59
APPENDIX C — FAN PERFORMANCE
General Fan Performance Notes
1. Interpolation is permissible. Do not extrapolate.
2. External static pressure is the static pressure difference
between the return duct and the supply duct plus the static
pressure caused by any FIOPs or accessories.
3. Tabular data accounts for pressure loss due to clean filters,
unit casing, and wet coils. Factory options and accessories
may add static pressure losses.
4. The Fan Performance tables offer motor/drive recommen-
dations. In cases when two motor/drive combinations
would work, Carrier recommended the lower horsepower
option.
5. For information on the electrical properties of Carrier’s
motors, please see the Electrical information section of
this book.
Boldface
indicates field-supplied drive is required.
NOTES:
1. For more information, see General Fan Performance Notes above.
2. Recommend using field-supplied fan pulley (part number
KR11AG006) and belt (part number KR30AE039) with field-sup-
plied drive.
3. Recommend using field-supplied motor pulley (part number
KR11HY161) and belt (part number KR30AE035) with field-sup-
plied drive.
Table C — 50KC**04 3 Ton Horizontal Supply (1 Phase)
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
0.2
0.4
0.6
0.8
1.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
900
574
0.13
707
0.23
817
0.34
913
0.47
999
0.61
975
597
0.15
727
0.25
835
0.37
929
0.50
1015
0.64
1050
621
0.18
747
0.28
853
0.40
946
0.53
1030
0.68
1125
646
0.20
768
0.31
872
0.43
964
0.57
1047
0.72
1200
671
0.23
790
0.34
892
0.47
982
0.61
1064
0.76
1275
696
0.26
812
0.38
912
0.51
1001
0.65
1082
0.81
1350
723
0.30
835
0.42
933
0.55
1020
0.70
1100
0.86
1425
749
0.34
859
0.46
955
0.60
1040
0.75
1119
0.91
1500
776
0.38
883
0.51
977
0.65
1061
0.80
1138
0.97
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.2
1.4
1.6
1.8
2.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
900
1078
0.77
1151
0.93
1220
1.11
1284
1.30
1346
1.49
975
1093
0.80
1165
0.97
1233
1.15
1297
1.33
—
—
1050
1108
0.84
1180
1.01
1247
1.19
1311
1.38
—
—
1125
1123
0.88
1195
1.05
1261
1.23
1325
1.42
—
—
1200
1140
0.92
1210
1.10
1276
1.28
1339
1.47
—
—
1275
1157
0.97
1226
1.15
1292
1.33
—
—
—
—
1350
1174
1.02
1243
1.20
1308
1.39
—
—
—
—
1425
1192
1.08
1260
1.26
1325
1.45
—
—
—
—
1500
1210
1.14
1278
1.33
—
—
—
—
—
—
Medium static 770-1175 RPM, 1.2 BHP max
High static 1035-1466 RPM, 1.5 BHP max
Содержание Puron R-410A
Страница 29: ...29 Fig 44 RTU Open Overlay for Economizer Wiring ...
Страница 30: ...30 Fig 45 VFD Overlay for W2770 Controller Wiring ...
Страница 50: ...50 Fig 63 50KC Typical Unit Wiring Diagram Power 06A 208 230 3 60 ...
Страница 51: ...51 Fig 64 50KC Unit Wiring Diagram Control A06 ...
Страница 76: ...76 Fig B Unit Wiring Diagram Controls for Sizes A04 A06 208 230 1 60 208 230 3 60 460 3 60 575 3 60 ...
Страница 77: ...77 Fig C Unit Wiring Diagram Power for Sizes A04 and A06 208 230 1 60 ...
Страница 78: ...78 Fig D Unit Wiring Diagram Power for Size A05 208 230 1 60 ...
Страница 79: ...79 Fig E Unit Wiring Diagram Power for Sizes A04 A06 208 230 3 60 460 3 60 575 3 60 ...
Страница 80: ...80 APPENDIX F MOTORMASTER SENSOR LOCATIONS Fig F 50KC A04 Outdoor Circuiting Fig G 50KC A05 Outdoor Circuiting ...
Страница 81: ...81 Fig H 50KC A06 Outdoor Circuiting ...