1 - PRECAUTIONS
Only specially trained and qualified technicians
and installers who have been fully trained on the
product concerned are authorized to install, to
commission and service this equipment.
In particular it is obligatory to disconnect all
power supplies to the unit and its accessories
before carrying out any work.
1.1 -
Operating limits
1.1.1 -
Cooling mode
Cooling mode - Operating Limits
Water circuit
Min. inlet Temperature >5°C ethylene /
propylene glycol rate < 40% Water side
pressure < 15,5 bar (1550 kPa)
Ambient
temperature and
humidity
T < 27°C / 65% relative humidity or
humidity weight < 14,7 g/kg dry air
Supply air
temperature
T > 12°C with maximum ambient humidity
conditions (14,7 g/kg dry air)
1.1.2 -
Heating mode
Heating mode - Operating Limits
Water circuit
Max. inlet Temperature < 80°C ethylene /
propylene glycol rate < 40% Water side
pressure < 15,5 bar (1550 kPa)
Ambient
temperature and
humidity
T < 40°C
Supply air
temperature
T < 60°C with supply plenum and spigots
application
1.1.3 -
Operating environment
The 42NH / 42NL has been designed for indoor
application in ‘urban’ conditions having a non-corrosive,
dust-free and non-marine environment.
The concentrations of the following chemicals must not
be exceeded in any event:
■
SO
2
< 0.02 ppm
■
H
2
S
< 0.02 ppm
■
NO, NO
2
< 1 ppm
■
NH
3
< 6 ppm
■
N
2
O
< 0.25 ppm
Do not install a unit where flammable gases or products
of an acidic or alkaline character may be present. The
copper/aluminium coil or components inside the unit
could suffer irreparable corrosion damage in their
presence.
1.1.4 -
Recommended coil water quality
At installation handover, and then periodically every
year, it is advised to analyse the water for bacteria
(detection of ferro-bacteria, H
2
S-producing and
sulphate-reducing bacteria) and chemicals (in order to
avoid problems due to corrosion and scaling).
The water circuit must include all the necessary
elements for the treatment of the water: filters, additives,
intermediate exchangers, purges, drains, isolating
valves, etc., according to the analysis results.
The results must be in accordance with the values
shown below:
■ Total hardness in mmol/l: 1 < mmol/l < 1.5
■
Chloride [CL
-
]
< 10 mg/litre
■
Sulphate [SO
4
2-
]
< 30 mg/litre
■
Nitrate [NO
3
-
]
= 0 mg/litre
■ Dissolved iron:
< 0.5 mg/litre
■ Dissolved oxygen:
4 < [O
2
] < 9 mg/litre
■
Carbon dioxide [CO
2
]
< 30 mg/litre
■ Resistivity:
20 Ohm·m< Resistivity
< 50 Ohm·m
■ pH:
6.9 < pH < 8
1.2 - Clearances required
Without rectangular flange inlet : Fig.1
With rectangular flange inlet
: Fig.2
With plenum
: Fig.2 and Fig. 3
NOTE : All informations about dimensions and
weights are available in the PSD documentation on
Carrier Webportal
1.3 -
Receiving a shipment -
installation methods
When receiving a shipment, check the condition of the
goods and report any damage in transit to the shipping
company. Do not unpack the units until just before they
are due to be installed, and make sure they are as close
as possible to the installation site when unpacking them.
Do not place heavy articles of any sort on them.
11
Содержание Idrofan 42NH
Страница 2: ......
Страница 6: ... 0 5 0 5 9a 9b L 11a 11a K 10a 10b M 12b 12a N 13a 13a 6 ...
Страница 7: ...O Ø16 26 Ø16 4w v 2w v 2w v B 40 40 40 B B B G G G C C C C C H D I E J F F F F K 7 ...
Страница 8: ...R BAS 60 50 75 100 70 80 90 DOWN 17a 17b 17c Q 16a 16b 16c 16d P 15a 15b 15d 15c 15e 8 ...
Страница 9: ...S 18a 9 ...
Страница 23: ......