28
Table 10 — 09DP Electrical Data — Low Sound Fan (cont)
LEGEND
1. Units are suitable for use on electrical systems where voltage
supplied to the unit terminals is not below or above the listed
minimum and maximum limits. Maximum allowable phase
imbalance is voltage 2% and amps 10%.
2. All units or modules have single point primary power connec-
tion. Main power must be supplied from a field-supplied
disconnect.
3. All terminal block units should be capable of handling 14 AWG
to 2 AWG.
4. Disconnect units with MOCP of greater than 40 require 8 AWG
to 1 AWG.
5. Disconnect units with MOCP less than 40 require 14 AWG to 6
AWG.
6. For all high short circuit capable FIOP units, fuses must be
used for overload protection.
Table 11 — Unit Incoming Power Options
LEGEND
NOTES:
1. Terminal block high SCCR option units must use approved
fuses to meet high SCCR rating.
2. High SCCR disconnect option units can use either approved
fuse or circuit breaker for incoming power protection.
3. Time delay fuse type required.
09DP UNIT SIZE
V-Ph-Hz
SUPPLY VOLTAGE
CONDENSER FAN
MCA
MOCP
Min
Max
TOTAL QTY
FLA
065
208/230-3-60
187
254
4
6.0
25.5
30
380-3-60
342
418
3.9
16.6
20
460-3-60
414
506
2.9
12.3
15
575-3-60
518
632
2.4
10.2
15
380/415-3-50
342
440
2.9
12.3
15
075
208/230-3-60
187
254
5
6.0
31.5
35
380-3-60
342
418
3.9
20.5
25
460-3-60
414
506
2.9
15.2
20
575-3-60
518
632
2.4
12.6
15
380/415-3-50
342
440
2.9
15.2
20
085
208/230-3-60
187
254
6
6.0
37.5
40
380-3-60
342
418
3.9
24.4
25
460-3-60
414
506
2.9
18.1
20
575-3-60
518
632
2.4
15.0
15
380/415-3-50
342
440
2.9
18.1
20
095
208/230-3-60
187
254
6
6.0
37.5
40
380-3-60
342
418
3.9
24.4
25
460-3-60
414
506
2.9
18.1
20
575-3-60
518
632
2.4
15.0
15
380/415-3-50
342
440
2.9
18.1
20
115
208/230-3-60
187
254
7
6.0
43.5
45
380-3-60
342
418
3.9
28.3
30
460-3-60
414
506
2.9
21.0
25
575-3-60
518
632
2.4
17.4
20
380/415-3-50
342
440
2.9
21.0
25
130
208/230-3-60
187
254
8
6.0
49.5
50
380-3-60
342
418
3.9
32.2
35
460-3-60
414
506
2.9
23.9
25
575-3-60
518
632
2.4
19.8
20
380/415-3-50
342
440
2.9
23.9
25
AWG
—
American Wire Gage
FIOP
—
Factory-Installed Option
FLA
—
Full Load Amps
MCA
—
Minimum Circuit Amps, complies with NEC, Article 430-24
MOCP —
Maximum Overcurrent Protection (Amps)
NEC
—
National Electrical Code
MOCP VALUE
UNIT INCOMING POWER OPTION
Standard Terminal
Block Option
High SCCR Terminal Block Option
Standard and High SCCR
Disconnect Option
Max
Wire Size
Min
Wire Size
Max
Wire Size
Min
Wire Size
High SCCR
Fuse Type
Max Wire Size
Min
Wire Size
100 A or less
2/0 AWG
14 AWG
2/0 AWG
6 AWG
J, RK1, or RK5
1/0 AWG
14 AWG
Greater than
100 A and Less than
or Equal to 200 A
2/0 AWG
14 AWG
2/0 AWG
6 AWG
J or RK1
350 kcmil
6 AWG
Greater than 200
600 kcmil
2 AWG
600 kcmil
3/0 AWG
J or RK1
500 kcmil (1)
500 kcmil (2)
3/0 AWG
AWG
—
American Wire Gage
kcmil
—
Thousand Circular Mills
MOCP —
Maximum Overcurrent Protection
SCCR —
Short Circuit Current Rating