4.8.1 - Optional balancing valves
Two-way valve with waterflow balancing function is embedded with a differential pressure controller (with or without
pressure test points to control the waterflow settings). The setting of the valve is shown in Fig. 16.
The manual control knob (16a) is ready fitted to protect valve stem and pre-set mechanism and facilitates manual
control of valve during commissioning.
Setting procedure:
■ Remove control knob from the valve (16a)
■ Loosen knurled nut (16b).
■ Adjust the desired dial setting with the white knob (16c)
-
See table below.
■ Retighten knurled nut by hand (16d).
Waterflow to adjust [l/h]
1/2’ valve
Not Standard
3/4’ valve
Available
1’’ valve
Available
Available
ON/OFF actuator
Not Standard
Available
Available
Moduling / 3p actua.
Not Standard
Available
Available
Waterflow range :
200 l/h (*)
600 l/h (*)
1200 l/h (*)
1600 l/h (*)
MINI
NA
NA
NA
NA
0,2
NA
NA
NA
NA
0,4
NA
NA
NA
NA
0,5
30
100
NA
NA
0,6
35
115
200
220
0,8
40
130
260
290
1
50
160
310
250
1,2
60
180
380
420
1,4
70
210
430
480
1,6
80
240
490
550
1,8
90
270
550
610
2
100
300
610
680
2,2
110
320
660
740
2,4
120
350
730
810
2,6
130
380
780
870
2,8
140
410
840
940
3
150
440
900
1000
3,2
160
460
960
1070
3,4
170
490
1010
1130
3,6
180
520
1070
1200
3,8
190
550
1130
1260
MAX
200
575
1190
1330
(*): Maximum specified water flow on the valve body
WARNING: The valves have to be open when flushing or pressure testing the system. Strong pressure
impacts can damage closed valves.
Differential pressure across the valve’s control path is not allowed to exceed 400 kPa.
4 - COMPONENTS AND MAINTENANCE
20
Содержание Idrofan 42NH
Страница 2: ......
Страница 6: ... 0 5 0 5 9a 9b L 11a 11a K 10a 10b M 12b 12a N 13a 13a 6 ...
Страница 7: ...O Ø16 26 Ø16 4w v 2w v 2w v B 40 40 40 B B B G G G C C C C C H D I E J F F F F K 7 ...
Страница 8: ...R BAS 60 50 75 100 70 80 90 DOWN 17a 17b 17c Q 16a 16b 16c 16d P 15a 15b 15d 15c 15e 8 ...
Страница 9: ...S 18a 9 ...
Страница 23: ......