S

Heat Pump:

Disabled, Low Stage or Turn off

d

Default = Disabled

6.3.11.

Hydronic Airflow

NOTE

: The daily duct assessment will occur even if Hydronic Airflow is set to

Off. This is done to ensure that the system will continue to provide proper airflow
for all installed equipment, since duct system changes may occur at any time, such
as opened or closed registers.
This option allows the installer to select the airflow for the fan coil when paired
with a hydronic coil. After the selections are made, touch

SAVE

.

A12194

S

Airflow:

Selectable between Off to Max in 50 CFM increments

d

Default = Off, 500 CFM, Max = (odu_size in KBTU * 400/12)

NOTE

: Selected airflow used during hydronic heating is a fixed value, it does not

vary.

S

Blower On Delay:

Selectable from 0 to 240 seconds

d

Default = 30 seconds

S

Blower Off Delay:

Selectable from 0 to 240 seconds

d

Default = 0 seconds

Содержание Infinity SYSTXCCITC-01SI

Страница 1: ...em operations with specific pieces of equipment The features and functions outlined in the Installation Instructions reflect Version 1 software See the Infinity System Control product page on the HVAC...

Страница 2: ...Zone 4 3 1 3 Enable Time Synchronization 4 3 2 Set Dealer Information 5 4 Installation 7 4 1 Overview 7 4 2 Check Equipment 7 4 3 Location 8 4 3 1 Wall Control 8 4 3 2 Remote Room Sensors 9 4 3 2 1 R...

Страница 3: ...Searching for Outdoor Unit 18 5 3 Indoor Evaporator Selection 19 5 4 Electric Heater Selection 19 5 4 1 Hydronic Heat Application 20 5 5 Searching SAM Module If Applicable 20 5 6 Searching for Zones...

Страница 4: ...t Cool Deadband 31 6 3 1 3 Offsets 32 6 3 1 4 Reset factory defaults 33 6 3 1 5 Scheduling Enable 33 6 3 1 6 Smart Recovery Enable 34 6 3 1 7 Room Occupancy Setup 35 6 3 2 Fan Coil 35 6 3 2 1 Airflow...

Страница 5: ...3 6 3 3 5 Furnace Off Delay 43 6 3 3 6 Altitude 43 6 3 3 7 Furnace Dehumidifier Drain 44 6 3 3 8 Furnace G Terminal 44 6 3 3 9 Furnace G Terminal Alert 45 6 3 3 10 Furnace G Terminal Alert Label 45 6...

Страница 6: ...50 6 3 5 Heat Source Lockout 50 6 3 6 Stages Latch for 18VS 51 6 3 7 Geo HP 52 6 3 7 1 Freeze Limits 52 6 3 7 2 Lockout Count 53 6 3 7 3 Brownout Override 53 6 3 7 4 Geothermal HP Energy Tracking 54 6...

Страница 7: ...Ultraviolet Lights 58 6 3 9 4 Ventilator 58 6 3 10 Utility Curtailment 59 6 3 11 Hydronic Airflow 60 6 4 Check out 61 6 4 1 Electric Heat 61 6 4 2 Furnace 61 6 4 3 Hydronic 62 6 4 4 Air Conditioning...

Страница 8: ...ensor Type 66 6 5 Service Information 67 6 5 1 Advanced Diagnostics 67 6 5 2 Fan Coil Status 67 6 5 3 Furnace Status 68 6 5 4 AC Status 68 6 5 5 Heat Pump Status 69 6 5 6 Geo HP Status 69 6 5 7 Zoning...

Страница 9: ...XV Position 77 6 7 Dealer Logo 77 6 8 Utility Event Setup 79 7 Wireless Setup 80 7 1 Setup and Status Information Homeowner s Router 80 7 2 Setup and Status Information Dealer provided Router 84 8 Wir...

Страница 10: ...warnings and cautions included in literature and attached to the unit Consult local building codes and the current edition of the National Electrical Code NEC NFPA 70 In Canada refer to the current e...

Страница 11: ...dehumidification and air quality control Either an Infinity System communicating or a standard single stage 24VAC controlled outdoor unit may be used When using conventional single stage outdoor units...

Страница 12: ...Wi Fi enabled units From the main screen touch MENU on the bottom of the control The TIME DATE icon will bring up the time and date menu A14215 3 1 1 Manually Adjust Time and Date d To set the HOUR M...

Страница 13: ...for the location Time zones for both US and Canada are included A14217 3 1 3 Enable Time Synchronization After setting up the time zone the time synchronization can then be done after connection to th...

Страница 14: ...nfinity System Control A150172 S Format your contact information and logo if applicable using the PC MAC Desktop application available at www MyInfinityTouch Carrier com Infinity Downloads and save it...

Страница 15: ...on screen prompts S More detailed information can be found on HVACPartners com under the Product tab Thermostats Controls SYSTXCCITC01 B Documents Downloads Marketing Miscellaneous Infinity System Con...

Страница 16: ...ided in the Infinity System to simplify and automate the initial commissioning of the system S Install the Infinity System Control according to this instruction S Install indoor unit outdoor unit and...

Страница 17: ...user For accurate temperature measurement the following guidelines should be followed The Infinity System Control and Remote Room Sensors SHOULD be mounted S Approximately 5 ft 1 5 m from the floor S...

Страница 18: ...ZS1 and ZS1C connection at the Damper Control Module In either case the Infinity System Control will automatically detect the Remote Room Sensor and ignore its internal temperature sensor NOTE Humidi...

Страница 19: ...System Control Only one Smart Sensor may be used per zone They cannot be averaged like Remote Room Sensors If a Smart Sensor is used in a zone a Remote Room Sensor may also be used in the same zone Th...

Страница 20: ...that the following color code be used when wiring each device A Green Data A B Yellow Data B C White 24VAC Com D Red 24VAC Hot A B C D A03193 It is not mandatory that the above color code be used but...

Страница 21: ...s from existing control d Discard or recycle old control S NOTE Mercury is a hazardous waste if existing control contains any mercury it MUST be disposed of properly The Infinity System Control does n...

Страница 22: ...uipment and device installation instructions for details S Turn on power to equipment 4 4 1 Shielded Wire If the thermostat wiring will be located near or in parallel with high voltage wiring radio TV...

Страница 23: ...ensation The cover must be installed to prevent damage from other sources Do not locate where it will be accessible to children It may be mounted in either vertical or horizontal position Remember tha...

Страница 24: ...ackplate assembly snapped together care must be taken not to bend or break the interlocking tabs when removing 4 5 1 Decorative Backplate Sold separately a thin decorative backplate is available to hi...

Страница 25: ...wered humidifiers produce internal 24VAC in order to energize upon a switch or contact closure For this application a 24VAC N O Isolation Relay DPST MUST be used to prevent mixing the internal humidif...

Страница 26: ...the commissioning process by displaying Searching for indoor unit A12177 NOTE If the Infinity System compatible indoor equipment package unit indoor section gas furnace or fan coil cannot be found th...

Страница 27: ...S Select the appropriate unit installed then touch NEXT d AC1Stage 1 stage air conditioner d AC2Stage 2 stage air conditioner d HP1Stage 1 stage heat pump d HP2Stage 2 stage heat pump d None No outdo...

Страница 28: ...quately calculate the refrigerant charge required while in the heat pump charging screens under Refrigerant Charging Section 6 6 Select other for non Carrier evaporators 5 4 Electric Heater Selection...

Страница 29: ...t number The system will self identify that hydronic heat has been installed during electric heater selection The system will treat the hot water coil as either auxiliary heat in a heat pump applicati...

Страница 30: ...e Zoning Searching will appear on the screen to determine if any zones are present The screen will show Zone 1 Zone 2 etc and indicate all zones having either a Remote Room Sensor or smart sensors ass...

Страница 31: ...be prompted to select whether ultraviolet lights are installed in the system Select YES or NO then touch NEXT 5 10 Equipment Summary The equipment summary screen will appear after accessories have be...

Страница 32: ...static pressure in inches across the equipment at a pre determined target airflow CFM If the achieved actual CFM is unacceptably below the target CFM a yellow notice will appear to invite the user to...

Страница 33: ...the duct leakage up to and through the dampers With these static pressure measurements the system will calculate the relative size of each zone as well as the percent leakage through the dampers At t...

Страница 34: ...25 A12186...

Страница 35: ...h and hold the SERVICE icon for at least ten seconds The following screens are available in installation and service To return to the previous screen touch BACK To exit the Service menus touch DONE NO...

Страница 36: ...Service menus touch DONE Example SPP Equipment Summary Screen A13121 6 2 Installation Touch INSTALLATION to perform the start up process in order to learn all equipment in system Select FULL INSTALLA...

Страница 37: ...door and OAC HP Indoor follow Fan Coil instructions For Gas PAC Indoor and Gas PHP Indoor follow Furnace instructions For all PAC Outdoor follow AC Heat Pump instructions 6 3 Set up A13130 NOTE Depend...

Страница 38: ...r S Outdoor d AC Heat pump d Geo HP d PAC AC outdoor d PAC HP outdoor d GAS PAC outdoor d GAS PHP outdoor Once the equipment has been selected the appropriate menus will be displayed 6 3 1 Thermostat...

Страница 39: ...changeover time is grayed out and shows N A S If Simultaneous Heat Cool is turned OFF Auto changeover time Adjustable from 5 to 120 minutes d Default 30 minutes NOTE AUTO mode is intended to switch b...

Страница 40: ...e minimum difference enforced between heating and cooling desired temperatures The deadband does not change when the user changes between Fahrenheit _F and Celsius _C Ex A 2_ deadband will be 2_F or 2...

Страница 41: ...ration of the temperature and humidity sensors These offsets are added to the actual temperature humidity values When the correct offsets are made touch SAVE S Outdoor temperature Adjustable from 5 to...

Страница 42: ...o pre programmed time and temperature S User Settings Reset user settings back to pre programmed values S Install Settings Reset installation settings back to pre programmed values S Last 10 Faults Re...

Страница 43: ...eration only Smart Recovery causes the system to ramp the system target setpoints to those for the next programmed schedule period to help save energy during period transitions Smart Recovery will sta...

Страница 44: ...isable the room occupancy sensor that is in the wall control After the selection is made touch SAVE When enabled the sensor will be used to determine if the room is occupied 6 3 2 Fan Coil First touch...

Страница 45: ...of the system The EFF325 airflow is a fixed airflow used to achieve specified ratings no dehumidification airflow reduction is performed This is nominally 325 CFM ton but will vary if a 2 stage outdo...

Страница 46: ...10 000 feet This is used to correct the static pressure readings the system performs 6 3 2 3 Dehumidification The Dehum Drain Time option turns off the continuous fan at the end of cooling for five mi...

Страница 47: ...ts desired operation when the R to G contact is closed on the fan coil control board Under this function option fan turns on fan to selected fan speed when G terminal is energized Use the alert functi...

Страница 48: ...ur selection A13230 Shutdown This setup option selects the change of state required for shutdown Select Normally Open or Normally Closed and then save your selection A13231 6 3 2 6 Fan Coil G Terminal...

Страница 49: ...40 A14224 6 3 3 Furnace First touch SETUP then touch FURNACE to set up the parameters for the furnace unit A14225A...

Страница 50: ...e furnace when cooling heat pump heating and dehumidification The QUIET airflow means the minimum cooling airflow that the system can safely run typically 300 CFM ton Use this setting if duct noise is...

Страница 51: ...flow during normal cooling operation to help reduce duct sweating After the selections are made touch SAVE S Cool Quiet Comfort EFF325 or EFF1 EFF350 or EFF2 or Max d Default Comfort S HP Heat Comfort...

Страница 52: ...ing limits Maximum CFM to run a modulating furnace This will increase the maximum operating capacity of the furnace d Default value is the furnace air flow for the highest heat capacity 6 3 3 5 Furnac...

Страница 53: ...nace G Terminal This setup option selects desired operation when the R G circuit changes state on the furnace control board depending on setup Under the function option FAN turns on fan to selected fa...

Страница 54: ...r selection A13230 Shutdown This setup option selects the change of state required for shutdown Select Normally Open or Normally Closed and then save your selection 6 3 3 10 Furnace G Terminal Alert L...

Страница 55: ...Pump First touch SETUP then touch AC HEAT PUMP to set up the parameters for the AC Heat Pump unit NOTE For Geo HP setup see Sec 6 3 7 A14227A 6 3 4 1 Latching Not available for geothermal units High C...

Страница 56: ...cooling will be energized S Only Low Cool d The system will only run in low stage cooling High Heat Latch A13228 S System in Control d The system will decide which stage should be running to satisfy...

Страница 57: ...SAVE S Set Defrost Interval 30 60 90 120 minutes or AUTO d Default AUTO NOTE See Heat Pump Installation Instructions for Defrost Timing Interval when using AUTO Defrost 6 3 4 4 Low Ambient Cooling Se...

Страница 58: ...touch SAVE S AC Heat Pump Max RPM Adjustable from 4500 7000 d Default 7000 RPM 6 3 4 7 Defrost Fan Delay Turns on the outdoor unit fan at the end of a defrost cycle for approximately 12 seconds This h...

Страница 59: ...the ratings are entered touch SAVE 6 3 5 Heat Source Lockout First touch SETUP then touch HEAT SOURCE LOCKOUTS to set up the parameters for the AC Heat Pump unit For hydronic heat applications this op...

Страница 60: ...ettings for heat source but may override the settings if the preferred heat source is unable to deliver heat 6 3 6 Stages Latch for 18VS For 18VS heat pumps the cooling and heating stage latch can be...

Страница 61: ...HP unit will stop operating See the Geo HP Installation Instructions for more details Typically 26_F is chosen for open loop systems using untreated water and 15_F is chosen for closed loop systems u...

Страница 62: ...or LPS trips before the Geo HP compressor will lockout for four hours After the selection is made touch SAVE S Lockout Count 4 or 2 d Default 2 A150180 6 3 7 3 Brownout Override This option controls...

Страница 63: ...Loop Flow Rate and the Loop Pump power See the figure in Section 6 3 7 These inputs will help the Energy Tracking algorithm properly calculate geothermal heat pump usage See the geothermal heat pump...

Страница 64: ...or Right buttons to change the zone After the selection is made touch SAVE S Temperature Offset Adjustable between 5 to 5_F 3 to 3_C d Default 0_F 6 3 8 3 Airflow Limits Since a bypass damper is prohi...

Страница 65: ...t airflow Low Med Low Medium Med High High or No Limit d Default High 6 3 8 4 Duct Assessment Time NOTE The daily duct assessment will occur even if static pressure monitoring is disabled This is done...

Страница 66: ...nstaller has the option of selecting pressure monitoring the type of filter installed and the time interval for cleaning After the selections are made touch SAVE S Pressure Monitoring not available or...

Страница 67: ...installer has the option of selecting whether ultraviolet lights are installed and the time interval for changing the ultraviolet lights After the selections are made touch SAVE S UV Lights Installed...

Страница 68: ...ressor section control board to the Utility connections Utility Saver is used to force the equipment to a lower stage low or off when activated by the utility company typically during peak load times...

Страница 69: ...uch as opened or closed registers This option allows the installer to select the airflow for the fan coil when paired with a hydronic coil After the selections are made touch SAVE A12194 S Airflow Sel...

Страница 70: ...cised With self identifying electric heaters three stages of electric heat are available to be exercised in any combination Non identifying heaters will only provide one stage of heat After the select...

Страница 71: ...layed on the screen After the selections are made touch START S Hydronic heater check Selectable from 0 to 120 minutes d Default 5 minutes 6 4 4 Air Conditioning This option allows the air conditioner...

Страница 72: ...nd time can be changed by pressing the Change button on the checkout status screen After the selections are made touch START NOTE Airflows during Checkout modes are fixed to the EFFICIENCY setting and...

Страница 73: ...s are made touch START NOTE Airflows during Checkout modes are fixed to the EFFICIENCY setting and are independent of other airflow settings To view airflows for normal air conditioning cooling mode e...

Страница 74: ...pen all others will close and the indoor unit will provide the maximum airflow for that zone as selected in SETUP ZONING Airflow Limits If the airflow noise is objectionable the installer can select a...

Страница 75: ...s to change the zone under test This should be done with each zone to verify that the zone sensor corresponds to that particular zone Once each zone has been checked touch DONE to return to the ZONING...

Страница 76: ...utton labeled View Diagnostics which provides the top 3 most likely root causes for the most recent fault NOTE This feature is only available with compatible models Those models are currently the FE f...

Страница 77: ...about the furnace operation To return to the previous screen touch BACK To exit the Service menus touch DONE A12198 6 5 4 AC Status The AC status screen displays relevant information about the AC oper...

Страница 78: ...e heat pump operation To return to the previous screen touch BACK To exit the Service menus touch DONE A12200 6 5 6 Geothermal HP Status The Geo HP status screen displays relevant information about th...

Страница 79: ...xit the Service menus touch DONE A12201 6 5 8 Last 10 System Events This screen will show the last 10 events that occurred throughout the system Each entry has the time and date incident recorded Thes...

Страница 80: ...ed on the control The indoor unit and outdoor unit if communicating have the following histories To return to the previous screen touch BACK To exit the Service menus touch DONE S Resettable Faults Fa...

Страница 81: ...return to the previous screen touch BACK To exit the Service menus touch DONE A14230 6 5 11 Service Phone Number This menu item allows the installer to view the name and phone number that the homeowne...

Страница 82: ...gerant Charging Greenspeed Intelligence 18VSt 19VSt Systems For variable capacity and multi stage heat pumps and AC units a refrigerant charging menu is available to aid in the proper charging of the...

Страница 83: ...n to verify the current total charge is accurate Once the installer has confirmed touch DONE Next the installer will enter the SERVICE VALVE SUBCOOL screen This screen will show the current liquid lin...

Страница 84: ...ure in _F outdoor temperature in _F compressor discharge pressure in psig and accumulator suction pressure in psig are displayed on this screen Once the stabilization time has expired touch DONE A1428...

Страница 85: ...ode after a brief delay 6 6 3 Evacuation Because this system has an EXV for the heating expansion device additional steps must be taken to open the EXV if the heat pump unit must be evacuated for serv...

Страница 86: ...GO to upload the dealer logo and contact information from a standard micro SD card connected to the Infinity System Control The Dealer Logo Application PC MAC Desktop application download available at...

Страница 87: ...Download the program and follow the program instructions Once the dealer logo and contact information have been properly loaded onto the micro SD card insert the micro SD card into the bottom edge of...

Страница 88: ...utility events if the home owner is participating in a utility event program Selecting ON will enable the utility event icon on the main menu NOTE See the Owner s Manual for additional details regard...

Страница 89: ...r service Carrier Corporation makes no representations or warranties express or implied including to the extent permitted by applicable law any implied warranty of merchantability or fitness for a par...

Страница 90: ...d by touching ENABLED S Touch SETUP A WI FI CONNECTION to begin the process S Next touch SCAN FOR AVAILABLE ACCESS POINTS A13235 S On the next screen look for the SSID of the router access point After...

Страница 91: ...ecured network will prompt for the Wi Fi security key A13237 S If a Wi Fi network security key is shown as on the right hand picture above then select the white bar and enter the security key then sel...

Страница 92: ...ess and serial number of the Infinity System Control To find the serial number and MAC address of the Infinity System Control click on Menu Down Arrow Wireless and View MyInfinity Info This screen wil...

Страница 93: ...the home s existing router LAN port using the provided Ethernet cable The LAN ports on the back of the TP LINK Wireless Access Point should not be used for other devices The Infinity TP LINK Wireless...

Страница 94: ...the myHVACxxxxxx connection from the list then touch NEXT myHVAC is followed by the last 6 digits of your Wireless Access Point s MAC address see the label on the bottom of the TP LINK Wireless Acces...

Страница 95: ...ard will appear d The security key can be found on the back of the TP LINK Wireless Ac cess Point A12117 S The control will inform you if the connection is successful If so touch DONE d If the connect...

Страница 96: ...ber and MAC address of the Infinity System Control click on Menu Down Arrow Wireless and View My Infinity Info This screen will provide the information needed on the MyInfinity website during registra...

Страница 97: ...w White Red OAT Sensor Optional Variable Speed Furnace Fan Coil NOTE Some outdoor units do not require the C and D connections See outdoor unit Installation Instructions NOTE For SPP products ABCD con...

Страница 98: ...ommunicating AC Green Data A Yellow Data B White COM Red 24VAC Optional Remote Room Sensor HUM COM 24V Humidifier Connection Y Y2 S2 S1 OAT OAT Sensor Variable Speed Furnace Fan Coil A12354 Connection...

Страница 99: ...unicating HP Green Data A Yellow Data B White COM Red 24VAC Optional Remote Room Sensor HUM C Humidifier Connection Y S2 S1 W2 Y O C R O R W OAT OAT Sensor Variable Speed Fan Coil G A12355 Connection...

Страница 100: ...A B C D OAT Sensor Optional A B C D A B C D Damper Control module A B C D Indoor Unit Communicating AC or HP A04018 Zoning Connection for Communicating Indoor Unit with 2 Stage Communicating Outdoor...

Страница 101: ...een Yellow White Red OAT HUM COM 24V Humidifier Connection OAT Sensor A B C D A B C D Damper Control module A B C D Indoor Unit C Y 1 Stage AC Y Y2 A04019 Zoning Connection Diagram for Furnace or FE F...

Страница 102: ...reen Yellow White Red A B C D A B C D Damper Control module A B C D Variable Speed Fan Coil 1 Spd HP HUM C Y W2 Y O C R O R W OAT OAT Sensor Humidifier Connection G A07149 Zoning Connection diagram fo...

Страница 103: ...94 A160170 NIM Chart...

Страница 104: ...95 A160171 Wiring Diagram Single Stage Non Communicating Heat Pump NIM...

Страница 105: ...96 A160172 Wiring Diagram Two Stage Non Communicating Heat Pump NIM...

Страница 106: ...97 R G FE Fan Coil or Variable Speed Furnace A07114 G Input Wiring for Blower Operation...

Страница 107: ...98 R G FE Fan Coil or Variable Speed Furnace A07115 G Input Wiring for System Shutdown...

Страница 108: ...used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equi...

Страница 109: ...xempt RSS standard s Operation is subject to the following two conditions 1 this device may not cause interference and 2 this device must accept any interference including interference that may cause...

Страница 110: ...101 NOTES...

Страница 111: ......

Страница 112: ...ks of their respective holders Wi Fi is a registered trademark of Wi Fi Alliance Corporation Copyright 2017 Carrier Corp S 7310 W Morris St S Indianapolis IN 46231 Edition Date 02 17 Manufacturer rese...

Отзывы: