To wire the ZS or SPT sensor to the UPC Open
1
Partially cut, then bend and pull off the outer jacket of the Rnet cable(s). Do not nick the inner insulation.
Strip about .25 inch (.6 cm) of the inner insulation from each wire.
Outer Jacket
Inner insulation
.25 in.
(.6 cm)
2
Wire each terminal on the sensor to the same terminal on the controller. See diagram below.
NOTE
Carrier recommends that you use the following Rnet wiring scheme:
Connect this wire...
To this terminal...
Red
Black
White
Green
+12V
Rnet-
Rnet+
Gnd
Wireless sensor overview
The Carrier wireless sensors, designed for zone control, are low-power wireless devices that use light-harvesting
through solar panels as their primary power source. The wireless line of sensors includes the models shown in the
list below. All are available in 868, 902, and 928 MHz radio frequency. The sensors are thermistor-based
temperature sensors that may optionally sense humidity
Wireless sensors communicate through a Wireless Adapter, which is wired to the Rnet port of the controller.
REQUIREMENTS
•
A v6.5 or later i-Vu® system
•
v6.04-xxx or later controller drivers