Introduction
MPC Open XP
MPC Open XPIO48/816
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
3
MPC Open XP specifications
Driver
drv_mpcxpopen_vanilla
Maximum number of control
programs*
999
Maximum number of
BACnet objects*
12000
Maximum number of third-
party integration points
using Snap*†
200
* Depends on available memory
† BACnet third-party integration points are not counted.
Power
24 Vac ±10%, 50–60 Hz
50 VA power consumption
26 Vdc (25 V min, 30 V max), 23 W
Single Class 2 source only, 100 VA or less
BACnet port
For communication with the controller network using BACnet ARC156 (156
kbps) or BACnet MS/TP (9600 bps – 76.8 kbps)
Rnet port
•
Supports up to 15 wireless and/or ZS sensors, and one Equipment Touch or
TruVu™ ET Display
•
Supplies 12 Vdc/210 mA power to the Rnet at an ambient temperature of
77°F (25°C) with a 24 Vac nominal power source.
NOTE Ambient temperature and power source fluctuations may reduce the
power supplied by the Rnet port.
NOTE
If the total power required by the sensors on the Rnet exceeds the power
supplied by the Rnet port, use an external power source. The Wireless Adapter,
Equipment Touch, or TruVu™ ET Display must be powered by an external power
source. See the specifications in each device's Installation and Start-up Guide to
determine the power required.
Local Access port
For system start-up and troubleshooting using Field Assistant
Xnet Remote Expansion port For communication with expanders MPC Open XPIO48 and/or MPC Open
XPIO816. Up to 3 expanders with a maximum of 92 points between the MPC
Open XP and the expanders.
Inputs
12 inputs, configurable for 0–5 Vdc, 0–10 Vdc, 0–20 mA, RTD, thermistor, or dry
contact
Input resolution
14 bit A/D
Input pulse frequency
40 pulses per second. Minimum pulse width (on or off time) required for each
pulse is 12.5 msec.
Outputs
8 outputs for 24 Vdc relay driver, 0–10 Vdc, or 0-20 mA. Does not support dry
contact output channels.
Output resolution
12 bit D/A
Memory
16 MB non-volatile battery-backed RAM (with 12 MB available for use), 8 MB
Flash memory, 32-bit memory bus
Real-time clock
Battery-backed real-time clock keeps track of time in event of power failure