Installing the MPC Open XP
MPC Open XP
MPC Open XPIO48/816
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
18
4
Set each input's
Universal Input Mode Select
jumper to indicate the type of input.
5
Connect digital and analog output wiring to the
UO
screw terminals on the MPC Open XP and to the controlled
device. Connect the ground wire to the UO's
Gnd
terminal.
WARNING!
Binary outputs are powered, 24 Vdc channels. Dry contact binary outputs are not
supported in the MPC Open XP product line. Do NOT apply 24 Vac to these universal outputs.
6
Set each output's jumper to the type of device wired to the output.
7
For each digital output, turn the output's potentiometer clockwise until it stops (maximum output).
8
Turn
on