8.5.1 - Variable speed pumps control

30RBS chillers and 30RQS

 heat pumps may be fitted with 

one or two variable speed pumps. 

Variable speed pumps give the possibility of saving the 

pumping energy cost, providing precise water flow control 

and improving the overall performance of the system. The 

frequency inverter continuously regulates the flow rate to 

minimise the pump power consumption at full load and 
part load.

Water flow management methods are as follows:
1)  Fixed speed control (the control ensures a constant 

pump speed based on compressor capacity). 

2)  Water flow control based on constant water delta 

pressure (the control continuously acts on the pump 
speed to ensure a constant delta pressure).

3)  Water flow control based on constant delta T on the 

water exchanger.

IMPORTANT: 

Pump speed configuration can be 

performed only by Carrier service.

8.5.2 - Pumps configuration

The control can command internal fixed speed or variable 

speed pumps as well as customer pumps. Variable speed 

pumps may also be configured as fixed speed pumps (see 
also section 8.5.1).

Basic pump configuration can be performed via the 
Configuration menu (PUMPCONF – Pump 
Configuration). Only logged-in users can access the menu. 

The unit must be stopped.

To set pumps sequence

1.  Navigate to the Configuration menu.

2. Select 

Pump Configuration

 (PUMPCONF).

3. Set 

Water Pumps Sequence

 [pump_seq].

Water Pumps Sequence [pump_seq]

0

No Pump

1

One Pump Only

2

Two Pumps Auto

3

Pump#1 Manual

4

Pump#2 Manual

8.5.3 - Automatic pump selection

If two pumps are controlled and the reversing function has 
been selected (PUMPCONF – Pump Configuration), the 

control balances the pump run time to match the 

configured pump changeover delay. If this delay has 

elapsed, the pump reversing function is activated.

To set pump automatic rotation delay

1.  Navigate to the Configuration menu.

2. Select 

Pump Configuration 

(PUMPCONF).

3. Set 

Pump Rotation Delay

 [pump_del].

Pump Rotation Delay [pump_del]

24 to 3000h

48h

8.5.4 - Customer pumps configuration

Units fitted with external pumps may have only fixed 

speed pumps available. Customer pumps may be 

configured as follows:

Pump available

Pumps sequence (PUMPCONF)

No pump

0 (no pump)

One single speed pump

1 (one pump only)

Two single speed pumps

2 (two pumps auto) 
3 (pump#1 manual)
4 (pump#2 manual)

Units with customer pumps are fitted with the flow switch, 
allowing for the water flow control. For more information 

about actuators, see 

Water flow switch

 in section 4.7.

8.5.5 - Pumps protection

The control provides the option to automatically start the 
pump each day at 14:00 for 2 seconds when the unit is off. 

If the unit is fitted with two pumps, the first pump is started 

on even days and the second pump is started on odd days. 
Starting the pump periodically for a few seconds extends 
the lifetime of the pump bearings and the tightness of the 
pump seal.
 
Periodical pump quick start can be selected via the 

Configuration menu (PUMPCONF – Pump 
Configuration).

To set periodical pump quick start

1.  Navigate to the Configuration menu.

2. Select 

Pump Configuration

 (PUMPCONF).

3. Set 

Pump Sticking Protection

 [pump_per].

Pump Sticking Protection [pump_per]

No/Yes

Yes

8.6 - Hydronic kit option

The hydronic kit option allows for continuous monitoring 

of the water flow rate (PUMPSTAT – Pump Status). 

The hydronic kit provides the option to measure the 
following parameters:

• 

Inlet and outlet water pressure. 

• 

Water exchanger flow rate.

The water flow rate is based on the pressure difference 

between the inlet and outlet pressures and the pressure 
drop curves. 

Hydronic kit option with variable speed pumps

For units with variable speed pumps, this option allows for 
the automatic adjustment of the pump speed necessary to 

maintain the correct water flow rate. Water flow control 

can be based on compressor usage, constant delta pressure 
or constant temperature difference. For more information 
on variable speed pumps control, see also section 8.5.1.

Содержание Touch Pilot Junior

Страница 1: ...CONTROLS MANUAL Touch Pilot Junior 30RBS 39 160 30RQS 39 160 Original document...

Страница 2: ...1 5 6 Stop the unit 11 5 7 Set the schedule 12 5 8 Manage display settings 12 5 9 Monitor unit parameters 13 5 10 Modify unit parameters 14 5 11 Override system configuration 14 6 WEB CONNECTION 15 6...

Страница 3: ...ation and forms no part of any offer for sale or any sale contract The manufacturer reserves the right to change the design at any time without notice 9 DIAGNOSTICS 32 9 1 Control diagnostics 32 9 2 A...

Страница 4: ...the language of the system all labels will be in the language selected by the user Please read all instructions prior to proceeding with any work Pay attention to all safety warnings The information p...

Страница 5: ...box covers and motor frames with great care 2 CONTROL OVERVIEW 2 1 Control system Carrier 30RBS chillers and 30RQS heat pumps come with a Touch Pilot Junior control that serves as the user interface a...

Страница 6: ...mpressor technology X X Water exchanger heater X X Defrost mechanism X Diagnostics X X Variable speed fans O O High static fan O O Fixed or variable speed pumps O O Cooling control X X Heating control...

Страница 7: ...reenLEDflashescontinuouslyonallboardstoshow thattheboardiscommunicatingcorrectlyoveritsinternal bus LENbus IfthegreenLEDisnotflashing this indicatesaLENbuswiringproblemoraconfigurationissue 4 HARDWARE...

Страница 8: ...erating mode is selected based on OAT 4 8 2 Volt free setpoint selection contact This dry contact input is used to switch between setpoints It is active only when the control is in Remote mode Cooling...

Страница 9: ...rent unit operating status etc Resistive touch screen technology Web connectivity Custom language support 5 1 Touch Pilot Junior overview Touch Pilot Junior provides access to the following screens We...

Страница 10: ...10 5 2 Touch Pilot Junior menu structure...

Страница 11: ...r starting the user interface It displays the application name as well as the current software version number Home button Software version number To exit the Welcome screen press Information message b...

Страница 12: ...f the controller change the system of measurement imperial or metric and enter a password to gain access to more control options To access the User Login screen press the Log button in the upper right...

Страница 13: ...t Junior allows users to add new languages to the control To learn more about language customization please contact your local Carrier representative 5 8 3 System of measurement The control offers the...

Страница 14: ...rd protected see also section 5 8 1 Press the field corresponding to the parameter to be modified and introduce all the necessary changes Press the Up Down buttons to navigate between the screens Once...

Страница 15: ...6 WEB CONNECTION 6 1 Web interface The Touch Pilot Junior control can be accessed via a web browser Internet Explorer Mozilla Firefox etc Connection is from a PC using a web browser with Java CAUTION...

Страница 16: ...OOL Heat Cool status Heating Cooling status 6 HC_SEL 0 to 2 Heat Cool Select Heating Cooling selection 0 Cool 1 Heat 2 Auto 0 Cool 1 Heat 2 Auto 7 SP_SEL 0 to 2 Setpoint Select Setpoint select 0 Auto...

Страница 17: ...ion 1 DP_A kPa PSI Discharge Pressure A Compressor discharge pressure circuit A 2 SP_A kPa PSI Suction Pressure A Compressor suction pressure circuit A 3 DP_B kPa PSI Discharge Pressure B Compressor d...

Страница 18: ...pumps 20 C_HEATER off on Cooler Drain Pan Heatr Water exchanger Drain pan heater 21 BOILER off on Boiler Command Boiler status 22 EHS_STEP Electrical Heat Stage Electric heating stages 23 ALARM_R off...

Страница 19: ...2 FC_FAN3S 0 to 999999 FC Fan Stage 3 Start Number of starts FC fan stage 3 13 FC_FAN3H 0 to 999999 FC Fan Stage 3 Hours Operating hours FC fan stage 3 14 FC_FAN4S 0 to 999999 FC Fan Stage 4 Start Num...

Страница 20: ...itch Limit Setpoint 2 Switch limit setpoint 2 10 lim_sp3 0 to 100 100 Switch Limit Setpoint 3 Switch limit setpoint 3 11 min_sct 26 7 to 60 0 80 0 to 140 0 40 0 104 0 C F Desuperheater Min Sct Desuper...

Страница 21: ...ked if Pump Off Water flow is checked when the pump is off Depends on the selected language English by default Heat Cool Config Menu HCCONFIG Point name Status Default Unit Displayed text Description...

Страница 22: ...Depends on the selected language English by default Schedule Menu SCHEDULE Point name Status Default Unit Displayed text Description 1 OCCPC01S OCCPC01S Schedule Menu Unit on off time schedule 2 OCCPC...

Страница 23: ...s Daylight sav time on Daylight saving time on off 8 no yes Today is a holiday The present day is a holiday 9 tom_hol no yes Tomorrow is a holiday The following day is a holiday Depends on the selecte...

Страница 24: ...the unit shuts down regardless of the active operating type General alarm The unit shuts down due to failure Active operating type Parameter status Result LOFF L C L SC Rem Net Mast Start stop force...

Страница 25: ...ling or heating is determined based on the following parameters Control type Local Remote or Network Local heat cool selection hc_sel Heat Cool selection when the unit is running in Local mode Control...

Страница 26: ...when mechanical heating is insufficient 8 4 1 Boiler control Boiler is activated when the outside air temperature is below the user configured boiler outdoor temperature threshold which is by default...

Страница 27: ...guration PUMPCONF 3 Set Pump Rotation Delay pump_del Pump Rotation Delay pump_del 24 to 3000h 48h 8 5 4 Customer pumps configuration Units fitted with external pumps may have only fixed speed pumps av...

Страница 28: ...represents the water temperature that the unit must produce The required capacity can be decreased depending on the unit load operating conditions Control point Active setpoint Reset The control poin...

Страница 29: ...etpoint 1 2 3 lim_sp1 2 3 Switch Limit Setpoint 1 2 3 lim_sp1 2 3 0 to 100 100 To verify lag limit set by the master unit 1 Navigate to the Main menu 2 Select General Parameters GENUNIT 3 Verify Lag C...

Страница 30: ...ve when the outdoor air temperature is below 0 C 32 F Starting free cooling The free cooling mode is ENABLED when the free cooling OAT fc_oat is below the water loop temperature and the start threshol...

Страница 31: ...heat from the refrigerant to desuperheat it to a lower pressure refrigerant The vapour that goes into the desuperheater is not fully condensed therefore the refrigerant vapour must be channelled to a...

Страница 32: ...the unit is still running The highlighted bell icon indicates that the unit is shut down due to a detected fault 9 1 1 Current alarms All currently active alarms can be found in the Current Alarms me...

Страница 33: ...tion fault communication error 17 AUX1_COM_F 4601 Loss of communication with AUX1 Board As above Unit shuts down As above 18 COOLER_ FREEZE_F 10001 Water Exchanger Freeze Protection Automatic the firs...

Страница 34: ...ectrical issue 50 SIOB_LOW_VOLT_ CIRB_F 57002 Circuit B SIOB Low Voltage Failure As above Unit shuts down As above 51 WP_IN_F 12024 Water Exchanger Entering Fluid Transducer Failure Automatic if senso...

Страница 35: ...arm CPU fault Contact Carrier Service 24 Alarm Communication error trip Contact Carrier Service 26 Alarm Current detector fault Contact Carrier Service 27 Alarm Optional circuit board type error Conta...

Страница 36: ...No 10099 02 2016 Supersedes order No 10099 08 2015 Manufacturer Carrier SCS Montluel France Manufacturer reserves the right to change any product specifications without notice Printed in the European...

Отзывы: