Fig. 11 -- Interface Fan Board (IFB)
Single Speed Cooling With Higher Electric Heat Speed
This unit can also be configured to operate with single speed
cooling and a higher speed for an accessory electric heater.
1. Using Fig. 11, move the two pin DEHUM jumper from the
“STD” position to the “DEHUM” position.
2. See Table 2 for minimum airflow for electric heat operation.
Add electric heater and filter pressure drop to duct system
static pressure to determine total external static pressure.
3. Select speed tap from Table 4 that will achieve required
airflow from Table 2.
4. Remove the vinyl cap off of the desired speed tap wire
(Refer to Table 3 for color coding).
5. Connect the desired speed tap wire to the “HIGH” terminal
on the interface fan board (IFB).
UNIT OPERATION HAZARD
Failure to follow this caution may result in unit
component damage or improper operation.
To use this mode, a speed connection must be made
on the “HIGH” terminal that meets or exceeds the
minimum airflow found in Table 2.
!
CAUTION
Table 3 – Color Coding for Indoor Fan Motor Leads
Black = High Speed
Orange = Med--High Speed
Red = Med Speed
Pink = Med--Low Speed
Blue = Low Speed
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Disconnect electrical power to the unit and install
lockout tag before changing blower speed.
!
WARNING
Continuous Fan Operation
When the DEHUM feature is not used, the continuous fan speed
will be the same as cooling fan speed. When the DEHUM feature
is used, the continuous fan will operate on IFB “LOW” speed
when the DH control lead is not energized, or IFB “HIGH” speed
when the DH lead is energized. (See Figure 11).
COOLING SEQUENCE OF OPERATION
With the room thermostat SYSTEM switch in the COOL position
and the FAN switch in the AUTO position, the cooling sequence of
operation is as follows:
When the room temperature rises to a point that is slightly above
the cooling control setting of the thermostat, the thermostat
completes the circuit between thermostat terminal R to terminals
Y and G. These completed circuits through the thermostat
connect contactor coil (C) (through unit wire Y) and time delay
relay (TDR) (through unit wire G) across the 24--V secondary of
transformer (TRAN).
The normally open contacts of energized contactor (C) close and
complete the circuit through compressor motor (COMP) to
condenser (outdoor) fan motor (OFM). Both motors start instantly.
A set of normally open contacts on the interface fan board (IFB)
are closed which energizes a circuit to the indoor fan motor (IFB).
NOTE
: Once the compressor has started and then has stopped,
it should not be started again until 5 minutes have elapsed.
The cooling cycle remains on until the room temperature drops to
a point that is slightly below the cooling control setting of the room
thermostat. At this point, the thermostat breaks the circuit between
thermostat terminal R to terminals Y and G. These open circuits
deenergize contactor coil C and IFB. The condenser and
compressor motors stop. After a 90--second delay, the blower
motor stops. The unit is in a standby condition, waiting for the next
call for cooling from the room thermostat.