NOTE:
Use propane-gas-resistant pipe dope to prevent gas leaks. DO NOT use Teflon tape.
WARNING: Gas valve knob or electric switch MUST be facing forward or tilted upward. Failure to follow this warning
could result in property damage or death.
4. If unit has a diverter plate installed above combustion air intake box, remove diverter plate as follows:
a. Remove front 2 screws on combustion air intake box. (See Fig. 13.)
b. Remove combustion air intake box and set aside. (See Fig. 13.)
c. Remove diverter plate. (See Fig. 14.)
d. Reinstall combustion air intake box and replace 2 screws. (See Fig. 13.)
5. Reinstall manifold, orifice, and gas valve assembly in burner box. Ensure manifold seal grommet is installed properly and burners fit over
orifices. (See Fig. 15 for ignitor position.)
6. Reconnect wires to gas valve. See wiring label on furnace to ensure proper location of wires.
7. If a LGPS was removed with propane gas valve, rewire unit low-pressure switch as follows:
a. Disconnect and discard orange wire and splice connector attached to orange wire from PL2-2 on control board.
b. Disconnect and discard orange wire attached to NO terminal of low-pressure switch LPS.
c. Connect orange wire from PL2-2 on control board to NO terminal of low-pressure switch LPS.
d. Refer to wiring label on furnace to ensure proper location of wires.
8. Reinstall gas supply pipe to gas valve using backup wrench on gas valve to prevent rotation and improper orientation.
NOTE:
Use propane-gas-resistant pipe dope to prevent gas leaks. DO NOT use Teflon tape.
9. DO NOT reinstall burner box pressure tube to gas valve regulator fitting or burner enclosure front at this time.
PROCEDURE 4—CHECK INLET GAS PRESSURE
NOTE:
This kit is to be used only when inlet gas pressure is between 4.5- and 13.6-in. wc.
1. Be sure main gas and electrical supplies to furnace are off.
2. Remove 1/8-in. pipe plug from inlet pressure tap on gas valve.
3. Attach manometer to inlet pressure tap on gas valve.
CAUTION: DO NOT operate furnace more than 1 minute to check inlet gas pressure as conversion is not complete at
this time.
4. Turn on furnace power supply.
Fig. 12—Air Shutter in Natural Gas Usage (NAT) Position
(060120 and 120-20 Size Units Only)
A96271
NATURAL
GAS
POSITION
AIR
SHUTTER
—22—
→