig. 4 — Service Clearance Dimensional Drawing (Sizes 08, 09)
LOCATION
DIMENSION
CONDITION
A
48-in. (1219 mm)
Unit disconnect is mounted on panel
18-in. (457 mm)
No disconnect, convenience outlet option
18-in. (457 mm)
Recommended service clearance
12-in. (305 mm)
Minimum clearance
B
42-in. (1067 mm)
Surface behind servicer is grounded (e.g., metal, masonry wall)
36-in. (914 mm)
Surface behind servicer is electrically non-conductive (e.g., wood, fiberglass)
Special
Check sources of flue products within 10 ft of unit fresh air intake hood
C
36-in. (914 mm)
Side condensate drain is used
18-in. (457 mm)
Minimum clearance
D
42-in. (1067 mm)
Surface behind servicer is grounded (e.g., metal, masonry wall, another unit)
36-in. (914 mm)
Surface behind servicer is electrically non-conductive (e.g., wood, fiberglass)
C
D
A
B
Содержание WeatherMaker 50TCQ*08
Страница 4: ...4 Fig 2 Unit Dimensional Drawing 08 and 09 Size Units ...
Страница 5: ...5 Fig 2 Unit Dimensional Drawing 08 and 09 Size Units cont ...
Страница 6: ...6 Fig 3 Unit Dimensional Drawing 12 Size Unit ...
Страница 7: ...7 Fig 3 Unit Dimensional Drawing 12 Size Unit cont ...
Страница 19: ...19 Fig 25 Typical 50TCQ Control Wiring Diagram Sizes 08 09 ...
Страница 20: ...20 Fig 26 Typical 50TCQ Control Wiring Diagram Size 12 ...
Страница 21: ...21 Fig 27 50TCQ 08 09 Power Wiring Diagram ...
Страница 22: ...22 Fig 28 Typical 50TCQ 12 Power Wiring Diagram 208 230 v 3 Phase 60Hz Unit Shown ...
Страница 45: ......