6.1.3
Control Unit (Pre-Alarm, Slowdown/Shutdown and Backup Alarm or Fault Relay Cable
Replacement (Supplied by Others)
1.
Switch off the system.
2.
Remove the Control Unit Lid by removing the 4 screws
3.
Disconnect the damaged relay cable from the Control Unit.
4.
Disconnect the damaged relay cable from the monitoring equipment.
5.
Connect the replacement relay cable to the Control Unit ensuring it is screwed in place.
6.
Connect the replacement relay cable to the monitoring equipment.
7.
Switch the system on and allow it to initialise.