background image

58PAV

Upflow Induced-Combustion Furnaces

Installation, Start-Up, and Operating Instructions

Sizes 045-155, Series 160 (LIMITED)

NOTE:

Read the entire instruction manual before starting the

installation.

Index

Page

SAFETY CONSIDERATIONS .....................................................1
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS

PROCEDURE ...........................................................................3
Dimensional Drawing ..............................................................2
Clearances From Combustible Materials .................................3

INTRODUCTION.......................................................................3-4
LOCATION ..................................................................................4

General ......................................................................................4
Location Relative to Cooling Equipment ................................4
Hazardous Locations.................................................................4

AIR FOR COMBUSTION AND VENTILATION ......................5

Unconfined Space .....................................................................5
Confined Space .........................................................................5

AIR DUCTS................................................................................5-6

General Requirements ...........................................................5-6
Ductwork Acoustical Treatment...............................................6
Supply-Air Connections............................................................6
Return-Air Connections ............................................................7

FILTER ARRANGEMENT...........................................................7
LEVELING LEGS (IF REQUIRED) ............................................7
GAS PIPING ..................................................................................8
ELECTRICAL CONNECTIONS...............................................8-9

115-v Wiring.............................................................................8
24-v Wiring...............................................................................9
Accessories................................................................................9

VENTING ....................................................................................10
START-UP, ADJUSTMENT, AND SAFETY CHECK .......10-17

General ....................................................................................10
Sequence Of Operation...........................................................10
Heating Mode..........................................................................12
Cooling Mode .........................................................................12
Continuous Blower Mode.......................................................12
Heat Pump Mode ....................................................................12
Start-Up Procedures...........................................................12-17
Adjustments.............................................................................13
Set Gas Input Rate..................................................................13
Set Temperature Rise ........................................................13-16
Set Thermostat Heat Anticipator............................................17
Check Safety Controls ............................................................17
Checklist..................................................................................18

SAFETY CONSIDERATIONS

Installing and servicing heating equipment can be hazardous due to
gas and electrical components. Only trained and qualified person-
nel should install, repair, or service heating equipment.

Untrained personnel can perform basic maintenance functions
such as cleaning and replacing air filters. All other operations must
be performed by trained service personnel. When working on
heating equipment, observe precautions in the literature, on tags,
and on labels attached to or shipped with the unit and other safety
precautions that may apply.

In the United States, follow all safety codes including the National
Fuel Gas Code (NFGC) NFPA 54-1999/ANSI Z223.1-1999 and
the Installation Standards, Warm Air Heating and Air Condition-
ing Systems (NFPA 90B) ANSI/NFPA 90B.
In Canada, refer to the CAN/CGA-B149.1- and .2-M95 National
Standard of Canada, Natural Gas and Propane Installation Codes
(NSCNGPIC).
Wear safety glasses and work gloves. Have fire extinguisher
available during start-up and adjustment procedures and service
calls.

Recognize safety information. This is the safety-alert symbol

.

When you see this symbol on the furnace and in instructions or
manuals, be alert to the potential for personal injury.

Understand the signal words DANGER, WARNING, CAUTION,
and NOTE. These words are used with the safety-alert symbol.
DANGER identifies the most serious hazards which will result in
severe personal injury or death. WARNING signifies a hazard
which could result in personal injury or death. CAUTION is used
to identify unsafe practices which would result in minor personal
injury or product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation, reliability,
or operation.

These instructions cover minimum requirements and conform to
existing national standards and safety codes. In some instances,
these instructions exceed certain local codes and ordinances,
especially those that may not have kept up with changing residen-
tial construction practices. We require these instructions as a
minimum for a safe installation.

ama

CERTIFIED

REGISTERED QUALITY SYSTEM

Visit www.carrier.com

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Book 1

4

Tab

6a 8a

PC 101

Catalog No. 535-756

Printed in U.S.A.

Form 58PA-15SI

Pg 1

1-00

Replaces: New

Содержание UPFLOW INDUCED-COMBUSTION FURNACES 58PAV

Страница 1: ...autions that may apply In the United States follow all safety codes including the National Fuel Gas Code NFGC NFPA 54 1999 ANSI Z223 1 1999 and the Installation Standards Warm Air Heating and Air Cond...

Страница 2: ...l 7 8 in dia holes are located in the top plate 2 Minimum return air openings at furnace based on metal duct If flex duct is used see flex duct manufacturer s recommendations for equivalent diameters...

Страница 3: ...essory gas conversion kit as listed on the furnace rating plate is required to convert furnace for use with propane gas The design of this furnace line is not A G A C G A certified for installation in...

Страница 4: ...me of these compounds are found in paneling and dry wall adhesives paints thinners masonry cleaning materials and many other solvents commonly used in the construction process Excessive exposure to co...

Страница 5: ...enings for structures not usually tight a Each opening MUST have at least 1 sq in of free area per 1000 Btuh of total input for all equipment within the confined space but not less than 100 sq in per...

Страница 6: ...Space A89012 SUPPLY AIR 6 MIN FRONT RETURN AIR VENT THROUGH ROOF 1 SQ IN PER 1000 BTUH IN DOOR OR WALL 12 MAX 1 SQ IN PER 1000 BTUH IN DOOR OR WALL 12 MAX INTERIOR HEATED SPACE Minimum opening size i...

Страница 7: ...t a filter or with filter access door removed Failure to follow this warning can cause fire personal injury or death Step 6 Leveling Legs If Required When the furnace is used with side inlet s and lev...

Страница 8: ...n be loosened before pressure testing After all connections have been made purge the lines and check for leakage with regulated gas supply pressure Never purge a gas line into a combustion chamber Nev...

Страница 9: ...MAXIMUM WIRE LENGTH FT MAXIMUM FUSE OR CKT BKR AMPS Maximum Minimum 045 08 115 60 1 127 104 6 0 14 47 15 045 12 115 60 1 127 104 8 3 14 34 15 070 08 115 60 1 127 104 5 9 14 47 15 070 12 115 60 1 127...

Страница 10: ...ust be made at the furnace 24 v terminal block on the control The gas service pressure must not exceed 0 5 psig 14 in wc but must be no less than 0 16 psig 4 5 in wc This furnace is equipped with a ma...

Страница 11: ...FRS1 FRS2 LGPS PL7 PRS FSE 9 1 5 CPU HSIR IDR BLWR Y G C R W SEC 1 HI LO GVR GVR 1 OM OM 10 4 6 2 HUM NEUTRAL L2 ILK FU2 L1 ILK GND GND RED BLU ORN WHT WHT WHT RED ORN WHT GRN RED WHT RED GRN YEL BLU...

Страница 12: ...heating speed 4 Heat pump mode When installed with a heat pump the furnace control auto matically changes the timing sequence to avoid long blower off time during demand defrost cycles When the W Y or...

Страница 13: ...tlined in item c 4 Burner flame should be clear blue almost transparent See Fig 13 c Verify natural gas input rate by clocking gas meter NOTE High Altitude Adjustment United States At installation alt...

Страница 14: ...3 3 0 43 3 1 43 3 2 43 3 3 Altitudes 950 43 2 7 43 2 8 43 2 9 43 3 0 43 3 1 2000 975 43 2 6 43 2 7 43 2 8 43 2 9 43 2 9 to 1000 43 2 5 43 2 5 43 2 6 43 2 7 43 2 8 4500 1025 43 2 3 43 2 4 43 2 5 43 2 6...

Страница 15: ...0 43 2 5 43 2 6 43 2 7 43 2 8 43 2 9 to 775 43 2 4 43 2 5 43 2 5 43 2 6 43 2 7 800 43 2 2 43 2 3 43 2 4 43 2 5 43 2 5 7000 825 43 2 1 43 2 2 43 2 2 43 2 3 43 2 4 850 48 3 7 43 2 0 43 2 1 43 2 2 43 2 3...

Страница 16: ...te Multiplier for U S A ALTITUDE FT PERCENT OF DERATE DERATE MULTIPLIER FACTOR FOR U S A 0 2000 0 1 00 2001 3000 8 12 0 90 3001 4000 12 16 0 86 4001 5000 16 20 0 82 5001 6000 20 24 0 78 6001 7000 24 2...

Страница 17: ...itions a Disconnect power to furnace and remove vent connector from furnace flue collar Be sure to allow time for vent pipe to cool down before removing b Restore power to furnace and set room thermos...

Страница 18: ...tools instruments and clean up debris 2 Verify manual reset switches have continuity 3 Ensure blower and control access doors are properly installed 4 Cycle test furnace with room thermostat 5 Check o...

Страница 19: ...s ____________ 1 4 in Upward Slope ____________ Joints Secure ____________ See Vent Table Instructions CHECKLIST START UP ____________ Gas Input Rate Set Within 2 percent of Rating Plate ____________...

Страница 20: ...vice Training plus hands on the products in our labs can mean increased confidence that really pays dividends in faster troubleshooting fewer callbacks Course descriptions and schedules are in our cat...

Отзывы: