Table 88 — Cooling Service Analysis
LEGEND
PROBLEM
SOLUTION
COMPRESSOR DOES NOT RUN
Active Alarm
Check active alarms using local display.
Contactor Open
1. Power off.
1. Restore power.
2. Fuses blown in field power circuit.
2. After finding cause and correcting, replace with correct size fuse.
3. No control power.
3. Check secondary fuse(s); replace with correct type and size.
Replace transformer if primary windings receiving power.
4. Compressor circuit breaker tripped.
4. Check for excessive compressor current draw. Reset breaker;
replace if defective.
5. Safety device lockout circuit active.
5. Reset lockout circuit at circuit breaker.
6. Low-pressure switch open.
6. Check for refrigerant undercharge, obstruction of indoor airflow, or
whether compressor suction shutoff valve is fully open. Make sure
liquid line solenoid valve(s) is open.
7. High-pressure switch open.
7. Check for refrigerant overcharge, obstruction of outdoor airflow, air
in system or whether compressor discharge valve is fully open. Be
sure outdoor fans are operating correctly.
8. Loose electrical connections.
8. Tighten all connections.
9. Compressor stuck.
9. See compressor service literature.
Contactor Closed
1. Compressor leads loose.
1. Check connections.
2. Motor windings open.
2. See compressor service literature.
3. Single phasing.
3. Check for blown fuse. Check for loose connection at compressor
terminal.
COMPRESSOR STOPS ON HIGH PRESSURE
Outdoor Fan On
1. High-pressure switch faulty.
1. Replace switch.
2. Airflow restricted.
2. Remove obstruction.
3. Air recirculating.
3. Clear airflow area.
4. Noncondensables in system.
4. Purge and recharge as required.
5. Refrigerant overcharge.
5. Purge as required.
6. Line voltage incorrect.
6. Consult power company.
7. Refrigerant system restrictions.
7. Check or replace filter drier, expansion valve, etc. Check that
compressor discharge valve is fully open.
Outdoor Fan Off
1. Fan slips on shaft.
1. Tighten fan hub setscrews.
2. Motor not running.
2. Check power and capacitor.
3. Motor bearings stuck.
3. Replace bearings.
4. Motor overload open.
4. Check overload rating. Check for fan blade obstruction.
5. Motor burned out.
5. Replace motor.
COMPRESSOR CYCLES ON LOW PRESSURE
Indoor-Air Fan Running
1. Filter drier plugged.
1. Replace filter drier.
2. Expansion valve power head defective.
2. Replace power head.
3. Low refrigerant charge.
3. Add charge. Check low-pressure switch setting.
Airflow Restricted
1. Coil iced up.
1. Check refrigerant charge.
2. Coil dirty.
2. Clean coil fins.
3. Air filters dirty.
3. Clean or replace filters.
4. Dampers closed.
4. Check damper operation and position.
Indoor-Air Fan Stopped
1. Electrical connections loose.
1. Tighten all connections.
2. Fan relay defective.
2. Replace relay.
3. Motor overload open.
3. Power supply.
4. Motor defective.
4. Replace motor.
5. Fan belt broken or slipping.
5. Replace or tighten belt.
VFD —
Variable Frequency Drive
Содержание WEATHERMAKER 48AJ020
Страница 95: ...95 Fig 13 Typical Main Control Box Wiring Schematic A48 7787 ...
Страница 96: ...96 TO NEXT PAGE Fig 14 Auxiliary Control Box Wiring Schematic A48 7294 ...
Страница 97: ...97 LEN PORT FOR USE WITH NAVIGATOR Fig 14 Auxiliary Control Box Wiring Schematic cont A48 7809 ...
Страница 98: ...98 Fig 15 Typical 2 Stage Gas Heat Wiring Schematic Size 051 and 060 Units Shown A48 6866 ...
Страница 99: ...99 TO NEXT PAGE Fig 16 Typical Staged Gas Heat Wiring Schematic Size 051 and 060 Units Shown A48 7296 ...
Страница 100: ...100 FROM PREVIOUS PAGE Fig 16 Typical Staged Gas Heat Wiring Schematic Size 051 and 060 Units Shown cont A48 7297 ...
Страница 101: ...101 Fig 17 Typical Electric Heat Control Schematic 50AJ AK AW AY Size 051 and 060 Units Shown A48 6689 ...
Страница 102: ...102 TO NEXT PAGE Fig 18 Typical Power Schematic Size 051 and 060 Units Shown A48 7298 ...
Страница 103: ...103 FROM PREVIOUS PAGE Fig 18 Typical Power Schematic Size 051 and 060 Units Shown cont A48 7299 ...
Страница 104: ...104 Fig 19 Controls Option Wiring Schematic A48 7810 ...
Страница 105: ...105 Fig 20 Small Chassis Component Location Size 020 035 Units A48 7301 ...
Страница 106: ...106 Fig 21 Large Chassis Component Locations Size 036 060 Units A48 7302 ...