background image

11

The first device in a network connects directly to the bridge

and the others are wired sequentially in a daisy chain fashion.
Refer to Fig. 11 for an illustration of communication bus
wiring.
COMMUNICATION BUS WIRE SPECIFICATIONS —
The communication bus wiring is field-supplied and field-
installed. It consists of shielded three-conductor cable with
drain (ground) wire. The cable selected must be identical to the
Carrier Network communication bus wire used for the entire
network. See Table 3 for recommended cable.

Table 3 — Recommended Cables

NOTE: Conductors and drain wire must be at least 20 AWG
(American Wire Gage), stranded, and tinned copper. Individual con-
ductors must be insulated with PVC, PVC/nylon, vinyl, Teflon, or
polyethylene. An aluminum/polyester 100% foil shield and an outer
jacket of PVC, PVC/nylon, chrome vinyl, or Teflon with a minimum
operating temperature range of –20

 

C to 60

 

C is required.

CONNECTION TO THE COMMUNICATION BUS

1. Strip the ends of the red, white, and black conductors of

the communication bus cable.

2. Connect one end of the communication bus cable to

the bridge communication port labeled COMM2 (if
connecting on a secondary bus).

When connecting the communication bus cable, a color
code system for the entire network is recommended to
simplify installation and checkout. See Table 4 for the
recommended color code.

Table 4 — Color Code Recommendations

3. Connect the other end of the communication bus cable

to the terminal block labeled CCN in the bypass
controller. Following the color code in Table 4,
connect the Red (+) wire to Terminal 1. Connect the
White (ground) wire to Terminal 2. Connect the Black
(–) wire to Terminal 3.

4. Connect additional devices in a daisy chain fashion,

following the color coded wiring scheme in Table 4.
Refer to Fig. 11.

NOTE: The communication bus drain wires (shield) must
be tied together at each device. If the communication bus is
entirely within one building, the resulting continuous shield
must be connected to ground at only one single point. If the
communication bus cable exits from one building and enters
another building, connect the shields to ground at a light-
ning suppressor in each building where the cable enters or
exits (one point only).

MANUFACTURER

CABLE PART NO.

Alpha

2413 or 5463

American

A22503

Belden

8772

Columbia

02525

SIGNAL TYPE

COMMUNICATION

BUS WIRE COLOR

PLUG PIN

NUMBER

+

Red

1

Ground

White

2

Black

3

1

2

3

6

5

4

1

2

3

COMM 2

1

2

3

4

GND

1000 FT. MAXIMUM

DRAIN WIRE (TYP)

BLK (TYP)

WHT (TYP)

RED (TYP)

BYPASS

CONTROLLER

ZONE

CONTROLLER

SYSTEM

PILOT

ZONE

CONTROLLER

BRIDGE

(RECOMMENDED)

1

2

3

Fig. 11 — Communication Bus Wiring

Содержание VVT 33ZC

Страница 1: ...oordinate up to 31 additional zone controllers The purpose of the Linkage Coordinator zone relationship is to provide an efficient data path for communica tion between the zone controllers bypass cont...

Страница 2: ...ding the damper shaft through the actuator clamp assembly See Fig 2 for details Remove the controller wiring access cover Secure the controller by installing the screw provided through the grommet in...

Страница 3: ...3 Fig 2 Bypass Controller Dimensions Fig 1 Bypass Controller Details...

Страница 4: ...ENSOR 1 6 J5 3 1 G CCN 3 3 G 1 1 5 1 6 1 J4 1 2 NOT USED NOT USED NOT USED DAT NOT USED NOT USED NOT USED NOT USED DAT TO COMMUNICATION BUS TO FEEDBACK POTENTIOMETER LINE VOLTAGE EQUIPMENT GROUND TO D...

Страница 5: ...p the grommet into the hole until it is secure Pull on the leads of the duct sensor until the sensor is snug against the grommet 3 Connect the sensor leads to the bypass controller s termi nal board a...

Страница 6: ...reverse rotation the actuator switch may be changed to the CCW position LINKED ACTUATORS Field supplied linked actuators may be used to link to the bypass controller actuator Install the actuators pe...

Страница 7: ...7 Fig 7 High Torque Actuator Wiring...

Страница 8: ...8 Fig 8 High Torque Actuator with Linked Dampers Wiring...

Страница 9: ...9 Fig 9 Field Supplied Linked Damper Wiring...

Страница 10: ...10 Fig 10 Multiple Field Supplied Linked Damper Wiring...

Страница 11: ...s cable a color code system for the entire network is recommended to simplify installation and checkout See Table 4 for the recommended color code Table 4 Color Code Recommendations 3 Connect the othe...

Страница 12: ...ew bypass pressure set point 10 Read the airflow with a measuring device If the reading varies from the screen value force the value to the mea sured value Once the pressure sensor is forced the contr...

Страница 13: ...iable displays whether the leaving air temperature exceeds the heating or cooling limit configured in the Bypass Controller Service Configuration Table If Yes is displayed the System Pressure Set Poin...

Страница 14: ...zone controller to turn the system fan off If the communication fails the damper calibration process will be terminated and this decision will be Disabled When the fan is off the zone controller will...

Страница 15: ...NT Duct Temperature This variable displays the duct tempera ture at the bypass damper through a 10K thermistor with a measurement range from 40 to 245 F in 0 1 F increments Duct Temperature Display Un...

Страница 16: ...efault Value Close Max Damper Alarm Limit This decision is used to gener ate alarms during system heating and cooling modes When the bypass damper position is greater than this configured limit and th...

Страница 17: ...ease to within the zero tolerance 1 0 0 1 vdc of the sensor The alarm is disabled if this decision is set to Disable Press Sensr Cal Alarm Default Value Enable Display Range Enable Disable Duct Temp C...

Страница 18: ...is off When the fan is off the bypass controller will drive its damper to the fully closed position The bypass controller will read the value of the actuator s feedback potentiometer until the value...

Страница 19: ...l terminate the calibration Once at the fully open damper position the bypass controller will read the output voltage of the pressure sensor If the voltage reads within the range of 1 0 vdc 0 1 volt i...

Страница 20: ...b 11a 13a Copyright 2004 Carrier Corporation SEN Fig 12 Bypass Controller Operation Flow Chart LEGEND BP Bypass BP_SETPT System Pressure Setpoint DAT Duct Air Temperature DMP_POS Damper Position LAT L...

Отзывы: