60
Boldface
indicates field-supplied drive is required.
NOTES:
1. For more information, see General Fan Performance Notes on
2. Recommend using field-supplied fan pulley (part number
KR11AG006) and belt (part number KR30AE039) with field-sup-
plied drive.
3. Recommend using field-supplied motor pulley (part number
KR11HY161) and belt (part number KR30AE035) with field-sup-
plied drive.
Table D — 50KC**04 3 Ton Vertical Supply (1 Phase)
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
0.2
0.4
0.6
0.8
1.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
900
594
0.15
740
0.25
867
0.37
981
0.52
1084
0.68
975
618
0.17
758
0.28
881
0.40
991
0.55
1092
0.71
1050
642
0.19
777
0.30
896
0.43
1003
0.58
1102
0.75
1125
668
0.22
797
0.34
912
0.47
1017
0.62
1113
0.79
1200
695
0.25
818
0.37
930
0.51
1032
0.66
1126
0.83
1275
722
0.29
841
0.41
949
0.55
1048
0.71
1140
0.88
1350
750
0.33
864
0.46
968
0.60
1065
0.76
1155
0.93
1425
778
0.37
888
0.50
989
0.65
1083
0.81
1171
0.99
1500
807
0.42
913
0.56
1011
0.71
1103
0.87
1188
1.05
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.2
1.4
1.6
1.8
2.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
900
1180
0.86
1269
1.05
1354
1.25
1434
1.47
—
—
975
1186
0.89
1275
1.08
1358
1.29
—
—
—
—
1050
1194
0.92
1281
1.12
1363
1.32
—
—
—
—
1125
1204
0.97
1289
1.16
1370
1.37
—
—
—
—
1200
1215
1.01
1298
1.21
1378
1.42
—
—
—
—
1275
1227
1.06
1309
1.26
1387
1.47
—
—
—
—
1350
1240
1.12
1321
1.32
—
—
—
—
—
—
1425
1254
1.18
1333
1.38
—
—
—
—
—
—
1500
1270
1.24
1347
1.45
—
—
—
—
—
—
Medium static 770-1175 RPM, 1.2 BHP max
High static 1035-1466 RPM, 1.5 BHP max
Содержание Puron R-410A
Страница 29: ...29 Fig 44 RTU Open Overlay for Economizer Wiring ...
Страница 30: ...30 Fig 45 VFD Overlay for W2770 Controller Wiring ...
Страница 50: ...50 Fig 63 50KC Typical Unit Wiring Diagram Power 06A 208 230 3 60 ...
Страница 51: ...51 Fig 64 50KC Unit Wiring Diagram Control A06 ...
Страница 76: ...76 Fig B Unit Wiring Diagram Controls for Sizes A04 A06 208 230 1 60 208 230 3 60 460 3 60 575 3 60 ...
Страница 77: ...77 Fig C Unit Wiring Diagram Power for Sizes A04 and A06 208 230 1 60 ...
Страница 78: ...78 Fig D Unit Wiring Diagram Power for Size A05 208 230 1 60 ...
Страница 79: ...79 Fig E Unit Wiring Diagram Power for Sizes A04 A06 208 230 3 60 460 3 60 575 3 60 ...
Страница 80: ...80 APPENDIX F MOTORMASTER SENSOR LOCATIONS Fig F 50KC A04 Outdoor Circuiting Fig G 50KC A05 Outdoor Circuiting ...
Страница 81: ...81 Fig H 50KC A06 Outdoor Circuiting ...