ALL UNITS
Field power wires are connected to the unit at line-side pressure
lugs on compressor contactor C and indoor fan contactor IFC (see
wiring diagram label for control box component arrangement) or
at factory-installed option non-fused disconnect switch. Max wire
size is #4 AWG (copper only) (sizes 07-14) and #2 AWG (copper
only) (size 16). See Fig. 46 and 47.
Refer to Table 7 for maximum wire size at connection lugs. Use
copper wire only. See Fig. 46, 47, and 52.
Table 7 —
Connection Lug Min/Max Wire Sizes
NOTE: TEST LEADS - Unit may be equipped with short leads
(pigtails) on the field line connection points on contactor C or op
-
tional disconnect switch, see Fig. 46 and 47. These leads are for
factory run-test purposes only; remove and discard before con
-
necting field power wires to unit connection points. Make field
power connections directly to line connection pressure lugs only.
Fig. 52 —
Disconnect Switch and Unit
UNITS WITH FACTORY-INSTALLED NON-FUSED DIS
-
CONNECT
The factory-installed optional non-fused disconnect (NFD) switch
is located in a weatherproof enclosure located under the main con
-
trol box. The manual switch handle and shaft are shipped in the
disconnect enclosure. Assemble the shaft and handle to the switch
at this point. Discard the factory test leads (see Fig. 53 and 54).
Connect field power supply conductors to LINE side terminals
when the switch enclosure cover is removed to attach the handle.
Fig. 53 —
Location of Non-Fused Disconnect
Enclosure (Sizes 07-14)
Minimum
Maximum
TB1 In Unit Control Box
#14
#1
80A Disconnect Option
#14
#4
100A Disconnect Option
#8
1/0
WARNING
FIRE HAZARD
Failure to follow this warning could result in personal injury,
death, or property damage.
Do not connect aluminum wire between disconnect switch and
unit. Use only copper wire.
COPPER
WIRE ONLY
ELECTRIC
DISCONNECT
SWITCH
ALUMINUM
WIRE
Содержание WeatherMaker 48TC A/B07 Series
Страница 5: ...5 Fig 2 Dimensional Drawing for Units Built On and After 4 15 19 Size 07 ...
Страница 6: ...6 Fig 3 Dimensional Drawing for Units Built Prior To 4 15 19 Size 07 ...
Страница 7: ...7 Fig 4 Unit Corner Weights and Clearances Size 07 ...
Страница 8: ...8 Fig 5 Base Rail Details Size 07 ...
Страница 9: ...9 Fig 6 Thru the Base Charts Size 07 ...
Страница 10: ...10 Fig 7 Unit Dimensional Drawing Size 08 09 12 ...
Страница 11: ...11 Fig 7 Unit Dimensional Drawing Size 08 09 12 ...
Страница 12: ...12 Fig 8 Unit Dimensional Drawing Size 14 ...
Страница 13: ...13 Fig 8 Unit Dimensional Drawing Size 14 cont ...
Страница 14: ...14 Fig 9 Unit Dimensional Drawing Size 16 ...
Страница 15: ...15 Fig 9 Unit Dimensional Drawing Size 16 cont ...
Страница 20: ...20 Fig 14 48TC 16 Roof Curb Details ...
Страница 39: ...39 Fig 69 48TC 07 14 Typical Humidi MiZer Adaptive Dehumidification System Humidistat Wiring ...
Страница 40: ...40 Fig 70 48TC 16 Typical Humidi MiZer Adaptive Dehumidification System Humidistat Wiring ...
Страница 57: ...57 Fig 83 Ultra Tech Scroll Compressor Diagram ...