1
Tab
1a 1b
CONTROLS SET POINT AND CONFIGURATION LOG
MODEL NUMBER:
Software Version
SERIAL NUMBER:
MBB
CESR131343--
DATE:
RCB
CESR131249--
TECHNICIAN:
ECB
CESR131249--
NAVI
CESR131227--
SCB
CESR131226--
CEM
CESR131174--
MARQ
CESR131171--
ITEM
EXPANSION
RANGE
DEFAULT
ENTRY
UNIT
UNIT CONFIGURATION
→
C.TYP
Machine Control Type
1 - 6 (multi-text strings)
4
→
CV.FN
Fan Mode (0=Auto, 1=Cont)
0 - 1 (multi-text strings)
1
→
RM.CF
Remote Switch Config
0 - 3 (multi-text strings)
0
→
CEM
CEM Module Installed
Yes/No
No
→
TCS.C
Temp.Cmp.Strt.Cool Factr
0 - 60 min
0
→
TCS.H
Temp.Cmp.Strt.Heat Factr
0 - 60 min
0
→
SFS.S
Fan Fail Shuts Down Unit
Yes/No
No
→
SFS.M
Fan Stat Monitoring Type
0 - 2 (multi-text strings)
0
→
VAV.S
VAV Unocc.Fan Retry Time
0 - 720 min
50
→
SIZE
Unit Size (20-60)
20 - 60
20
→
DP.XR
Disch.Press. Transducers
Yes/No
No
→
SP.XR
Suct. Pres. Trans. Type
0 -1 (multi-text strings)
0
→
MAT.S
MAT Calc Config
0 - 2 (multi-text strings)
1
→
MAT.R
Reset MAT Table Entries?
Yes/No
No
→
ALTI
Altitude……..in feet:
0 - 60000
0
→
DLAY
Startup Delay Time
0 - 900 sec
0
→
STAT
TSTAT_Both Heat and Cool
Yes/No
No
→
SENS
INPUT SENSOR CONFIG
→
SENS
→
SPT.S
Space Temp Sensor
Enable/Disable
Disable
→
SENS
→
SP.O.S
Space Temp Offset Sensor
Enable/Disable
Disable
→
SENS
→
SP.O.R
Space Temp Offset Range
1 - 10
5
→
SENS
→
RRH.S
Return Air RH Sensor
Enable/Disable
Disable
→
SENS
→
FLT.S
Filter Stat.Sw.Enabled ?
Enable/Disable
Disable
COOL
COOLING CONFIGURATION
→
Z.GN
Capacity Threshold Adjst
–10
→
10
1
→
MC.LO
Compressor Lockout Temp
–20
→
40 dF
40
→
C.FOD
Fan-Off Delay, Mech Cool
0
→
600 sec
60
→
MLV
Min. Load Valve? (HGBP)
Yes/No
No
→
M.M.
Motor Master Control
Yes/No
No
→
HPSP
Head Pressure Setpoint
80 - 150 dF
113
→
A1.EN
Enable Compressor A1
Enable/Disable
Enable
→
A2.EN
Enable Compressor A2
Enable/Disable
Enable
→
B1.EN
Enable Compressor B1
Enable/Disable
Enable
→
B2.EN
Enable Compressor B2
Enable/Disable
Enable
→
CS.A1
CSB A1 Feedback Alarm
Enable/Disable
Enable
→
CS.A2
CSB A2 Feedback Alarm
Enable/Disable
Enable
→
CS.B1
CSB B1 Feedback Alarm
Enable/Disable
Enable
→
CS.B2
CSB B2 Feedback Alarm
Enable/Disable
Enable
→
REV.R
Rev Rotation Verified ?
Yes/No
No
→
H.SST
Hi SST Alert DelayTime
5 - 30 min
10
EDT.R
EVAP.DISCHRGE TEMP RESET
→
RS.CF
EDT Reset Configuration
0 - 3 (multi-text strings)
0
→
RTIO
Reset Ratio
0 - 10
2
→
LIMT
Reset Limit
0 - 20 ^F
10
→
RES.S
EDT 4-20 ma Reset Input
Enable/Disable
Disable
Содержание WEATHERMAKER 48AJ020
Страница 95: ...95 Fig 13 Typical Main Control Box Wiring Schematic A48 7787 ...
Страница 96: ...96 TO NEXT PAGE Fig 14 Auxiliary Control Box Wiring Schematic A48 7294 ...
Страница 97: ...97 LEN PORT FOR USE WITH NAVIGATOR Fig 14 Auxiliary Control Box Wiring Schematic cont A48 7809 ...
Страница 98: ...98 Fig 15 Typical 2 Stage Gas Heat Wiring Schematic Size 051 and 060 Units Shown A48 6866 ...
Страница 99: ...99 TO NEXT PAGE Fig 16 Typical Staged Gas Heat Wiring Schematic Size 051 and 060 Units Shown A48 7296 ...
Страница 100: ...100 FROM PREVIOUS PAGE Fig 16 Typical Staged Gas Heat Wiring Schematic Size 051 and 060 Units Shown cont A48 7297 ...
Страница 101: ...101 Fig 17 Typical Electric Heat Control Schematic 50AJ AK AW AY Size 051 and 060 Units Shown A48 6689 ...
Страница 102: ...102 TO NEXT PAGE Fig 18 Typical Power Schematic Size 051 and 060 Units Shown A48 7298 ...
Страница 103: ...103 FROM PREVIOUS PAGE Fig 18 Typical Power Schematic Size 051 and 060 Units Shown cont A48 7299 ...
Страница 104: ...104 Fig 19 Controls Option Wiring Schematic A48 7810 ...
Страница 105: ...105 Fig 20 Small Chassis Component Location Size 020 035 Units A48 7301 ...
Страница 106: ...106 Fig 21 Large Chassis Component Locations Size 036 060 Units A48 7302 ...