Installing the MPC Open XP
MPC Open XP
MPC Open XPIO48/816
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
11
To mount an expander
WARNING
When you handle the expander:
• Do not contaminate the printed circuit board with fingerprints, moisture, or any foreign material.
• Do not touch components or leads.
• Handle the board by its edges.
• Isolate from high voltage or electrostatic discharge.
• Ensure that you are properly grounded.
Wiring restrictions for connecting the expander to the MPC Open XP
○
Maximum length: 100 feet (30 meters)
○
22 or 24 AWG, low-capacitance, twisted, stranded, shielded copper wire
You can mount the expander in one of the following locations:
•
On top of a MPC Open XP, using the two allen cap screws provided. Connect
Gnd
to
Gnd
,
Xnet-
to
Xnet-
,
Xnet+
to
Xnet+
.