Fig. 49 — Supply Air Sensor Location
The temperature sensor looks like an eyelet terminal with wires
running to it. The sensor is located in the “crimp end” and is
sealed from moisture.
Outdoor Air Lockout Sensor
The EconoMi$er IV system is equipped with an ambient tem-
perature lockout switch located in the outdoor airstream which
is used to lock out the compressors below a 42°F (6°C) ambi-
ent temperature. (See Fig. 42.)
ECONOMI$ER IV CONTROL MODES
IMPORTANT:
The optional EconoMi$er2 system does not
include a controller. The EconoMi$er2 system is operated by a
4 to 20 mA signal from an existing field-supplied controller.
See Fig. 43 for wiring information.
Determine the EconoMi$er IV control mode before set up of
the control. Some modes of operation may require different
sensors. The EconoMi$er IV system is supplied from the facto-
ry with a supply-air temperature sensor and an outdoor-air tem-
perature sensor. This allows for operation of the EconoMi$er
IV system with outdoor air dry bulb changeover control. Addi-
tional accessories can be added to allow for different types of
changeover control and operation of the EconoMi$er IV sys-
tem and unit.
Outdoor Dry Bulb Changeover
The standard controller is shipped from the factory configured
for outdoor dry bulb changeover control. The outdoor air and
supply air temperature sensors are included as standard. For
this control mode, the outdoor temperature is compared to an
adjustable set point selected on the control. If the outdoor-air
temperature is above the set point, the EconoMi$er IV system
will adjust the outside air dampers to minimum position. If the
outdoor-air temperature is below the set point, the position of
the outside air dampers will be controlled to provided free
cooling using outdoor air. When in this mode, the LED next to
the free cooling set point potentiometer will be on. The
changeover temperature set point is controlled by the free cool-
ing set point potentiometer located on the control. (See
Fig. 50.) The scale on the potentiometer is A, B, C, and D. See
Fig. 51 for the corresponding temperature changeover values.
Fig. 50 — EconoMi$er IV Controller Potentiometer
and LED Locations
Fig. 51 — Outside Air Temperature Changeover
Set Points
Table 6 — Thermistor Resistance vs Temperature
Values for Space Temperature Sensor, Supply Air
Temperature Sensor, and Outdoor Air
Temperature Sensor
TEMP (°C)
TEMP (°F)
RESISTANCE
(ohms)
-40
-40
335,651
-35
-31
242,195
-30
-22
176,683
-25
-13
130,243
-20
-4
96,974
-15
5
72,895
-10
14
55,298
-5
23
42,315
0
32
32,651
5
41
25,395
10
50
19,903
15
59
15,714
20
68
12,494
25
77
10,000
30
86
8,056
35
95
6,530
40
104
5,325
45
113
4,367
50
122
3,601
55
131
2,985
60
140
2,487
65
149
2,082
70
158
1,752
SUPPLY
AIR TEMPERATURE
SENSOR MOUNTING
LOCATION
SUPPLY AIR
TEMPERATURE
SENSOR
(SEALED
INSIDE CRIMP
END)
LED
LED
LED
LED ON
LED ON
LED ON
LED ON
LED OFF
19
18
LED OFF
LED OFF
LED OFF
17
16
15
14
1
3
12
11
10
9
40
45
50
55
60
65
70
75
80
85
90
95
100
DEGREE
S
FAHRENHEIT
mA
D
C
B
A
Содержание Puron R-410A
Страница 29: ...29 Fig 44 RTU Open Overlay for Economizer Wiring ...
Страница 30: ...30 Fig 45 VFD Overlay for W2770 Controller Wiring ...
Страница 50: ...50 Fig 63 50KC Typical Unit Wiring Diagram Power 06A 208 230 3 60 ...
Страница 51: ...51 Fig 64 50KC Unit Wiring Diagram Control A06 ...
Страница 76: ...76 Fig B Unit Wiring Diagram Controls for Sizes A04 A06 208 230 1 60 208 230 3 60 460 3 60 575 3 60 ...
Страница 77: ...77 Fig C Unit Wiring Diagram Power for Sizes A04 and A06 208 230 1 60 ...
Страница 78: ...78 Fig D Unit Wiring Diagram Power for Size A05 208 230 1 60 ...
Страница 79: ...79 Fig E Unit Wiring Diagram Power for Sizes A04 A06 208 230 3 60 460 3 60 575 3 60 ...
Страница 80: ...80 APPENDIX F MOTORMASTER SENSOR LOCATIONS Fig F 50KC A04 Outdoor Circuiting Fig G 50KC A05 Outdoor Circuiting ...
Страница 81: ...81 Fig H 50KC A06 Outdoor Circuiting ...