PROCEDURE 6—LABEL APPLICATION
NOTE:
See Fig. 1 or 2 for label location.
1. Fill in Conversion Responsibility Label (321201-104) and apply inside furnace as shown. Date, name, and address of organization making
this conversion are required.
2. Attach Furnace Conversion Rating Plate (323870-101) near existing furnace rating plates.
3. Check for correct normal operating sequence of ignition system as described in the furnace Installation Instructions.
4. Replace furnace control component access door.