Condensate drain pipe (Fig. 10): Use a flexible pipe with 

an inside diameter of 16 mm and provide a constant fall 

of 20 mm/m over the whole horizontal pipe run. Install 

a 50 mm (minimum) siphon to prevent gases and odours 

from flowing back into the ceiling void.

WARNING: After drain pipe connection, control 

clamping of the drain pipe and be sure there is no 

water leakage.

If several units are connected to a common collector, a 

device must be installed (Fig. 11). Before operating the 

unit,  ensure  that  the  water  flows  into  the  internal 

condensate drain pan by pouring some water into it. If 

problems are detected, check the drain pipe slope and 

look for possible obstructions. In all cases the 

connection duct(s) at the unit outlet must be insulated 

to prevent any condensate formation on the walls.

NOTE: The pressure losses of these ducts must be 

compatible  with  the  unit  performance.  The  duct 

must be as smooth as possible. Avoid sharp bends. 

Check that there are no leaks or kinks, and that there 

is  no  dirt  or  installation  debris  inside  the  ducts. 

Debris within the ducts might damage the fan wheel 

and the damper in the air diffusers.

When  installation  is  complete  -  i.e.  when  the  unit  is 

attached to the ceiling, air ducts are complete, water 

mani-folds are in position with stop valves ready on the 

connection stubs, and electrical installation is prepared 

- then connect the water pipe (1/2” gas screw connector 

for size 2 to 5 ; 3/4” gas screw connector for size 6 and 

7).

WARNING: Be sure that the coil protective caps are 

removed before connecting the water pipes (see 

Fig. 19). 

NOTE : Each fan-coil units shall be connected with 

water flexible pipes in order to avoid any damage 

due to vibrations.

Ensure that a gasket (not supplied by Carrier) is installed 

between the screw connector and the stop valve.

When all units are installed, open the stop valves on 

the manifolds, bleed and then pressurize the circuits. 

To bleed the coils, slightly loosen the bleed screws. The 

installation can then be started.

NOTE:  Do  not  switch  on  the  power  until  all 

connections are made and earthed.

3.3 - 

Removal procedure

Switch  off  the  unit  power  supply  at  the  isolator 

provided for the purpose during installation (isolator 

not supplied by Carrier).

 

■ Disconnect the power supply and connection cables.

 

Close the isolating valves on the manifolds.

 

■ Disconnect the flexible water pipes by unscrewing 

the gas connectors.

WARNING:  Since  the  flexible  water  pipes  do  not 

have drain valves, a receiver must be provided to 

allow the cooling coil to be drained.

 

Disconnect the supply air ducts.

 

■ Disconnect the flexible condensate drain pipe. Drain 

the siphon into a suitable vessel.

 

■ Support the unit lightly and release it by unscrewing 

the four nuts on the threaded hangers. Lower the unit 

carefully.

3.4 - 

Safety considerations relating to 

final shut-down

Separate the units from their energy sources, allow them 

to cool down and then drain completely.

DISMANTLING: see §3.3.

Respect the local environmental laws and regulations.
Presence of waste electrical and electronic equipment 

(WEEE): At the end of its life, units must be disassembled, 

with any contaminated fluids removed by professionals, 

and then processed via approved channels for waste 

electrical and electronic equipment (WEEE).
Check whether any part of the unit can be recycled for 

another purpose.
Sort the components according to their material for 

recycling or disposal, in accordance with regulations in 

force.
Materials to be recovered for recycling - Steel - Copper 

- Brass - Aluminium - Plastics - Insulation.
The proportions of materials for each unit are listed in 

the Product Environmental  Profile (PEP) available  at 

the following website: http://www.pep-ecopassport.org/

fr/consulter-les-pep/ or on request from our departments.
Any contaminated fluids must be disposed of by 

specialist professionals.

3 - INSTALLATION OF THE UNIT

16

Содержание Idrofan 42NH

Страница 1: ...Translation of the original document DUCTED FAN COIL UNITS 42NL 42NH INSTALLATION OPERATING AND M A I N T E N A N C E I N S T R U C T I O N S ...

Страница 2: ......

Страница 3: ...Installing the unit in the false ceiling 15 3 2 Installation procedure 15 3 3 Removal procedure 16 3 4 Safety considerations relating to final shut down 16 4 COMPONENTS AND MAINTENANCE 17 4 1 Fan motor assembly 17 4 2 Drain pan removal 18 4 3 Water coil 18 4 4 Duct connection spigots 18 4 5 Duct connection rectangular flanges 18 4 6 Optional filter and filter access 19 4 7 Fresh air controller 19 ...

Страница 4: ...2NH L size 4 1114 300 50 42NH L size 5 1314 300 50 42NH L size 6 1314 345 50 42NH L size 7 1614 345 50 B C A B A B 42NH L size 2 744 300 42NH L size 3 914 300 42NH L size 4 1114 300 42NH L size 5 1314 300 42NH L size 6 1314 345 42NH L size 7 1614 345 C A B 4 ...

Страница 5: ...A B 42NH L size 2 744 300 42NH L size 3 914 300 42NH L size 4 1114 300 42NH L size 5 1314 300 42NH L size 6 1314 345 42NH L size 7 1614 345 D A B E F G H I 0 5 5 ...

Страница 6: ... 0 5 0 5 9a 9b L 11a 11a K 10a 10b M 12b 12a N 13a 13a 6 ...

Страница 7: ...O Ø16 26 Ø16 4w v 2w v 2w v B 40 40 40 B B B G G G C C C C C H D I E J F F F F K 7 ...

Страница 8: ...R BAS 60 50 75 100 70 80 90 DOWN 17a 17b 17c Q 16a 16b 16c 16d P 15a 15b 15d 15c 15e 8 ...

Страница 9: ...S 18a 9 ...

Страница 10: ...4w v 9 Water outlet of 2w v 10 Water outlet of 2w v B 2w v Two way valve 2w v B Two way valve and balancing function 4w v Four way valve Three way valve with integral by pass Connections for two way valve with balancing function Size 2 and 3 3 4 diameter Size 4 and 5 1 diameter Connections for other valves and coils Size 2 3 4 and 5 1 2 diameter Size 6 and 7 3 4 diameter 15 Meaning of wires propor...

Страница 11: ...haracter may be present The copper aluminium coil or components inside the unit could suffer irreparable corrosion damage in their presence 1 1 4 Recommended coil water quality At installation handover and then periodically every year it is advised to analyse the water for bacteria detection of ferro bacteria H2S producing and sulphate reducing bacteria and chemicals in order to avoid problems due...

Страница 12: ... 60 or 50 Hz 1ph 60Hz not available for 42NH3_5 NOTE All performances data certified by Eurovent are based on 50Hz application Carrier doesn t ensure the same performances when the unit operates at 60Hz the RPM and power input of the fan motor are usually higher WARNING Failure to take proper account of the above advice and unauthorised modification of the electrical connections will render the Ca...

Страница 13: ...tic compatibility in residential commercial and light industrial areas They also comply with the low voltage directive If the product is supplied without a Carrier control device verification of EMC conformity is the responsibility of the installer 2 3 General installation conditions IMPORTANT The Carrier numeric controller power module or in general units fitted with controls loops must have an i...

Страница 14: ...4 Caution for the control of the unit IMPORTANT It is not permitted to connect several units to the same control device electronic NTC controller WTC controller or any other third party controller Carrier electronic Thermostat type A B for AC motors require additional accessory board to allow master slave function Carrier electronic Thermostat type C D for EC motors can be connected upto 10 units ...

Страница 15: ...ts need to be installed it may be advisable to produce a drilling template The method of fixing the threaded hangers not supplied by Carrier depends on the ceiling type maximum diameter of the threaded hangers is 10 mm Once the threaded hangers are fixed to the ceiling tighten the first nuts WARNING When moving the units do not use water pipes condensate drain pan valves or flexible pipes to lift ...

Страница 16: ...alled open the stop valves on the manifolds bleed and then pressurize the circuits To bleed the coils slightly loosen the bleed screws The installation can then be started NOTE Do not switch on the power until all connections are made and earthed 3 3 Removal procedure Switch off the unit power supply at the isolator provided for the purpose during installation isolator not supplied by Carrier Disc...

Страница 17: ...Disconnect the capacitor by withdrawing the flat spade connectors from the back of the capacitor Replacement of the capacitor assembly is by the reversal of the above procedure 4 1 3 Fan wiring For any modifications of the wiring harness refer to the fan wiring diagrams provided with the units With the optional electrical box three of the available five or six speeds of AC motor are connected maxi...

Страница 18: ... fixing screws Pull out the drain pan and coil assembly the drain pan remains attached to the unit for approximately 100 mm until the coil is completely detached Then remove the coil from the drain pan Replacement is by the reversal of the procedure described above Ensure that all gaskets are changed new gaskets fitted and that the inlet and outlet connections to the coil are made correctly using ...

Страница 19: ...f the supply air flow delivered by the unit at minimum speed NOTE To operate correctly the constant fresh air flow controller requires a differential pressure in the range of 60 Pa to 210 Pa 4 7 2 Fresh air controller with variable air volume The unit can be equipped with a variable fresh air flow controller from 0 to 55 l s 0 to 200 m3 h This is connected to the numeric Carrier controller and can...

Страница 20: ...lable ON OFF actuator Not Standard Available Available Moduling 3p actua Not Standard Available Available Waterflow range 200 l h 600 l h 1200 l h 1600 l h MINI NA NA NA NA 0 2 NA NA NA NA 0 4 NA NA NA NA 0 5 30 100 NA NA 0 6 35 115 200 220 0 8 40 130 260 290 1 50 160 310 250 1 2 60 180 380 420 1 4 70 210 430 480 1 6 80 240 490 550 1 8 90 270 550 610 2 100 300 610 680 2 2 110 320 660 740 2 4 120 3...

Страница 21: ... to the valve body maximum torque 15 N m 4 8 5 Valve body replacement procedure Disconnect the power supply before carrying out any work on a unit Close the isolating valves on the manifolds Unscrew the union nuts to disconnect the flexible water pipes Remove the valve actuators taking care to identify the cooling and heating valves Disconnect the flexible condensate drain pipe which is held in pl...

Страница 22: ... above 1400 W capacity All units delivered with an electrical box or a Carrier controller are always equipped with a relay if the capacity of the electrical heater is above 1400W WARNING In case of customer supplied controller it is the responsability of the installer to set up an additional protection relay corresponding to the electrical heater capacity 4 11 Optional water sensor A water tempera...

Страница 23: ......

Страница 24: ... 08 2022 Manufacturer Carrier S C S Rte de Thil 01120 Montluel France Supersedes order No X 00DCG000132000D 09 2017 Manufacturer reserves the right to change any product specifications without notice Printed in the European Union ...

Отзывы: