Table 12 – Troubleshooting Chart
SYMPTOM
CAUSE
REMEDY
Compressor and outdoor fan will not start
Power failure
Call power company
Fuse blown or circuit breaker tripped
Replace fuse or reset circuit breaker
Defective contactor, transformer or high--pressure,
loss--of--charge or low--pressure switch
Replace component
Insufficient line voltage
Determine cause and correct
Incorrect or faulty wiring
Check wiring diagram and rewire correctly
Thermostat setting too high
Lower thermostat setting below room temperat-
ure
Compressor will not start but condenser fan
runs
Faulty wiring or loose connections in compressor cir-
cuit
Check wiring and repair or replace
Compressor motor burned out, seized, or internal over-
load open
Determine cause
Replace compressor
Defective run/start capacitor, overload, start relay
Determine cause and replace
Three--phase scroll compressor (size 30--60
unit) has a low pressure differential
Scroll compressor is rotating in the wrong direction
Correct the direction of rotation by reversing the
3--phase power leads to the unit
Compressor cycles (other than normally
satisfying thermostat)
Refrigerant overcharge or undercharge
Recover refrigerant, evacuate system, and re-
charge to capacities shown on rating plate
Defective compressor
Replace and determine cause
Insufficient line voltage
Determine cause and correct
Blocked condenser
Determine cause and correct
Defective run/start capacitor, overload or start relay
Determine cause and replace
Defective thermostat
Replace thermostat
Faulty condenser--fan motor or capacitor
Replace
Restriction in refrigerant system
Locate restriction and remove
Compressor operates continuously
Dirty air filter
Replace filter
Unit undersized for load
Decrease load or increase unit size
Thermostat set too low
Reset thermostat
Low refrigerant charge
Locate leak, repair, and recharge
Mechanical damage in compressor
Replace compressor
Air in system
Recover refrigerant, evacuate system, and re-
charge
Condenser coil dirty or restricted
Clean coil or remove restriction
Excessive head pressure
Dirty air filter
Replace filter
Dirty indoor or outdoor coil
Clean coil
Refrigerant overcharged
Recover excess refrigerant
Air in system
Recover refrigerant, evacuate system, and re-
charge
Head pressure too low
Low refrigerant charge
Check for leaks, repair and recharge
Compressor IPR leaking
Replace compressor
Restriction in liquid tube
Remove restriction
Excessive suction pressure
High heat load
Check for source and eliminate
Compressor IPR leaking
Replace compressor
Refrigerant overcharged
Recover excess refrigerant
Suction pressure too low
Dirty air filter
Replace filter
Low refrigerant charge
Check for leaks, repair and recharge
Metering device or low side restricted
Remove source of restriction
Insufficient evaporator airflow
Increase air quantity
Check filter–replace if necessary
Temperature too low in conditioned area
Reset thermostat
Outdoor ambient below 55
F (12.7
C)
Install low--ambient kit
Filter drier restricted
Replace filter
50V
R
Содержание Performance 50VR-A
Страница 3: ...3 A180108 Fig 2 50VR C24 30 Unit Dimensions 50VR...
Страница 4: ...4 A180107 Fig 3 50VR A36 60 Unit Dimensions 50VR...
Страница 23: ...23 A13144 Fig 15 Connection Wiring Diagram without Advanced Dehumidification AD FIOP 208 230 1 60 50VR...
Страница 24: ...24 A13145 Fig 15 Cont Ladder Wiring Diagram without Advanced Dehumidification AD FIOP 208 230 1 60 50VR...
Страница 27: ...27 A13146 Fig 17 Connection Wiring Diagram 208 230 3 60 50VR...
Страница 28: ...28 A13147 Fig 17 Cont Ladder Wiring Diagram 208 230 3 60 50VR...
Страница 29: ...29 A13148 Fig 18 Connection Wiring Diagram 460 3 60 50VR...
Страница 30: ...30 A13149 Fig 18 Cont Ladder Wiring Diagram 460 3 60 50VR...
Страница 31: ...31 A170012 Fig 19 Cooling Charging Chart 50VR...