Outputs Menu – OUTPUTS
Point name
Status
Unit
Displayed text*
Description
1
CP_A1
off/on
-
Compressor A1 Output
Compressor A1 status
2
CP_A2
off/on
-
Compressor A2 Output
Compressor A2 status
3
CP_A3
off/on
-
Compressor A3 Output
Compressor A3 status
4
FAN_A1LS
off/on
-
Fan A1LS Output
Fan A1 low speed status
5
FAN_A1HS
off/on
-
Fan A1HS Output
Fan A1 high speed status
6
FAN_A2LS
off/on
-
Fan A2LS Output
Fan A2 low speed status
7
FAN_A2HS
off/on
-
Fan A2HS Output
Fan A2 high speed status
8
HD_POS_A
-
%
Head Pressure Position A
Head pressure, circuit A
9
EXVPosA
-
%
EXV Position Circuit A
EXV position, circuit A
10
EXVNPosA
-
%
EXV Next Pos Circuit A
EXV next position, circuit A
11
RV_A
off/on
-
4 Way Refrigerant ValveA
4-way refrigerant valve, circuit A: Used to manage cooling / heating
/ defrost operation (heat pumps)
12
CP_B1
off/on
-
Compressor B1 Output
Compressor B1 status
13
CP_B2
off/on
-
Compressor B2 Output
Compressor B2 status
14
FAN_B1LS
off/on
-
Fan B1LS Output
Fan B1 low speed status
15
FAN_B1HS
off/on
-
Fan B1HS Output
Fan B1 high speed status
16
HD_POS_B
-
%
Head Pressure Position B
Head pressure, circuit B
17
EXVPosB
-
%
EXV Position Circuit B
EXV position, circuit B
18
EXVNPosB
-
%
EXV Next Pos Circuit B
EXV next position, circuit B
19
RV_B
off/on
-
4 Way Refrigerant ValveB
4-way refrigerant valve, circuit B: Used to manage cooling/heating/
defrost operation (heat pumps)
20
C_HEATER
off/on
-
Cooler & Drain Pan Heatr
Water exchanger / Drain pan heater
21
BOILER
off/on
-
Boiler Command
Boiler status
22
EHS_STEP
-
-
Electrical Heat Stage
Electric heating stages
23
ALARM_R
off/on
-
Alarm Relay Status
Alarm relay status
24
RUN_R
off/on
-
Running Status
Unit ON relay
25
OIL_VALV
off/on
-
Oil Valve Status
Oil valve status
*Depends on the selected language (English by default).
Pump Status Menu – PUMPSTAT
Point name
Status
Unit
Displayed text*
Description
1
CPUMP_1
off/on
-
Water Pump #1 Command
Water pump 1 command
2
CPUMP_2
off/on
-
Water Pump #2 Command
Water pump 2 command
3
ROT_PUMP
no/yes
-
Rotate Pumps Now?
Water exchanger pumps rotation
4
W_P_IN
-
kPa / PSI
Inlet Water Pressure
Inlet water pressure
5
W_P_OUT
-
kPa / PSI
Outlet Water Pressure
Outlet water pressure
6
WP_CALIB
no/yes
-
Water Pressure Calibrat
Water pressure calibration
7
WP_OFFST
-
kPa / PSI
Water Pressure Offset
Water pressure offset
8
DP_FILTR
-
kPa / PSI
Delta Water Press. Filt
Delta water pressure filtration
9
WP_MIN
-
kPa / PSI
Mini Water Pressure
Minimum water pressure
10
WAT_FLOW
-
l/s / GPS
Water Flow
Water flow status
11
CAPPOWER
-
kW
Actual Power Capacity
Actual power capacity
12
p_dt_spt
-
^C / ^F
Water DT Setpoint
Water discharge temperature setpoint
13
p_dp_spt
-
kPa / PSI
Water DP Setpoint
Water discharge pressure setpoint
14
drvp_pct
-
%
Pump Drive Percent
Pump drive percent
15
drvp_pwr
-
kW
Pump Drive Power
Pump drive power
16
drvp_i
-
A
Pump Drive Amps
Pump drive (A)
17
drvp_ver
xxx
-
Pump Drive Version
Pump drive version
*Depends on the selected language (English by default).