28
LEGEND
NOTES:
1. There is a 3-second pause between alarm code displays.
2. If more than one alarm code exists, all applicable alarm codes will
be displayed in numerical sequence.
3. Alarm codes on the IGC will be lost if power to the unit is interrupted.
Table 7 —
IGC Board LED Alarm Codes
LED
FLASH
CODE
DESCRIPTION
ACTION TAKEN BY
CONTROL
RESET METHOD
PROBABLE CAUSE
On
Normal Operation
—
—
—
Off
Hardware Failure
No gas heating.
—
Loss of power to the IGC. Check 5 amp fuse
on IGC, power to unit, 24V circuit breaker,
transformer, and wiring to the IGC.
1 Flash
Indoor Fan On/Off Delay
Modified
5 seconds subtracted from
On delay.
5 seconds added to Off
delay (3 min max).
Power reset.
High temperature limit switch opens during
heat exchanger warm-up period before fan-
on delay expires.
High temperature limit switch opens within 10
minutes of heat call (W) Off.
See Limit Switch Fault.
2 Flashes
Limit Switch Fault
Gas valve and igniter Off.
Indoor fan and inducer On.
Limit switch closed, or
heat call (W) Off.
High temperature limit switch is open. Check
the operation of the indoor (evaporator) fan
motor.
Ensure that the supply-air temperature rise is
within the range on the unit nameplate.
Check wiring and limit switch operation.
3 Flashes
Flame Sense Fault
Indoor fan and inducer On. Flame sense normal.
Power reset for LED reset.
The IGC sensed a flame when the gas valve
should be closed. Check wiring, flame
sensor, and gas valve operation.
4 Flashes
Four Consecutive Limit
Switch Fault
No gas heating.
Heat call (W) Off.
Power reset for LED reset.
4 consecutive limit switch faults within a
single call for heat. See Limit Switch Fault.
5 Flashes
Ignition Fault
No gas heating.
Heat call (W) Off.
Power reset for LED reset.
Unit unsuccessfully attempted ignition for 15
minutes.
Check igniter and flame sensor electrode
spacing, gaps, etc. Check flame sense and
igniter wiring. Check gas valve operation and
gas supply.
6 Flashes
Induced Draft Motor
Fault
If heat off: no gas heating.
If heat on: gas valve Off and
inducer On.
Inducer sense normal, or
heat call (W) Off.
Inducer sense On when heat call Off, or
inducer sense Off when heat call On. Check
wiring, voltage, and operation of IGC motor.
Check speed sensor wiring to IGC.
7 Flashes
Rollout Switch Lockout
Gas valve and igniter Off.
Indoor fan and inducer On.
Power reset.
Rollout switch has opened. Check gas valve
operation. Check induced-draft blower wheel
is properly secured to motor shaft.
8 Flashes
Internal Control Lockout
No gas heating.
Power reset.
IGC has sensed internal hardware or
software error. If fault is not cleared by
resetting 24 v power, replace the IGC.
9 Flashes
Temporary Software Lockout No gas heating.
1 hour auto reset, or power
reset.
Electrical interference is disrupting the IGC
software.
IGC
— Integrated Gas Unit Control
LED
— Light-Emitting Diode
Содержание WeatherExpert 48JC04
Страница 4: ...4 Fig 2 Unit Dimensional Drawing ...
Страница 5: ...5 Fig 2 Unit Dimensional Drawing cont ...
Страница 6: ...6 Fig 2 Unit Dimensional Drawing cont ...
Страница 24: ...24 Fig 46 48JC 04 06 Control Wiring Diagram ...
Страница 25: ...25 Fig 47 48JC 04 06 Power Wiring Diagram 208 230 460V Unit Shown ...
Страница 26: ...26 Fig 48 48JC 04 06 Power Wiring Diagram 575V Unit Shown ...
Страница 32: ......
Страница 33: ......