28
LOCAL OPERATING TYPE
Heating/Cooling
Setpoint selection (Local)
Setpoint switch
Schedule 2 status
Active setpoint
Cooling
sp-1
-
-
Cooling setpoint 1
Cooling
sp-2
-
-
Cooling setpoint 2
Cooling
auto
-
occupied
Cooling setpoint 1
Cooling
auto
-
unoccupied
Cooling setpoint 2
Heating
sp-1
-
-
Heating setpoint 1
Heating
sp-2
-
-
Heating setpoint 2
Heating
auto
-
occupied
Heating setpoint 1
Heating
auto
-
unoccupied
Heating setpoint 2
REMOTE OPERATING TYPE
Heating/Cooling
Setpoint selection (Local)
Setpoint switch
Schedule 2 status
Active setpoint
Cooling
-
sp1
-
Cooling setpoint 1
Cooling
-
sp2
-
Cooling setpoint 2
Cooling
-
auto
occupied
Cooling setpoint 1
Cooling
-
auto
unoccupied
Cooling setpoint 2
Heating
-
sp1
-
Heating setpoint 1
Heating
-
sp2
-
Heating setpoint 2
Heating
-
auto
occupied
Heating setpoint 1
Heating
-
auto
unoccupied
Heating setpoint 2
NETWORK OPERATING TYPE
Heating/Cooling
Setpoint selection (Local)
Setpoint switch
Schedule 2 status
Active setpoint
Cooling
sp-1
-
-
Cooling setpoint 1
Cooling
sp-2
-
-
Cooling setpoint 2
Cooling
auto
-
occupied
Cooling setpoint 1
Cooling
auto
-
unoccupied
Cooling setpoint 2
Cooling
auto
-
-
Cooling setpoint 2
Heating
sp-1
-
-
Heating setpoint 1
Heating
sp-2
-
-
Heating setpoint 2
Heating
auto
-
occupied
Heating setpoint 1
Heating
auto
-
unoccupied
Heating setpoint 2
Heating
auto
-
-
Heating setpoint 2
8.7 - Control point
The control point represents the water temperature that
the unit must produce. The required capacity can be
decreased depending on the unit load operating
conditions.
Control point = Active se Reset
The control point is calculated based on the active setpoint
and the reset calculation. The forced value can be used
instead of any other setpoint calculation only when the
unit is in the Network operating type.
To verify the control point
1. Navigate to the Main menu.
2. Select
General Parameters
(GENUNIT).
3. Verify
Control Point
[CTRL_PNT].
Control Point [CTRL_PNT]
-20.0 to 67.0°C
-4.0 to 153.0°F
8.7.1 - Active setpoint
Two setpoints can be selected, where the first setpoint is
used during occupied periods, whereas the second one is
used during unoccupied periods.
Depending on the current operation type, the active
setpoint can be selected manually via the Main menu on
the user interface, with the volt-free user contacts, with
network commands (CCN or BACnet) or automatically
with the setpoint time schedule (schedule 2).
The following tables summarise possible selections
depending on the control operating type (Local, Remote
or Network) and the following parameters:
•
Heating or Cooling operating mode [HC_SEL]
:
Heat/
Cool select
(GENUNIT – General Parameters).
•
Setpoint selection [SP_SEL]
:
Setpoint select
permits
selection of the active setpoint if the unit is in the
Local operating type (GENUNIT – General
Parameters
).
•
Setpoint switch status [SETP_SW]
:
Remote Setpoint
Switch
(INPUTS – Inputs).
•
Occupied state of dual setpoint time schedule
[SP_OCC]
: Schedule for setpoint selection.