Table 6—Model 58PAV Orifice Size* and Manifold Pressure for Correct Input

(Tabulated Data Based on 22,000 Btuh per Burner, Derated 4 Percent per 1000 Ft Above Sea Level)

ALTITUDE

RANGE

(FT)

AVG GAS

HEAT VALUE

AT ALTITUDE

(BTU/CU FT)

SPECIFIC GRAVITY OF NATURAL GAS

0.58

0.60

0.62

0.64

0.66

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

U.S.A.

and

Canada

850

42

3.6

42

3.8

41

3.5

41

3.6

41

3.7

875

42

3.4

42

3.6

42

3.7

42

3.8

41

3.5

900

42

3.2

42

3.4

42

3.5

42

3.6

42

3.7

0

925

43

3.7

42

3.2

42

3.3

42

3.4

42

3.5

950

43

3.6

43

3.7

43

3.8

42

3.2

42

3.3

to

975

43

3.4

43

3.5

43

3.6

43

3.7

43

3.8

1000

43

3.2

43

3.3

43

3.4

43

3.5

43

3.6

2000

1025

44

3.5

43

3.2

43

3.3

43

3.4

43

3.5

1050

44

3.3

44

3.4

44

3.6

43

3.2

43

3.3

1075

45

3.8

44

3.3

44

3.4

44

3.5

43

3.2

1100

45

3.7

45

3.8

44

3.2

44

3.4

44

3.5

ALTITUDE

RANGE

(FT)

AVG GAS

HEAT VALUE

AT ALTITUDE

(BTU/CU FT)

SPECIFIC GRAVITY OF NATURAL GAS

0.58

0.60

0.62

0.64

0.66

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

U.S.A.

and

Canada

U.S.A.

775

42

3.4

42

3.5

42

3.6

42

3.7

42

3.8

Altitudes

800

43

3.8

42

3.3

42

3.4

42

3.5

42

3.6

2001

825

43

3.6

43

3.7

42

3.2

42

3.3

42

3.4

to

850

43

3.4

43

3.5

43

3.6

43

3.8

42

3.2

3000

875

43

3.2

43

3.3

43

3.4

43

3.5

43

3.6

or

900

43

3.0

43

3.1

43

3.2

43

3.3

43

3.4

Canada

925

43

2.9

43

3.0

43

3.1

43

3.2

43

3.3

Altitudes

950

43

2.7

43

2.8

43

2.9

43

3.0

43

3.1

2000

975

43

2.6

43

2.7

43

2.8

43

2.9

43

2.9

to

1000

43

2.5

43

2.5

43

2.6

43

2.7

43

2.8

4500

1025

43

2.3

43

2.4

43

2.5

43

2.6

43

2.7

ALTITUDE

RANGE

(FT)

AVG GAS

HEAT VALUE

AT ALTITUDE

(BTU/CU FT)

SPECIFIC GRAVITY OF NATURAL GAS

0.58

0.60

0.62

0.64

0.66

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

U.S.A.

Only

750

43

3.8

42

3.3

42

3.4

42

3.5

42

3.6

775

43

3.6

43

3.7

43

3.8

42

3.3

42

3.4

800

43

3.4

43

3.5

43

3.6

43

3.7

43

3.8

3001

825

43

3.2

43

3.3

43

3.4

43

3.5

43

3.6

850

43

3.0

43

3.1

43

3.2

43

3.3

43

3.4

to

875

43

2.8

43

2.9

43

3.0

43

3.1

43

3.2

900

43

2.7

43

2.8

43

2.9

43

2.9

43

3.0

4000

925

43

2.5

43

2.6

43

2.7

43

2.8

43

2.9

950

43

2.4

43

2.5

43

2.6

43

2.6

43

2.7

975

43

2.3

43

2.4

43

2.4

43

2.5

43

2.6

1000

43

2.2

43

2.2

43

2.3

43

2.4

43

2.5

ALTITUDE

RANGE

(FT)

AVG GAS

HEAT VALUE

AT ALTITUDE

(BTU/CU FT)

SPECIFIC GRAVITY OF NATURAL GAS

0.58

0.60

0.62

0.64

0.66

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

U.S.A.

Only

725

43

3.6

43

3.7

42

3.2

42

3.3

42

3.4

750

43

3.4

43

3.5

43

3.6

43

3.7

43

3.8

775

43

3.2

43

3.3

43

3.4

43

3.5

43

3.6

4001

800

43

3.0

43

3.1

43

3.2

43

3.3

43

3.4

825

43

2.8

43

2.9

43

3.0

43

3.1

43

3.2

to

850

43

2.6

43

2.7

43

2.8

43

2.9

43

3.0

875

43

2.5

43

2.6

43

2.6

43

2.7

43

2.8

5000

900

43

2.3

43

2.4

43

2.5

43

2.6

43

2.7

925

43

2.2

43

2.3

43

2.4

43

2.4

43

2.5

950

43

2.1

43

2.2

43

2.2

43

2.3

43

2.4

* Orifices sizes shown in BOLD are factory installed.

14

Содержание UPFLOW INDUCED-COMBUSTION FURNACES 58PAV

Страница 1: ...autions that may apply In the United States follow all safety codes including the National Fuel Gas Code NFGC NFPA 54 1999 ANSI Z223 1 1999 and the Installation Standards Warm Air Heating and Air Cond...

Страница 2: ...l 7 8 in dia holes are located in the top plate 2 Minimum return air openings at furnace based on metal duct If flex duct is used see flex duct manufacturer s recommendations for equivalent diameters...

Страница 3: ...essory gas conversion kit as listed on the furnace rating plate is required to convert furnace for use with propane gas The design of this furnace line is not A G A C G A certified for installation in...

Страница 4: ...me of these compounds are found in paneling and dry wall adhesives paints thinners masonry cleaning materials and many other solvents commonly used in the construction process Excessive exposure to co...

Страница 5: ...enings for structures not usually tight a Each opening MUST have at least 1 sq in of free area per 1000 Btuh of total input for all equipment within the confined space but not less than 100 sq in per...

Страница 6: ...Space A89012 SUPPLY AIR 6 MIN FRONT RETURN AIR VENT THROUGH ROOF 1 SQ IN PER 1000 BTUH IN DOOR OR WALL 12 MAX 1 SQ IN PER 1000 BTUH IN DOOR OR WALL 12 MAX INTERIOR HEATED SPACE Minimum opening size i...

Страница 7: ...t a filter or with filter access door removed Failure to follow this warning can cause fire personal injury or death Step 6 Leveling Legs If Required When the furnace is used with side inlet s and lev...

Страница 8: ...n be loosened before pressure testing After all connections have been made purge the lines and check for leakage with regulated gas supply pressure Never purge a gas line into a combustion chamber Nev...

Страница 9: ...MAXIMUM WIRE LENGTH FT MAXIMUM FUSE OR CKT BKR AMPS Maximum Minimum 045 08 115 60 1 127 104 6 0 14 47 15 045 12 115 60 1 127 104 8 3 14 34 15 070 08 115 60 1 127 104 5 9 14 47 15 070 12 115 60 1 127...

Страница 10: ...ust be made at the furnace 24 v terminal block on the control The gas service pressure must not exceed 0 5 psig 14 in wc but must be no less than 0 16 psig 4 5 in wc This furnace is equipped with a ma...

Страница 11: ...FRS1 FRS2 LGPS PL7 PRS FSE 9 1 5 CPU HSIR IDR BLWR Y G C R W SEC 1 HI LO GVR GVR 1 OM OM 10 4 6 2 HUM NEUTRAL L2 ILK FU2 L1 ILK GND GND RED BLU ORN WHT WHT WHT RED ORN WHT GRN RED WHT RED GRN YEL BLU...

Страница 12: ...heating speed 4 Heat pump mode When installed with a heat pump the furnace control auto matically changes the timing sequence to avoid long blower off time during demand defrost cycles When the W Y or...

Страница 13: ...tlined in item c 4 Burner flame should be clear blue almost transparent See Fig 13 c Verify natural gas input rate by clocking gas meter NOTE High Altitude Adjustment United States At installation alt...

Страница 14: ...3 3 0 43 3 1 43 3 2 43 3 3 Altitudes 950 43 2 7 43 2 8 43 2 9 43 3 0 43 3 1 2000 975 43 2 6 43 2 7 43 2 8 43 2 9 43 2 9 to 1000 43 2 5 43 2 5 43 2 6 43 2 7 43 2 8 4500 1025 43 2 3 43 2 4 43 2 5 43 2 6...

Страница 15: ...0 43 2 5 43 2 6 43 2 7 43 2 8 43 2 9 to 775 43 2 4 43 2 5 43 2 5 43 2 6 43 2 7 800 43 2 2 43 2 3 43 2 4 43 2 5 43 2 5 7000 825 43 2 1 43 2 2 43 2 2 43 2 3 43 2 4 850 48 3 7 43 2 0 43 2 1 43 2 2 43 2 3...

Страница 16: ...te Multiplier for U S A ALTITUDE FT PERCENT OF DERATE DERATE MULTIPLIER FACTOR FOR U S A 0 2000 0 1 00 2001 3000 8 12 0 90 3001 4000 12 16 0 86 4001 5000 16 20 0 82 5001 6000 20 24 0 78 6001 7000 24 2...

Страница 17: ...itions a Disconnect power to furnace and remove vent connector from furnace flue collar Be sure to allow time for vent pipe to cool down before removing b Restore power to furnace and set room thermos...

Страница 18: ...tools instruments and clean up debris 2 Verify manual reset switches have continuity 3 Ensure blower and control access doors are properly installed 4 Cycle test furnace with room thermostat 5 Check o...

Страница 19: ...s ____________ 1 4 in Upward Slope ____________ Joints Secure ____________ See Vent Table Instructions CHECKLIST START UP ____________ Gas Input Rate Set Within 2 percent of Rating Plate ____________...

Страница 20: ...vice Training plus hands on the products in our labs can mean increased confidence that really pays dividends in faster troubleshooting fewer callbacks Course descriptions and schedules are in our cat...

Отзывы: