IM-KSAIC03-03 Specifications subject to change without notice.
15
APPENDIX 1 - COMPATIBILITY AND FAN SPEED WIRING
The 24V Interface Kit is compatible with most single stage conventional 24V thermostats matched with the conventional fan coils listed in
Tables 17, 18, and 19. Before installation, check the compatibility of your outdoor and indoor fan coil.
Professional installation is
recommended.
Select Proper Blower Speed For the Fan Coil
Before operating the unit, ensure that the proper blower speed has been selected. Fan speeds are selected manually. Refer to the indoor unit’s
installation manual for instructions on how to change the fan speed and select the taps (see Tables 17, 18, and 19) for the proper matches.
24V Interface Fan Speed Wiring (See “WIRING” on page 11 for Wiring Connections)
G3 is the High Fan Speed terminal and should be connected to the high tap speed inputs at the fan coil.
G2 is the Medium Fan Speed terminal and should be connected to the medium tap speed inputs at the fan coil.
Tap G1 is the Low Fan Speed terminal and should be connected to the low tap speed inputs at the fan coil. The 24V interface may be connected
to a low Tap Speed, based on the indoor unit’s installation instructions.
Table 17 — Compatibility with FMA4 Fan Coils
Table 18 — Compatibility with FMC4 Cased Horizontal Fan Coils
Table 19 — Compatibility with FMU4 Uncased Horizontal Fan Coils
Table 20 — Compatibility with FV4 Fan Coils
Indoor
Volt-
Ph@60Hz
Kit Number
Nominal System
Size MBTUH
Indoor Model
Number
Outdoor Model
Number
Recommended Maximum
Indoor Fan
Speed Tap Number
FMA4
Vertical
Fan Coil
208/230-1
KSAIC0301230
12
FMA4X1800AL
38MAQB12R--3
Tap 1
18
FMA4X1800AL
38MAQB18R--3
Tap 2
24
FMA4X2400AL
38MAQB24R--3
Tap 5
30
FMA4X3000AL
38MAQB30R--3
Tap 2
36
FMA4X3000AL
38MAQB36R--3
Tap 4
Indoor
Volt-
Ph@60Hz
Kit Number
Nominal System Size
MBTUH
Indoor Model
Number
Outdoor Model
Number
Recommended Maximum
Indoor Fan
Speed Tap Number
FMC4
Cased
Horizontal
Fan Coil
208/230-1
KSAIC0301230
12
FMC4Z1800AL1
38MAQB12R--3
Low (Black)
18
FMC4Z1800AL1
38MAQB18R--3
Medium low (Blue)
24
FMC4Z2400AL1
38MAQB24R--3
Medium low (Blue)
30
FMC4Z3000AL1
38MAQB30R--3
Medium high (White)
36
FMC4Z3600AL1
38MAQB36R--3
Medium high (White)
Indoor
Volt-
Ph@60Hz
Kit Number
Nominal System Size
MBTUH
Indoor Model
Number
Outdoor Model
Number
Recommended Maximum
Indoor Fan
Speed Tap Number
FMU4
Uncased
Horizontal
Fan Coil
208/230-1
KSAIC0301230
12
FMU4Z1800AL1
38MAQB12R--3
Low (Black)
18
FMU4Z1800AL1
38MAQB18R--3
Medium low (Blue)
24
FMU4Z2400AL1
38MAQB24R--3
Medium low (Blue)
30
FMU4Z3000AL1
38MAQB30R--3
Medium high (White)
36
FMU4Z3600AL1
38MAQB36R--3
Medium high (White)
Indoor
Volt-
Ph@60Hz
Kit Number
Nominal System
Size MBTUH
Indoor Model
Number
Outdoor Model
Number
Recommended Fan Speed
Wiring and Configuration
FV4
Fan Coil
208/230-1
KSAIC0301230
12
FV4CNF002L00
38MAQB12R--3
Connect G1 on the 24V
interface to G on the fan coil.
Under the configuration taps
for AC/HP CFM ADJUST, the
recommendation is to
select
NOM.
Refer to “TXV REPLACEMENT
page 16 for setup.
18
FV4CNF002L00
38MAQB18R--3
24
FV4CNF002L00
38MAQB24R--3
30
FV4CN(B,F)003L
38MAQB30R--3
36
FV4CN(B,F)003L
38MAQB36R--3