Matched system

System Design

1. Intended for outdoor installation with free-air inlet and outlet. Outdoor fan external static pressure available is less than 0.01-in. wc.
2. Minimum outdoor operating air temperature in cooling mode is 55

°

F (12.8

°

C).

3. Minimum outdoor operating air temperature in heating mode is –30

°

F (–34.4

°

C).

4. Maximum outdoor operating air temperature in heating mode is 66

°

F (18.9

°

C).

5. Low-ambient operation accessory is not available.
6. Maximum outdoor operating air temperature is 125

°

F (51.7

°

C).

7. For reliable operation, unit should be level in all horizontal planes.
8. Maximum elevation of indoor coil above or below base of outdoor unit is: indoor coil above = 50 ft, indoor coil below = 100 ft. 
9. Interconnecting refrigerant tubing is limited to a maximum equivalent of 100 ft.

10. Not more than 3 ft of refrigerant tube should be buried in the ground. If necessary to bury tubes under a sidewalk, provide a minimum 6-in. vertical

rise to the valve connections at the unit.

11. Use only copper wire for electric connection at unit. Aluminum and clad aluminum are not acceptable for the type of connector provided.
12. Must be installed with factory-supplied hard shutoff, balanced port TXV (field installed) except for FK and FC Fan Coil units. (Bi-flow, hard 

shutoff, balanced port TXVs are factory installed.)

A97114

AIR CLEANER

HEAT PUMP

COMFORT VENTILATOR

HUMIDIFIER

COMFORT ZONE II
CONTROL CENTER

FAN COIL

Содержание SYNERGY 2000 38YDA

Страница 1: ...d field stripped lead wire connections facilitate ease of installation Range of Sizes Available in 3 nominal sizes 036 048 and 060 to meet the needs of residential applications Weather Armor II Cabine...

Страница 2: ...tandard Features An electronic control eliminates excessive wiring and features selectable second stage latching TimeGuard II short cycle protection a malfunction output signal to the indoor thermosta...

Страница 3: ...to the evaporator in response to the superheat of the refrigerant gas leaving the evaporator Kit includes valve adapter tubes and external equalizer tube Both hard shutoff and RBP valves are available...

Страница 4: ...greater than 30 C 86 F consult Table 310 16 of the NEC ANSI NFPA 70 The ampacity of nonmetallic sheathed cable NM trade name ROMEX shall be that of 60 C 140 F conductors per the NEC ANSI NFPA 70 Artic...

Страница 5: ...ambient in heating mode is 66 F 4 Series designation is the 13th position of the unit model number 5 Center of gravity NOTES AIR DISCHARGE 3 8 IN DIA LIQUID LINE CONN AIR DISCHARGE AIR DISCHARGE AIR I...

Страница 6: ...ING CAPACITY 1000 BTU HR OUTDOOR TEMPERATURE F 10 0 10 20 30 40 50 60 70 80 2 9 5 9 8 8 11 7 14 7 17 6 20 5 70 60 50 40 30 20 10 KW BASED ON INDOOR ENT AIR AT 70 F AND AT RATED CFM A 38YDA036 FK4CNB00...

Страница 7: ...80 76 70 CK3BA042 1200 800 37 000 21 000 14 40 34 000 20 200 7 80 76 70 COILS 58MVP080 14 VARIABLE SPEED FURNACE CC5A CD5A CD5BA036 1200 800 37 000 21 000 14 70 33 000 20 800 8 00 76 70 CC5A CD5A CD5B...

Страница 8: ...BA042 1070 810 37 000 21 000 14 80 34 000 20 200 8 00 76 70 CJ5A CK5A CK5BW036 1070 810 37 000 21 000 14 80 34 000 20 200 8 00 76 70 CK3BA036 1090 815 37 000 21 000 14 80 34 000 20 200 8 00 76 70 CK3B...

Страница 9: ...5 995 47 000 26 600 13 50 47 000 25 600 7 80 78 72 CD3 A B A048 1475 1000 47 000 26 600 13 50 47 000 25 600 7 80 78 72 CD3 A B A060 1470 995 47 000 26 600 13 50 47 000 25 600 7 80 78 72 CD3CA048 1435...

Страница 10: ...p Heating Performance tables Normally the high tempera ture COP is calculated at 47 F and the low temperature COP is calculated at 17 F The formula for calculating the COP is as follows COP THC total...

Страница 11: ...4 36 8 3 25 37 0 35 7 3 47 34 7 34 5 3 68 32 7 32 7 3 89 57 38 5 38 5 3 23 36 6 36 6 3 46 34 7 34 7 3 68 32 7 32 7 3 89 Multipliers for Determining the Performance With Other Indoor Sections Indoor Se...

Страница 12: ...5 5 27 6 4 01 63 40 2 29 7 3 27 37 7 28 7 3 49 35 2 27 6 3 70 32 7 26 5 3 89 62 39 4 36 8 3 25 37 0 35 7 3 47 34 7 34 5 3 68 32 7 32 7 3 89 57 38 5 38 5 3 23 36 6 36 6 3 46 34 7 34 7 3 68 32 7 32 7 3...

Страница 13: ...6 24 1 16 1 1 83 22 4 15 6 1 99 67 25 1 23 1 1 49 23 5 22 5 1 65 22 0 21 8 1 81 20 6 20 6 1 97 63 23 2 22 1 1 49 21 8 21 4 1 65 20 4 20 4 1 80 19 1 19 1 1 94 62 24 6 24 6 1 49 23 3 23 3 1 65 22 0 22 0...

Страница 14: ...4 21 3 21 3 1 80 20 1 20 1 1 95 1200 72 27 5 17 2 1 49 25 8 16 7 1 66 24 1 16 1 1 83 22 4 15 6 1 99 67 25 1 23 1 1 49 23 5 22 5 1 65 22 0 21 8 1 81 20 6 20 6 1 97 63 23 2 22 1 1 49 21 8 21 4 1 65 20 4...

Страница 15: ...28 9 5 68 50 8 27 9 6 04 67 54 5 39 6 4 80 51 8 38 5 5 13 49 1 37 5 5 47 46 3 36 4 5 80 63 50 6 38 4 4 68 48 1 37 3 5 00 45 6 36 2 5 32 42 9 35 1 5 61 62 49 9 47 9 4 66 47 6 46 7 4 98 45 2 45 2 5 30 4...

Страница 16: ...7 34 5 5 72 63 49 9 36 6 4 62 47 4 35 5 4 94 44 9 34 5 5 24 42 3 33 3 5 53 62 49 0 45 4 4 59 46 7 44 2 4 91 44 3 43 1 5 21 41 9 41 7 5 50 57 47 7 47 7 4 55 45 8 45 8 4 87 43 9 43 9 5 20 41 8 41 8 5 5...

Страница 17: ...8 2 23 27 3 27 3 2 43 25 8 25 8 2 63 57 30 4 30 4 2 02 28 9 28 9 2 23 27 3 27 3 2 43 25 8 25 8 2 63 1450 72 35 0 21 5 2 03 32 9 20 9 2 26 30 8 20 2 2 48 28 8 19 6 2 70 67 31 9 28 9 2 03 30 0 28 1 2 25...

Страница 18: ...28 1 2 21 26 6 26 6 2 41 25 1 25 1 2 60 1325 72 34 7 20 6 2 01 32 7 20 0 2 24 30 6 19 3 2 47 28 6 18 6 2 68 67 31 6 27 4 2 02 29 7 26 7 2 23 27 8 25 9 2 44 26 0 25 2 2 64 63 29 2 26 3 2 02 27 4 25 5 2...

Страница 19: ...0 51 8 51 8 5 75 49 3 49 3 6 09 46 7 46 7 6 41 2025 72 66 6 35 0 5 89 63 1 33 8 6 29 59 6 32 6 6 66 55 9 31 3 7 01 67 61 0 45 5 5 70 57 7 44 2 6 07 54 3 42 9 6 41 50 9 41 6 6 72 63 56 7 44 0 5 56 53 6...

Страница 20: ...10 57 35 9 35 9 2 12 35 9 35 9 2 47 36 0 36 0 2 82 35 7 35 7 3 18 1500 72 37 7 22 3 2 07 35 8 21 7 2 46 33 8 21 1 2 82 31 6 20 4 3 14 67 34 5 29 8 2 16 32 7 29 1 2 52 30 8 28 3 2 84 28 8 27 5 3 13 63...

Страница 21: ...r Indoor Sections Indoor Section Size Heating Indoor Section Size Heating Capacity Power Capacity Power F A B 4ANF 036 0 97 1 15 COILS 58MVP080 14 VARIABLE SPEED FURNACE F A B 4AN F B 042 0 97 1 12 CC...

Страница 22: ...900 13 5 12 4 2 12 17 5 16 1 2 34 21 7 19 8 2 58 26 2 23 2 2 83 27 7 24 2 2 91 990 13 7 12 6 2 13 17 7 16 3 2 35 22 0 20 0 2 59 26 5 23 6 2 82 28 0 24 6 2 90 1100 13 9 12 8 2 14 18 0 16 5 2 36 22 3 2...

Страница 23: ...ILS 58MVP080 14 VARIABLE SPEED FURNACE F A B 4AN F B 042 1 02 1 28 CC5A CD5A CD5BA 036 0 96 1 08 FC4BN F B 042 1 02 1 28 042 0 96 1 08 FC4BNF 036 1 02 1 33 CC5A CD5A CD5BW 042 0 96 1 09 FK4CNB 006 1 0...

Страница 24: ...3 0 1 39 16 9 15 4 1 45 20 1 20 1 1 52 23 7 23 7 1 59 950 15 0 13 2 1 39 17 2 15 6 1 43 20 4 20 4 1 50 24 1 24 1 1 56 1075 15 2 13 3 1 38 17 4 15 8 1 43 20 7 20 7 1 48 24 4 24 4 1 54 Multipliers for D...

Страница 25: ...9 8 3 64 37 5 32 3 3 84 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Heating Indoor Section Size Heating Capacity Power Capacity Power F A B 4AN F B 048 1...

Страница 26: ...16 2 14 9 2 61 22 1 20 3 2 93 27 8 25 3 3 25 33 6 29 8 3 56 37 6 32 4 3 76 1470 16 5 15 2 2 65 22 4 20 6 2 96 28 2 25 7 3 27 34 0 30 2 3 57 38 0 32 8 3 76 1625 16 8 15 5 2 68 22 8 21 0 2 99 28 6 26 0...

Страница 27: ...Determining the Performance With Other Indoor Sections Indoor Section Size Heating Indoor Section Size Heating Capacity Power Capacity Power F A B 4AN F B 048 1 00 1 26 CJ5A CK5A CK5BX 060 0 98 1 02 0...

Страница 28: ...31 8 2 03 1200 21 5 18 5 1 85 23 1 21 1 1 88 27 3 27 3 1 95 32 1 32 1 2 01 1325 21 7 18 7 1 85 23 4 21 2 1 88 27 6 27 6 1 94 32 4 32 4 1 99 1450 21 9 18 9 1 86 23 5 21 4 1 88 27 8 27 8 1 93 32 7 32 7...

Страница 29: ...4 7 3 57 32 8 29 9 3 94 39 3 34 9 4 31 49 2 49 2 4 87 1650 21 4 19 7 3 28 27 2 25 0 3 62 33 2 30 3 3 97 39 8 35 3 4 34 49 8 49 8 4 89 1835 21 8 20 0 3 34 27 6 25 4 3 67 33 7 30 7 4 02 40 3 35 8 4 38 5...

Страница 30: ...115 27 7 27 7 2 27 30 9 30 9 2 32 35 7 35 7 2 37 1240 28 0 28 0 2 25 31 2 31 2 2 29 36 1 36 1 2 33 1365 28 2 28 2 2 24 31 5 31 5 2 28 36 5 36 5 2 30 1500 28 5 28 5 2 24 31 7 31 7 2 26 36 8 36 8 2 28 1...

Страница 31: ...f indoor coil above or below base of outdoor unit is indoor coil above 50 ft indoor coil below 100 ft 9 Interconnecting refrigerant tubing is limited to a maximum equivalent of 100 ft 10 Not more than...

Страница 32: ...wledge of the equipment discussed in this manual including Unit Familiarization Maintenance Installation Overview Operating Sequence A large selection of product theory and skills programs is availabl...

Отзывы: